DVC6200f Digital Valve Controller
November 2010
32
Resource Block Overview
The resource block contains the hardware specific
characteristics associated with a device; it has no
input or output parameters. The resource block
monitors and controls the general operation of other
blocks within the device. Most of the resource block
parameters are operational parameters that provide
information about the instrument such as identification,
hardware information, available options, etc. and are
read only. Configuration of the resource block involves
selecting features from those that are available,
setting the mode, setting write lock, and setting up
alert reporting details.
The following procedures address only the key
resource block parameters; however, all resource
block parameters are listed in table 4-3.
Configure/Setup
Setup
Resource Block Mode
Field Communicator
RB
>
Configure/Setup
>
Setup
>
Resource
Block Mode
Modes
The resource block can be in one of two modes
(MODE_BLK [5]):
Automatic (Auto)—This is the operational mode for
this block. When the resource block is in the Auto
mode, all other function blocks are allowed to function
normally.
Out of Service (OOS)—Placing the resource block
in Out of Service mode stops all function block
execution, by setting their modes to Out of Service as
well. The actual mode of the function blocks is
changed to Out of Service, but the function block
target modes are retained. Placing the resource block
in the Out of Service mode does not affect the mode
of the transducer block.
Write Lock
Field Communicator
RB
>
Configure/Setup
>
Write Lock
Write Lock
Write Lock (WRITE_LOCK [34]) determines if writes
are permissible to other device parameters. The
Firmware Write Lock feature must be selected to be
able to use Write Lock (see Features). When Write
Lock is set to Locked, no writes are permitted to any
parameters within the device except to set Write Lock
to Not Locked. When locked, the device functions
normally, updating inputs and outputs and executing
algorithms. When Write Lock is set to Not Locked, the
Write Alarm (WRITE_ALM [40]) alert is active.
Write Priority
Write Priority (WRITE_PRI [39]) sets the priority for
Write Alarm. The lowest priority is 0. The highest is
15.
Communication Time Out
Field Communicator
RB
>
Configure/Setup
>
Communication Time
Out
Shed Remote Cascade
Note
Typically this parameter does not need
to be changed. The unit will be
operational using the default values
assigned by the factory. Perform this
procedure only if a remote computer is
sending setpoints from your
“advanced” control.
Default value for RCas Timeout is 20
seconds.
Shed Remote Cascade (SHED_RCAS [26])
determines how long function blocks in the DVC6200f
should wait before giving up on remote computer
writes to RCas parameters. When the timeout is
exceeded, the block sheds to the next mode as
defined by the block shed options. If Shed Remote
Cascade is set to 0, the block will not shed from RCas.
Enter a positive value in the Shed Remote Cascade
field. Time duration is in 1/32 milliseconds (640000
=
20 secs).
4
Содержание FIELDVUE DVC6200f
Страница 42: ...DVC6200f Digital Valve Controller November 2010 30 4 ...
Страница 60: ...DVC6200f Digital Valve Controller November 2010 48 4 ...
Страница 108: ...DVC6200f Digital Valve Controller November 2010 96 4 ...
Страница 122: ...DVC6200f Digital Valve Controller November 2010 110 4 ...
Страница 188: ...DVC6200f Digital Valve Controller November 2010 176 4 ...
Страница 200: ...DVC6200f Digital Valve Controller November 2010 188 4 ...
Страница 216: ...DVC6200f Digital Valve Controller November 2010 204 5 ...
Страница 250: ...DVC6200f Digital Valve Controller November 2010 238 8 ...
Страница 251: ...Principle of Operation November 2010 239 A A Appendix A Principle of Operation Digital Valve Controller Operation 240 A ...
Страница 254: ...DVC6200f Digital Valve Controller November 2010 242 A ...
Страница 284: ...DVC6200f Digital Valve Controller November 2010 272 D ...
Страница 290: ...DVC6200f Digital Valve Controller November 2010 278 E ...
Страница 308: ...DVC6200f Digital Valve Controller November 2010 296 F ...
Страница 312: ...DVC6200f Digital Valve Controller September 2010 300 Notes G Glossary ...
Страница 324: ...DVC6200f Digital Valve Controller November 2010 312 F Index ...
Страница 325: ...This page intentionally left blank ...