Instruction Manual
D102748X012
DLC3010 Digital Level Controller
Configuration
May 2018
44
Figure 4‐3. Example of the Use of Level Offset
LEVEL
OFFSET
(6 FEET)
URV
(10 FEET)
LRV
(6 FEET)
E0368
DISPLACER
Process Conditions
Field Communicator
Configure > Manual Setup > Process Conditions (2-2-4)
Follow the prompts on the Field Communicator to view or edit process condition information.
D
RTD Data
is visible when Process Temperature Source is not Manual Entry.
Process Temperature
displays the process temperature measured by a resistance temperature detector (RTD)
located in the process fluid.
RTD
Wire Resistance
displays the user estimate of wiring resistance (per lead) when employing a 2-wire RTD
connection.
D
Temperature Se
tting is a menu item that only appears when Process Temperature Source is "Manual Entry".
If a process temperature sensor (RTD) is not installed, it is possible to manually set the Digital Process Temperature
variable to the target process temperature. This value will be used by any SG-compensation tables that the user has
entered. If no compensation tables are active, the Digital Process Temperature value may be used to document the
process temperature at which the instrument was calibrated, or the process temperature for which the stored
torque rate is pre-compensated.
The Process Temperature value may be edited directly in the Temperature Setting menu item. Press Enter and then
Send to load the new value to the device.
D
Process Temperature Source
allows you to select the source of the process temperature parameter; Manual or
100 ohm platinum 2-wire or 3-wire RTD.
D
Change Source
allows you to configure an RTD to measure process temperature, or manually enter a process
temperature value to be used for Primary Variable compensation.
When configuring an RTD you must select the number of wires for an RTD; either 2 or 3.
For a 2‐wire RTD, you must specify the connecting wire resistance for one wire of the pair. If you know the
resistance, select
Resistance
and enter the resistance of the wire. 250 feet of 16 AWG wire has a resistance of 1 ohm.
Содержание FISHER FIELDVUE DLC3010
Страница 14: ...Instruction Manual D102748X012 DLC3010 Digital Level Controller Introduction and Specifications May 2018 14 ...
Страница 98: ...Instruction Manual D102748X012 DLC3010 Digital Level Controller Parts May 2018 98 ...
Страница 104: ...Instruction Manual D102748X012 DLC3010 Digital Level Controller Principle of Operation May 2018 104 ...