AI Function Block
December 2009
4-135
Table 4-56. Analog Input Block Parameter Definitions
Label
PARAMETER_NAME
Description
Initial
Value
Range
Write Block
Mode
RO /
RW
Index
Number
Output Scale
OUT_SCALE
11
OOS
EU at 100%
EU at 10%
Units Index
Decimal Point
100
0
%
2
Data Type: DS-68
The high and low scale values, engineering units
code, and number of decimal places to be used in
displaying the OUT parameter and parameters
which have the same scaling as OUT.
Grant Deny
GRANT_DENY
12
Data Type: DS-70
Options for controlling access of host computer
and local control panels to operating, tuning, and
alarm parameters of the block.
GRANT: 0=N/A, 1=granted
DENY: 0=N/A, 1=denied
GRANT
12.1
ALL
Valid Bits
0: Program
1: Tune
2: Alarm
3: Local
All bits: 0
DENY
12.2
ALL
All bits: 0
I/O Options
IO_OPTS
13
OOS
10: Low cutoff
All bits: 0
Data Type: Bit String
0=Disable
1=Enable
User options for Output Control.
Status Options
STATUS_OPTS
14
OOS
3: Propagate Failure
forward
6: Uncertain if Limited
7: Bad if Limited
8: Uncertain in Man
Mode
All bits: 0
Data Type: Bit String
0=Disable
1=Enable
User options for Status
AI Channel
CHANNEL
15
OOS
See table 4-53
0: Undefined
Data Type: Unsigned16
Used to select the type of threshold that is used to
set the output.
Linearization Type
L_TYPE
16
OOS, MAN
0: Undefined
1: Direct
2: Indirect
3: Ind. Sqr. Root
0: Undefined
Data Type: Enum
Linearization type. Determines whether the field
value is used directly (Direct), is converted linearly
(Indirect), or is converted with the square root
(Indirect Square Root). The OUT_SCALE is
normally the same as the transducer, but if
L_TYPE is set to Indirect or Ind Sqr Root,
OUT_SCALE determines the conversion from
FIELD_VAL to the output.
Low Cutoff
LOW_CUT
17
ALL
Positive
0
Data Type: Float
If calculated output is below this value the output is
0.
Process Value Filter Time
PV_FTIME
18
ALL
Positive
0
Data Type: Float
Time constant of first order filter on PV, in
seconds.
Field Value
FIELD_VAL
19
RO
0
Data Type: DS-65
Value of the field device analog input, with a status
reflecting the Transducer condition.
Updated Event
UPDATE_EVT
20
Data Type: DS-73
This alarm is generated whenever a static
parameter is changed.
UNACKNOWLEDGED
20.1
RW
N/A
0
=
Undefined
1
=
Acknowledged
2
=
Unacknowledged
0
=
Undefined
UPDATE_STATE
20.2
RO
N/A
0
=
Undefined
1
=
Update reported
2
=
Update not reported
0
=
Undefined
TIME_STAMP
20.3
RO
N/A
0
STATIC_REVISION
20.4
RO
N/A
0
RELATIVE_INDEX
20.5
RO
N/A
0
−
Continued
−
4
Содержание Fisher FIELDVUE DVC6000f
Страница 54: ...DVC6000f Digital Valve Controllers December 2009 2 30 2 ...
Страница 62: ...DVC6000f Digital Valve Controllers December 2009 4 2 4 ...
Страница 127: ...Transducer Block December 2009 4 67 4 ...
Страница 141: ...AO Function Block December 2009 4 81 4 ...
Страница 207: ...MAI Function Block December 2009 4 147 4 ...
Страница 219: ...DO Function Block December 2009 4 159 4 ...
Страница 231: ...DI Function Block December 2009 4 171 4 ...
Страница 232: ...DVC6000f Digital Valve Controllers December 2009 4 172 Block Parameter Index 4 173 Block Channel Index 4 186 4 ...
Страница 302: ...DVC6000f Digital Valve Controllers December 2009 8 16 8 ...
Страница 303: ...Principle of Operation December 2009 A 1 A A Appendix A Principle of Operation Digital Valve Controller Operation A 2 A ...
Страница 306: ...DVC6000f Digital Valve Controllers December 2009 A 4 A ...
Страница 350: ...DVC6000f Digital Valve Controllers December 2009 E 6 E ...
Страница 368: ...DVC6000f Digital Valve Controllers December 2009 F 18 F ...
Страница 372: ...DVC6000f Digital Valve Controllers December 2009 Glossary 4 Notes G Glossary ...
Страница 382: ...DVC6000f Digital Valve Controllers December 2009 Index 10 F Index ...
Страница 383: ...This page intentionally left blank ...