Instruction Manual

D102005X012

846 Transducer

February 2021

4

Table 1. Specifications (continued)

Performance

 

(continued)

(5)

Electromagnetic Interference (EMI):

 Tested per IEC

61326‐1:2013. Meets emission levels for Class A
equipment (industrial locations) and Class B
equipment (domestic locations). Meets immunity
requirements for industrial locations (Table A.1 in the
IEC specification document). Immunity performance
is shown in table 2.

Leak Sensitivity

(4)

:

 Less than 1.0% of span for up to

4.8 m

3

/hr (180 scfh) downstream leakage.

Overpressure Effect: 

Less than 0.25% of span for

misapplication of up to 7.0 bar (100 psi) supply
pressure for less than 5 minutes to the input port.

Reverse Polarity Protection:

No damage occurs from reversal of normal supply
current (4 to 20 mA) or from misapplication of up to
100 mA.

Connections

Supply Air, Output Signal, and Output Gauge:

 

1/4‐18 NPT internal connection

Electrical: 

1/2‐14 NPT internal conduit connection

Adjustments

Zero and Span:

 screwdriver adjustments located in

terminal compartment.

Remote Pressure Reading (RPR)
Jumper selectable, ON or OFF, if unit includes
option

Frequency Range:

 0 to 10,000 Hz

Amplitude:

 0.4 to 1.0 V

p‐p

Required Operating Voltage with Remote pressure
Reading Off

Min. 6.0 V (at 4 mA)
Max. 7.2 V (at 20 mA)

Required Operating Voltage with Remote Pressure
Reading On

Min 6.4 V (at 4 mA)
Max. 8.2 V (at 20 mA)

Electrical Classification

Hazardous area:

CSA C/US

—Intrinsically Safe, Explosion-proof,

Non-Incendive

FM

—Intrinsically Safe, Explosion-proof, Non-Incendive

ATEX

—Intrinsically Safe, Flameproof, Type n

IECEx

—Intrinsically Safe, Flameproof

Electrical Housing:

Tropicalization (Fungus test per MIL-STD-810)

CSA C/US

—Type 4X

FM

—Type 4X

ATEX

—IP66

(6)

IECEx

—IP66

(6)

Other Classifications/Certifications

CUTR

— Customs Union Technical Regulations

(Russian, Kazakhstan, Belarus, and Armenia)

ESMA

— Emirates Authority for Standardization and

Metrology - ECAS-Ex (UAE)

INMETRO

—National Institute of Metrology, Quality,

and Technology (Brazil)

KGS

—Korea Gas Safety Corporation (South Korea)

NEPSI

— National Supervision and Inspection Centre

for Explosion Protection and Safety of
Instrumentation (China)

PESO CCOE

— Petroleum and Explosives Safety

Organization -  Chief Controller of Explosives (India)
Contact your 

Emerson sales office

 for

classification/certification specific information

Construction Materials

Housing: 

Low‐copper aluminum with polyurethane

paint, or 316 stainless steel

O‐Rings:

 

Nitrile, except silicone for sensor O‐rings.

Options

Fisher 67CFR filter regulator, supply and output
gauges or tire valve remote pressure reading, module
cover with multiple stroke ports, stainless steel
housing, or stainless steel mounting bracket.

Weight

Aluminum:

 2.9 kg (6.5 lb) excluding options

Stainless Steel:

 6.7 kg (14.8 lb) excluding options

-continued-

Содержание Fisher 846

Страница 1: ...n 21 4 to 12 mA Input Signal 21 12 to 20 mA Input Signal 21 Transporting the Module Final Assembly 22 Principle of Operation 22 Electronic Circuit 22 Magnetic Actuator 23 Pilot Stage 23 Booster Stage 24 Troubleshooting 25 Diagnostic Features 25 Stroke Port 25 Figure 1 Fisher 846 Current to Pressure Transducer X0234 Remote Pressure Reading RPR 25 Using a Frequency Counter to read the RPR Signal 25 ...

Страница 2: ...uce a pneumatic output for operating a control valve actuator or positioner The 846 may also be used to produce a signal for a pneumatic receiving instrument The 846 is an electronic I P transducer It has a single electronic circuit board as shown in figure 2 The circuit contains a solid state pressure sensor that monitors output pressure and is part of an electronic feedback network The self corr...

Страница 3: ... 01 A maximum 40 micrometer particle size in the air system is acceptable Further filtration down to 5 micrometer particle size is recommended Lubricant content is not to exceed 1 ppm weight w w or volume v v basis Condensation in the air supply should be minimized Per ISO 8573 1 Maximum particle density size Class 7 Oil content Class 3 Pressure Dew Point Class 3 or at least 10 C less than the low...

Страница 4: ...tage with Remote Pressure Reading On Min 6 4 V at 4 mA Max 8 2 V at 20 mA Electrical Classification Hazardous area CSA C US Intrinsically Safe Explosion proof Non Incendive FM Intrinsically Safe Explosion proof Non Incendive ATEX Intrinsically Safe Flameproof Type n IECEx Intrinsically Safe Flameproof Electrical Housing Tropicalization Fungus test per MIL STD 810 CSA C US Type 4X FM Type 4X ATEX I...

Отзывы: