Instruction Manual
D102748X012
DLC3010 Digital Level Controller
Installation
May 2018
29
Installation in Conjunction with a Rosemount 333 HART Tri‐Loop
HART‐to‐Analog Signal Converter
Use the DLC3010 digital level controller in operation with a Rosemount 333 HART Tri-Loop HART‐to‐Analog Signal
Converter to acquire an independent 4‐20 mA analog output signal for the process variable, % range, electronics
temperature, and process temperature. The Tri‐Loop divides the digital signal and outputs any or all of these variables
into as many as three separate 4‐20 mA analog channels.
Refer to figure 2‐13 for basic installation information. Refer to the 333 HART Tri‐Loop HART‐to‐Analog Signal
Converter Product Manual (
) for complete installation information.
Figure 2‐13. HART Tri‐Loop Installation Flowchart
START HERE
DONE
Digital level
controller
Installed?
Unpack the
HART Tri‐Loop
Review the
HART Tri‐Loop
Product Manual
Set the digital
level controller
Burst Option
Set the digital
level controller
Burst Mode
No
Yes
Install the digital
level controller.
Install the HART
Tri‐Loop. See
HART Tri‐Loop
Product Manual
Mount the HART
Tri‐Loop to the
DIN rail.
Wire the digital
level controller to
the HART Tri‐Loop.
Install Channel 1
wires from HART
Tri‐Loop to the
control room.
(Optional)
Install Channel
2 and3 wires from
HART Tri‐Loop to
the control room.
Configure the HART
Tri‐Loop to receive
digital level controller
burst commands
Pass system
test?
Check
troubleshooting
procedures in HART
Tri‐Loop product
manual.
No
Yes
E0365