background image

CC7.5.1/0705/E 

Technical Information 

3.3 

Fans used on units manufactured before 1994 

If you have an "old" unit manufactured before 1994, some fans are not supplied anymore, but you can replace them 
with the present fans. 
You can find the equivalent in the following cross reference (table 3). 

Fan characteristics

Blade 

φ 

mm

Motor

Q2 Q3

350

25W

1 Ph

still supplied

Q3 Q4 T42

T43 T81

350

60W

3 Ph

model 120 / 121

Q5 Q6 Q7

T5 T71 T82

356

60W

3 Ph

model 120 / 121

Q8 Q10 Q12 T93 T94 T101 T121 T151

420

200W

3 Ph

model 270 / 271

T17 U61 U121

500

700W

3 Ph

still supplied

Old condensor

Replacement fan

 

Table 3: 

Cross-reference: replacement fans

 

 

Fans for Copeland EazyCool outdoor condensing units 

The OM and OL units are fitted with a single-phase fan since the beginning of 2003, earlier manufactured units are 
provided with a three-phase fan, models 120 and 270 depending on the condensing unit model.  
Current used fans (model 121 or 271) are interchangeable with the previous models, but the wiring has to be 
changed to single-phase wiring.  
The OMQ and OLQ have a low speed (910 rpm) 6 pole single-phase motor. 
 
Today, the condensers of the OM, OMQ, OL and OLQ units are equipped with single-phase fan(s). 
 
The fan model is given in our Product Selection Catalogues and in Copeland Selection Software, both available on 
www.eCopeland.com. 
 

4.1 Technical 

data 

 

Blade 

diameter

Power input

Voltage

Motor 

current

mm

W

V (±10%) / Ph / Hz

EBM

Rotomatika

A

Main

Auxilary

121

350

117

220 - 240 / 1 / 50

0.54

72

108

271

420

300

220 - 240 / 1 / 50

5 / 400

6.3 / 400

1.35

25

88

65

350

78

220 - 240 / 1 / 50

2 / 400

3.15 / 400

0.31

143

159

145

420

155

220 - 240 / 1 / 50

4 / 400

6.3 / 400

0.67

45.9

51.6

301

500

290

220 - 240 / 1 / 50

1.7

24.7

33.3

8 / 400

Run capacitor

 µF / V

Winding resistance 

Ω 

(±10%), 25°C

Fan model

4 / 400

Table 4: 

Technical data – fans for Copeland EazyCool condensing units

 

 

4.2 Wiring 

diagram 

See figure 1. 
 

Information in this document are subject to change without notification

4/4

 

Содержание FANS

Страница 1: ... 54 and its insulation class is F Most fans can be equipped with a speed controller connected to the condensing pressure 3 Fans for Copeland Scroll and DWM Copeland semi hermetic condensing units The fan is positioned in order to blow the air from the condenser to the compressor so the compressor additional fan is not necessary any more NOTE After connecting the condensing unit electrically check ...

Страница 2: ... Y 3 50 1 10 0 65 500 550 3 50 0 52 220 240 1 50 3 6 220 240 380 420 Y 3 50 2 95 1 70 500 550 3 50 1 1 9 3 Winding resistance 5 400 8 400 16 400 25 400 20 60 51 6 2 6 2 18 6 54 7 57 3 172 10 325 24 20 Ω 10 25 C 102 104 3 218 6 574 37 270 420 280 610 500 630 Fan model 75 300 80 Run capacitor µF V 120 350 135 Table 2 Technical data three phase fans Old units were delivered with three phase fans as a...

Страница 3: ... M21 L3 L2 L1 L3 L2 L1 A M22 A M22 Figure 2 230V 15 3 50 60 Hz Figure 3 Y 400V 15 3 50 60 Hz Y 500V 15 3 50 60 Hz Three phase fans can also be connected in single phase thanks to a run capacitor V2 Grey V2 Grey W1 Black W1 Black U2 Red U2 Red V1 Blue V1 Blue W2 Orange W2 Orange U1 Brown U1 Brown White White White White C1 C1 M21 F10 M Fan M Fan M21 F10 15 16 X1 N 14 13 L 12 11 10 9 L 8 Figure 4 Th...

Страница 4: ...nding on the condensing unit model Current used fans model 121 or 271 are interchangeable with the previous models but the wiring has to be changed to single phase wiring The OMQ and OLQ have a low speed 910 rpm 6 pole single phase motor Today the condensers of the OM OMQ OL and OLQ units are equipped with single phase fan s The fan model is given in our Product Selection Catalogues and in Copelan...

Отзывы: