Emerson Fisher LR125 Series Скачать руководство пользователя страница 3

3

Type LR125

BODY SIZE

DIAPHRAGM 

MATERIAL

MAXIMUM OPERATING  

INLET PRESSURE

(4)

MAXIMUM OPERATING 

DIFFERENTIAL PRESSURE

(3)(4)

MAXIMUM EMERGENCY INLET 

AND DIFFERENTIAL PRESSURE

MAIN SPRING COLOR

DN

NPS

bar

psig

bar

psig

bar d

psid

25

1

17E68 Nitrile (NBR)

20.7

300

20.7

300

20.7

300

Black and Yellow

17E97 Nitrile (NBR)

20.7

300

20.7

300

20.7

300

Black and Yellow

41.4

600

41.4

600

41.4

600

Black and White

(2)

17E88  

Fluorocarbon (FKM)

20.7

300

20.7

300

20.7

300

Black and Yellow

41.4

600

34

500

41.4

600

Black and White

(2)

50

2

17E68 Nitrile (NBR)

20.7

300

20.7

300

20.7

300

Green and White

17E97 Nitrile (NBR)

20.7

300

20.7

300

20.7

300

Green and White

41.4

600

41.4

600

41.4

600

Purple

(2)

17E88  

Fluorocarbon (FKM)

20.7

300

20.7

300

20.7

300

Green and White

41.4

600

34

500

41.4

600

Purple

(2)

80

3

17E68 Nitrile (NBR)

20.7

300

20.7

300

20.7

300

Light Blue and White

17E97 Nitrile (NBR)

20.7

300

20.7

300

20.7

300

Light Blue and White

41.4

600

41.4

600

41.4

600

Black

(2)

17E88  

Fluorocarbon (FKM)

20.7

300

20.7

300

20.7

300

Light Blue and White

41.4

600

34

500

41.4

600

Black

(2)

100

4

17E68 Nitrile (NBR)

20.7

300

20.7

300

20.7

300

Green and White

17E97 Nitrile (NBR)

20.7

300

20.7

300

20.7

300

Green and White

41.4

600

41.4

600

41.4

600

Red

(2)

17E88  

Fluorocarbon (FKM)

20.7

300

20.7

300

20.7

300

Green and White

41.4

600

34

500

41.4

600

Red

(2)

1. See Table 1 for main valve structural design ratings and Table 2 for pilot ratings.

2. The black and white, purple, black and red springs are only recommended for applications where the maximum inlet pressure can exceed 20.7 bar / 300 psig.

3. Maximum differential pressures may be lower for applications where cavitation may be present.

4.  These are recommendations that provide the best regulator performance for a typical application. Please contact your local Sales Office for further information if a deviation from the 

standard recommendations are required.

Table 5.

 Main Valve Maximum Pressure Ratings, Diaphragm Selection Information and Main Spring Selection

(1)

Overpressure Protection

The recommended pressure limitations are 

stamped on the regulator nameplate. Some type of 

overpressure protection is needed if the actual inlet 

pressure exceeds the maximum operating outlet 

pressure rating. Overpressure protection should 

also be provided if the regulator inlet pressure 

is greater than the safe working pressure of the 

downstream equipment.
Regulator operation below the maximum pressure 

limitations does not preclude the possibility of 

damage from external sources or debris in the line. 

The regulator should be inspected for damage after 

any overpressure condition.

Startup

The regulator is factory set at approximately 

the midpoint of the spring range or the pressure 

requested, so an initial adjustment may be required 

to give the desired results. With proper installation 

completed and relief valves properly adjusted, 

slowly open the upstream and downstream 

shutoff valves.

Adjustment

To change the outlet pressure, loosen the jam nut 

and turn the adjusting screw clockwise to increase 

outlet pressure or counterclockwise to decrease it. 

Monitor the outlet pressure with a test gauge during 

the adjustment. Tighten the jam nut to maintain the 

desired setting.

Taking Out of Service (Shutdown)

!

WARNING

To avoid personal injury resulting from 

sudden release of pressure, isolate the 

regulator from all pressure before 

attempting disassembly.

Table 6.

 Main Valve Minimum Differential Pressure

(1)

MAIN VALVE BODY SIZE

MAIN SPRING PART NUMBER AND COLOR

DIAPHRAGM MATERIAL

MINIMUM DIFFERENTIAL, PERCENT OF CAPACITY

For 90% Capacity

For 100% Capacity

DN

In.

bar d

psid

bar d

psid

25

1

GE12727X022, Black and Yellow

17E68 and 17E88

2.1

30

2.1

30

17E97

2.5

35

2.5

35

19B2401X022, Black and White

17E88 and 17E97

3.0

43

3.0

43

50

2

18B2126X022, Green and White

17E68 and 17E88

1.2

18

1.3

19

17E97

1.7

24

1.7

24

18B5955X012, Red

17E88 and 17E97

2.0

29

2.1

31

80

3

19B0781X022, Light Blue and White

17E68 and 17E88

1.5

21

1.9

28

17E97

1.6

23

1.6

23

19B0782X022, Black and White

17E88 and 17E97

2.2

32

2.6

38

100

40

18B8501X022, Green and White

17E68 and 17E88

1.1

16

2.1

30

17E97

1.1

16

2.3

34

18B8502X022, Red and White

17E88 and 17E97

1.5

21

2.8

40

1. See Table 1 for Type LR125 main valve structural design ratings and Table 2 for pilot rating.

Содержание Fisher LR125 Series

Страница 1: ...velops in the system it indicates that service is required Failure to take the regulator out of service immediately may create a hazardous condition Personal injury equipment damage or leakage due to escaping fluid or bursting of pressure containing parts may result if this regulator is overpressured or is installed where service conditions could exceed the limits given in the Specifications secti...

Страница 2: ...0 7 bar 300 psig 20 7 bar 300 psig 20 7 bar 300 psig Type MR95HP 1 2 NPT Steel Stainless steel 41 4 bar 600 psig 41 4 bar 600 psig 41 4 bar 600 psig 37 9 bar 550 psig 1 The pressure temperature limits in this Installation Guide and any applicable standard or code limitation should not be exceeded 2 Temperature and or the body end connection may decrease these maximum pressures Table 3 Outlet Contr...

Страница 3: ...essure limitations are stamped on the regulator nameplate Some type of overpressure protection is needed if the actual inlet pressure exceeds the maximum operating outlet pressure rating Overpressure protection should also be provided if the regulator inlet pressure is greater than the safe working pressure of the downstream equipment Regulator operation below the maximum pressure limitations does...

Страница 4: ...Y SIZE 3 24 26 25 22 15 4 6 18 16 63 12 28 9 130 1 23 21 20 19 17 2 14 L2 5 70 10 11 129 7 8 L1 L1 L1 L2 L1 L1 Parts List Type LR125 Main Valve Key Description 1 Valve Body 2 Bonnet Assembly 3 Cap Screw 4 Hex Nut 5 Top Plug 6 O ring 7 Cage 8 Cage O ring 9 Diaphragm 10 O ring 11 Bottom Plug 12 Main Valve Spring 13 Flanged Hex Nut 14 Top Plug O ring 15 Stem 16 Back up Ring 17 Upper Spring Seat 18 O ...

Страница 5: ... Screw 16 Cap Screw 17 Jam Nut 18 Nameplate Drive Screw 26 Inner Valve Spring 63 Bottom Plug Seal Recommended spare part GF04914 APPLY LUBRICANT SEALANT 1 L1 GENERAL PURPOSE PTFE OR LITHIUM GREASE L2 ANTI SEIZE COMPOUND 1 Lubricant and sealant must be selected such that they meet the temperature requirements 2 Apply L2 anti seize compound on key 16 for Stainless steel bolts L2 L2 L2 L1 L2 15 17 8 ...

Страница 6: ...intenance of any Emerson Process Management Regulator Technologies Inc product remains solely with the purchaser Industrial Regulators Emerson Process Management Regulator Technologies Inc USA Headquarters McKinney Texas 75070 USA Tel 1 800 558 5853 Outside U S 1 972 548 3574 Asia Pacific Shanghai 201206 China Tel 86 21 2892 9000 Europe Bologna 40013 Italy Tel 39 051 419 0611 Middle East and Afric...

Отзывы: