2502 Series Controllers
Instruction Manual
Form 1446
November 2006
22
AV2323-A
AV2322-A
B0995-2/IL
SEAL
SCREW
SEAL
SCREW
RING
SEAL
SCREW
SEAL
SCREW
RING
FLAPPER
HOOK
FLAPPER
HOOK
PROPORTIONAL
TUBING
RESET
TUBING
RESET
TUBING
PROPORTIONAL
TUBING
RESET
VALVE
RESET
VALVE
SEAL
SCREW
RINGS
SEAL
SCREWS
TO RELAY
TO RELAY
TO
PROPORTIONAL
VALVE
TO
PROPORTIONAL
VALVE
DIRECT ACTING—RIGHT HAND MOUNTING
REVERSE ACTING—LEFT HAND MOUNTING
REVERSE ACTING—RIGHT HAND MOUNTING
DIRECT ACTING—LEFT HAND MOUNTING
Figure 13. Nozzle, Flapper, and Tubing Arrangements
for Various Actions and Mountings
4. Install a new gasket, the replacement relay if
necessary, and both mounting screws. Reconnect
the tubing. On a controller with indicator assembly,
slide the base plate under the two lower screws of
the relay case, align the plate so that the pointer will
read properly, and tighten the screws.
Replacing Bellows
Key numbers are shown in figure 14.
1. To gain access to the lower bellows, remove the
relay according to the Changing Relay section.
2. Remove the upper and lower bellows frame
screws (key 96) that hold both bellows assemblies to
the bellows frame. Unscrew each bellows from the
spacer (key 98), being careful not to lose the O-ring
(key 57, not shown) from the spacer end of the
bellows.
3. Inspect each bellows and O-ring and replace if
necessary, using an unpainted bellows for a 0.2
to 1.0 bar (3 to 15 psig) range and a red bellows for
a 0.4 to 2.0 bar (6 to 30 psig) range. Be sure to
install the O-ring at the spacer end of the bellows.
4. Install each bellows by screwing it down over the
stud (key 97, not shown) protruding from each end
of the spacer. Secure with a bellows frame screw,
and install the relay according to the Changing Relay
section.
5. Perform the calibration procedure and any other
necessary part of the calibration sequence.
Reversing Action
Note
The following procedure will be
necessary to restore previous action if
the mounting method has been
changed. Key numbers are shown in
1. Remove two screws (keys 63 and 64), two seal
rings (key 55), and the nozzle block (key 101).
Check seal ring condition and replace rings as
necessary.
2. Install the nozzle block, seal rings, and screws on
the opposite side of the beam as shown in figure 13.
Disconnect the proportional band tubing (key 76)
and one of the two pieces of reset tubing (key 75)
from the bellows frame (key 94) and reconnect them