Section 3 4195KA Proportional‐Only Controllers
Adjustments for 4195KA Controllers
This section includes descriptions of adjustments and procedures for prestartup, startup, and calibration. Adjustment
locations are shown in figures 3‐1 and 3‐3. To better understand the adjustments and overall controller operation,
refer to the Principle of Operation section and the schematic diagrams in figures 3‐4 and 3‐5. Unless otherwise noted,
key numbers given in this section are found in figure 7‐1.
Figure 3‐1. Fisher 4195KA Controller Adjustment Locations
METAL BALL
SWITCHING
ZONE
INDICATOR
LOADER KNOB
AUTO/MANUAL
SWITCH
W3679
AUTO/MANUAL STATION
(SUFFIX LETTER E)
SET POINT
INDICATOR
PROCESS POINTER
PROPORTIONAL BAND
ADJUSTMENT
PROPORTIONAL BAND
INDICATOR COVER
OUTPUT PRESSURE GAUGE
W6832
Manual Set Point Adjustment
Adjust the set point by moving the set point indicator until the line on the set point indicator is over the desired value
on the process pressure scale. Move the indicator to the right to increase the set point and to the left to decrease it.
Adjusting the set point does not affect the proportional band setting.