2

Type MR108

have accumulated. To prevent such 

injury or damage, provide piping or 

tubing to vent the fluid to a safe,  

well-ventilated area or containment 

vessel. Also, when venting a 

hazardous fluid, the piping or tubing 

should be located far enough away 

from any buildings or windows so to 

not create a further hazard and the 

vent opening should be protected 

against anything that could clog it.
Personal injury, equipment damage 

or leakage due to escaping fluid 

or bursting of pressure-containing 

parts may result if this backpressure 

regulator is overpressured or is 

installed where service conditions 

could exceed the limits given in 

the Specifications section or where 

conditions exceed any ratings of the 

adjacent piping or piping connections.
To avoid such injury or damage, 

provide pressure-relieving or pressure-

limiting devices (as required by 

the appropriate code, regulation or 

standard) to prevent service conditions 

from exceeding limits. Additionally, 

physical damage to the backpressure 

regulator could result in personal 

injury and property damage due to 

escaping fluid. To avoid such injury 

and damage, install the backpressure 

regulator in a safe location.

Clean out all pipelines before installation of the 

backpressure regulator and check to be sure the 

backpressure regulator has not been damaged or 

has collected foreign material during shipping. For 

NPT bodies, apply pipe compound to the external 

pipe threads. For flanged bodies, use suitable line 

gaskets and approved piping and bolting practices.
Vertical installation with the actuator oriented up 

or down is recommended. The unit will operate in 

horizontal installation with actuator on the side, 

however, this could result in premature wear of parts.   

Make sure that flow will be in the same direction as 

that indicated by the body arrow. Orientation of the 

two vents should always be down. Vents may be 

rotated after regulator installation so that the vent 

screens are down. 
A control line must be installed to allow inlet pressure 

to register on the actuator’s diaphragm. It should 

be installed four to eight pipe diameters upstream 

of the regulator and in an area of pipe that is free 

of turbulence.

Note

It is important that the backpressure 

regulator be installed so that the vent 

hole in the spring case is unobstructed 

at all times. For outdoor installations, 

the backpressure regulator should be 

located away from vehicular traffic and 

positioned so that water, ice and other 

foreign materials cannot enter the 

spring case through the vent. Avoid 

placing the backpressure regulator 

beneath eaves or downspouts and 

be sure it is above the probable 

snow level.

Overpressure Protection

Maximum inlet pressures depend upon body end 

connections, materials and temperatures. Refer 

to the nameplate for the maximum inlet pressure 

of the valve. The valve should be inspected for 

damage after any overpressure condition. 

Fisher

®

 

backpressure regulators are NOT ASME safety 

relief valves.

Startup

The backpressure regulator is factory set at 

approximately the midpoint of the spring range 

or the pressure requested. If a pressure setting 

other than specified is desired, be sure to change 

the pressure setting by following the Adjustment 

section. With proper installation completed, slowly 

open the upstream and downstream shutoff valves 

(if applicable).

Adjustment

To change the control pressure, loosen the locknut 

and turn the adjusting screw clockwise to increase 

pressure or counterclockwise to decrease pressure. 

Monitor the control pressure with a test gauge during 

the adjustment. Tighten the locknut to maintain the 

desired setting.

Taking Out of Service (Shutdown)

!

WARNING

To avoid personal injury 

resulting from sudden release of 

pressure, isolate the backpressure 

regulator from all pressure before 

attempting disassembly.

Содержание FISHER MR108 Series

Страница 1: ...FKM Diaphragm 10 3 bar 150 psig Temperature Capabilities 1 Nitrile NBR 29 to 82 C 20 to 180 F Fluorocarbon FKM 7 to 121 C 20 to 250 F 4 Ethylene Propylene EPDM 29 to 107 C 20 to 225 F 6 Maximum Emergency Casing Pressures 1 7 Low Pressure Actuator 4 8 bar 70 psig High Pressure Actuator 27 6 bar 400 psig 5 Maximum Inlet Pressures 1 7 Low Pressure Actuator 4 8 bar 70 psig High Pressure Actuator 27 6 ...

Страница 2: ...the body arrow Orientation of the two vents should always be down Vents may be rotated after regulator installation so that the vent screens are down A control line must be installed to allow inlet pressure to register on the actuator s diaphragm It should be installed four to eight pipe diameters upstream of the regulator and in an area of pipe that is free of turbulence Note It is important that...

Страница 3: ...ator 16 required High Pressure Actuator 8 required 58 Hex Nut Low Pressure Actuator Steel 16 required Stainless steel 16 required High Pressure Actuator Steel 8 required Stainless steel 16 required 60 Bonnet O ring 61 Bonnet 62 Lower Diaphragm Casing 63 Upper Diaphragm Casing 64 Upper Casing O ring 65 Cap Screw 10 required 66 Spring Case Spacer 67 Cap Screw 6 required 68 Control Spring Figure 1 Ty...

Страница 4: ...1 8100 Natural Gas Technologies Emerson Process Management Regulator Technologies Inc USA Headquarters McKinney Texas 75070 USA Tel 1 800 558 5853 Outside U S 1 972 548 3574 Asia Pacific Singapore 128461 Singapore Tel 65 6770 8337 Europe Bologna 40013 Italy Tel 39 051 419 0611 Chartres 28008 France Tel 33 2 37 33 47 00 Middle East and Africa Dubai United Arab Emirates Tel 971 4811 8100 TESCOM Emer...

Отзывы: