DVC6000 Digital Valve Controllers
September 2013
2-4
Hazardous Area Classifications and
Special Instructions for “Safe Use”
and Installations in Hazardous
Locations
Certain nameplates may carry more than one
approval, and each approval may have unique
installation/wiring requirements and/or conditions of
safe use. These special instructions for “safe use” are
in addition to, and may override, the standard
installation procedures. Special instructions are listed
by approval.
Note
This information supplements the
nameplate markings affixed to the
product.
Always refer to the nameplate itself to
identify the appropriate certification.
Contact your Emerson Process
Management sales office for
approval/certification information not
listed here.
Approval information is for both
aluminum and stainless steel
constructions.
WARNING
Failure to follow these conditions of
“safe use” could result in personal
injury or property damage from fire or
explosion, or area re-classification.
CSA
Intrinsically Safe, Explosion-proof, Division 2,
Dust Ignition-proof
No special conditions for safe use.
Refer to table 1-4 for approval information, figures B-1
and B-3 for CSA loop schematics, and figures B-2 and
B-5 for typical CSA nameplates.
FM
Special Conditions of Safe Use
Intrinsically Safe, Explosion-proof, Non-incendive,
Dust Ignition-proof
1. When product is used with natural gas as the
pneumatic medium, the maximum working pressure of
the natural gas supply shall be limited to 145 psi.
2. When product is used with natural gas as the
pneumatic medium the product shall not be permitted
in a Class I, Division 2, Group A, B, C, D location
without the proper venting installation as per the
manufacturer’s instruction manual.
3. The apparatus enclosure contains aluminum and is
considered to constitute a potential risk of ignition by
impact or friction. Care must be taken into account
during installation and use to prevent impact or friction.
4. Part of the enclosure is constructed from plastic.
To prevent the risk of electrostatic sparking the plastic
surface should only be cleaned with a damp cloth.
Refer to table 1-5 for approval information, figures B-6
and B-7 for FM loop schematics, and figures B-2 and
B-9 for typical FM nameplates.
ATEX
Special Conditions for Safe Use
Intrinsically Safe
1. This apparatus can only be connected to an
intrinsically safe certified equipment and this
combination must be compatible as regards the
intrinsically safe rules.
2. The electrical parameters of this equipment must
not exceed any following values:
Uo
≤
30 V; Io
≤
226 mA; Po
≤
1.4 W
3. Operating ambient temperature:
−
52
C or
−
40
C
to + 80
C
4. For the model with aluminum body: the apparatus
must not be submitted to frictions or mechanical
impacts.
5. Covered by standards EN 60079-0 (2009),
EN 60079-11 (2012), EN 60079-26 (2007).
6. Install per drawing GE60771.
Refer to table 1-6 for additional approval information,
figure B-10, B-12, and B-13 for ATEX loop schematics
and figure B-11 for typical ATEX Intrinsic Safety
nameplates.
2
Содержание Fisher FIELDVUE DVC6000
Страница 2: ......
Страница 22: ...DVC6000 Digital Valve Controllers September 2013 1 12 1 ...
Страница 82: ...DVC6000 Digital Valve Controllers September 2013 4 22 4 ...
Страница 94: ...DVC6000 Digital Valve Controllers September 2013 5 12 5 ...
Страница 139: ...Loop Schematics Nameplates September 2013 B 1 B B Appendix B Loop Schematics Nameplates B ...
Страница 161: ......