Basic Setup and Calibration
July 2009
3-5
Quick Setup
When installing the DVC2000 digital valve controller
on an actuator for the first time, the quick setup
procedure will calibrate and tune the instrument
automatically. Table 3-3 lists the values that are
preconfigured at the factory.
WARNING
During calibration the valve will move
full stroke. Changes to the tuning set
may also cause the valve/actuator
assembly to stroke. To avoid personal
injury and property damage caused by
moving parts, keep hands, tools, and
other objects away from the
valve/actuator assembly.
Note
If optional limits switches are being
used, power must be applied to the
switch circuits throughout the quick
setup routine. Failure to power the
switches may result in incorrect switch
orientation.
Table 3-3. Factory Default Settings Accessible from the Local
Interface
Setup Parameter
Default Setting
Zero Control Signal
Open
(1)
Pressure Units
BAR or PSIG
Input Range Low
4 mA
Input Range High
20 mA
Characteristic
Linear
Transmitter (optional feature)
4 mA = Valve Closed
Switch 1 Trip Point (optional feature)
90%
Switch 1 Closed (optional feature)
Disabled
Switch 2 Trip Point (optional feature)
10%
Switch 2 Closed (optional feature)
Disabled
1. If the instrument is shipped mounted on an actuator, these values depend upon
the actuator on which the instrument is mounted.
Refer to the DETAILED SETUP procedure for further
explanation of the parameters.
To access the QUICK SETUP routine from the home
screen, press the DOWN (
) arrow key and then the
RIGHT (
) arrow key. A warning will advise you that
this procedure will cause the valve to move. Another
RIGHT (
) button press will begin the calibration
process. Pressing the LEFT (
) arrow key will bring
you back to the main menu.
This procedure will automatically calibrate the
instrument and apply tuning parameters specifically fit
for the size of the actuator.
To abort the procedure at any time, press the RIGHT
(
) and LEFT (
) arrow keys together for 3 seconds.
When the procedure is complete, press the RIGHT
(
) arrow key to return to the status screen. If the
RIGHT (
) button is not pressed within 30 seconds,
the device will revert back to the status screen
automatically.
TRAVEL = 66.8%
14.6 MA 0.92 BAR
VALVE WILL MOVE
PRESS
FOR 3 SEC
QUICK SETUP
FINDING 0%...
QUICK SETUP
COMPLETE
Figure 3-2. Quick Setup
3
Содержание Fisher FIELDVUE DVC2000
Страница 40: ...DVC2000 Digital Valve Controller July 2009 3 14 3 ...
Страница 70: ...DVC2000 Digital Valve Controller July 2009 6 10 6 ...
Страница 71: ...Parts July 2009 7 1 7 7 Section 7 Parts Parts Ordering 7 2 Parts Kits 7 2 Parts List 7 2 7 ...
Страница 77: ...Principle of Operation July 2009 A 1 A A Appendix A Principle of Operation DVC2000 Operation A 2 A ...
Страница 80: ...DVC2000 Digital Valve Controller July 2009 A 4 A ...
Страница 104: ...DVC2000 Digital Valve Controller July 2009 Index 8 C Index ...
Страница 105: ......