Emerson EXD-TEVI Скачать руководство пользователя страница 2

 

 

Operating instructions 

EXD-TEVI Economizer Controller with  

ModBus Communication Capability

 

 

 

 

Emerson Climate Technologies GmbH  

 

www.emersonclimate.eu

  

2/3 

Holzhauser Straße 180 I 13509 Berlin I Germany  

Date: 19.08.2014 

EXD-TEVI_OI_EN_R02_865908.docx 

Preparation for Start-up: 

 

Vacuum the entire refrigeration circuit. 

 

EMERSON’s Electrical Control Valves EXM/EXL are delivered in partially 
open position. Do not charge system with refrigerant before closure of valve. 

Procedure for Valve Closure: 

 

Apply supply voltage 24V to EXD-TEVI while the digital inputs (DI1 and DI2) 
are Off (open). The valve(s) will be driven to close position. 

 

After closure of valve, start to charge the system with refrigerant. 

 

Setup of parameters  
(need to be checked/modified before start-up): 

 

Make sure that digital inputs (DI1 and DI2) are off (open).  

 

Turn the power supply ON. 

Once  the  main  parameters  have  been  selected/saved  the  EXD-TEVI  is  ready  for 
startup.  All  other  parameters  can  be  modified  at  any  time  during  operation  or 
standby if it is necessary. 

 

Procedure for parameter modification: 

The  parameters  can  be  accessed  via  the  4-button  keypad.  The  configuration 
parameters  are  protected  by  a  numerical  password.  The  default  password  is  “12”. 
To select the parameter configuration: 

 

Press the 

 button for more than 5 seconds  

 

A flashing “0” is displayed 

 

Press 

 until “12” is displayed; (password) 

 

Press 

 to confirm password  

 

The 1

st

 parameter H5 is displayed 

 

Press 

or 

 to show the code of the parameter that has to be changed 

 

Press 

 to display the selected parameter value 

 

Press 

or 

 to increase or decrease the value 

 

Press 

 to temporarily confirm the new value and display its code 

 

Repeat the procedure from the beginning "press 

or 

 to show..." 

To exit and save the new settings

 

Press 

  to  confirm  the  new  values  and  exit  the  parameters  modification 

procedure. 

 

To exit without modifying/saving any parameters. do not press any button for at 
least 60 seconds (TIME OUT). 

 

Reset all parameters to factory setting: 

 

Make sure that digital inputs (DI1/DI2) are Off (open). 

 

Press 

 and 

 together for more than 5 seconds. 

 

A flashing “0” is displayed. 

 

Press 

or 

 until the password is displayed (Factory setting = 12).  

  If password was changed, select the new password. 

 

Press 

 to confirm password 

 

Factory setting are applied 

 

Display System Parameters: 

 

In standard mode the EVI superheat is shown at the display.  In case of  wet vapor 
injection and economizer function this changes to discharge temperature. 

 

To display other data of EXD-TEVI:  

 

 

 

Press 

 for 3 seconds to show data 

To display data: Press the 

 button for 1 second until index number according 

to the below table appears. Release the 

 button and the next variable data will 

appear. By repeating above procedure, variable data can be displayed in a sequence 
as in following table. 

Index No.  Variable data 

Units  Source 

Default displayed value

  

measured 

EVI Pressure  

bar  measured 

Total combination 
Valves opening  

 

EVI suction gas temp  

°C 

measured 

EVI saturation temp.  

°C 

calculated 

Discharge temp. 1 

°C 

measured 

Discharge temp. 2 

°C 

measured 

Note: After 3 minutes, display reverts to index 0. 

Manual alarm reset/clearing functional alarms (except 
hardware errors): 

 

Press 

 and 

 together for 5 seconds.  

 

When the clearing is done, “CL” message appears for 2 seconds. 

List of parameters in scrolling sequence by pressing 

 

button: 

Code  Parameter description and choices 

Min 

Max 

Factory 

setting 

H5 

Password 

1999   

12 

Adr 

ModBus address 

127 

br 

Modbus baud rate 

PAr 

Modbus parity 

tAn 

Single / Tandem Operation 

 

1 = single compressor, 2 = tandem compressor 

1u4 

Superheat control mode 

 

0 = Standard;  

1 = Slow; 

2 = Fix PID (For trouble shooting/no warranty if system to be 
operated with fix PID) 

1uu 

Start valve opening (%) 

100 

15 

1u9 

Start opening duration (second) 

30 

1u5 

Superheat set-point (1/10 K) 

0.5 

30.0 

7.0 

1PE 

Economizer control fixed PID (Kp 
factor; 1/10) 

0.1 

10.0 

2.0 

 

For trouble shooting/no warranty if system to be operated with PID 

1IE 

Economizer control circuit1 (Ti factor) 

350 

100 

 

For trouble shooting/no warranty if system to be operated with PID 

1dE 

Economizer control circuit1 (Td factor; 
1/10) 

0.1 

30.0 

1.0 

 

For trouble shooting/no warranty if system to be operated with PID 

1uC 

Units conversion 

 

0 = °C, K, bar;  

1 = F, psig 

1dt 

Discharge temperature limit (1/100 °C)  100.0 

140.0 

135.0 

1Lo 

Load shedding valve offset 

10 

20 

18 

 

(Valve opening change by adding/removing compressors. 
10 is no offset, 20 is 50% of current valve opening as offset) 

dAd 

Discharge temp. alarm delay (sec) 

10 

60 

60 

EC0 

Number of installed expansion valves 

t2E 

Threshold start second valve (%) 

50 

30 

 

Control (valve) start-up behavior (Parameter 1uu and 1u9) 

 

 
 

1uu: 
Min.:      0%  (<1 sec.) 
Default: 15% (< 1.5 sec.) 
Max.:     100% (< 6 sec.) 

 

 

 

 

 

Содержание EXD-TEVI

Страница 1: ...ils are supplied with fix cable and JST terminal block at cable end Cut the wires close to terminal block Remove the wire insulation approximately 7mm at the end It is recommended to protect wire ends with ferrules Color codes for connection of EXM EXL and pressure sensor PT5 EXM L BR Brown BL Blue OR Orange YE Yellow WH White PT5 BN Brown WH White Digital inputs DI1 and DI2 The digital inputs DI1...

Страница 2: ...g are applied Display System Parameters In standard mode the EVI superheat is shown at the display In case of wet vapor injection and economizer function this changes to discharge temperature To display other data of EXD TEVI Press for 3 seconds to show data To display data Press the button for 1 second until index number according to the below table appears Release the button and the next variabl...

Страница 3: ...lly close Check wiring connection and measure the resistance of sensor Auto 2Ed Hot gastemp sensor2 fail Triggered Fully close Check wiring connection and measure the resistance of sensor Auto 1Π EXM EXL electrical connection error Triggered Check wiring connection and measure the resistance of winding Auto 2Π EXM EXL electrical connection error Triggered Check wiring connection and measure the re...

Страница 4: ...лер и провода датчиков на расстоянии минимум 30 мм от кабелей питания Катушки у EXM 125 и EXL 125 поставляются вместе с вмонтированным кабелем и клеммной колодкой на конце кабеля Отрежьте клеммную колодку Зачистите от изоляции примерно 7 мм на концах проводов На зачищенные участки рекомендуется одеть наконечники Коды расцветок при подключении EXM EXL и датчика давления PT5 EXM L BR Коричневый BL С...

Страница 5: ...ение параметров системы При впрыске пара стандартный режим на дисплее отображается перегрев а при впрыске влажного пара температура нагнетания Для отображения других данных на EXD TEVI Нажмите на 3 секунды для показа данных Показать данные Нажимайте в течение 1 секунды пока не появится индекс нужного параметра из таблицы ниже Отпустите кнопку и появится нужное значение Повторяя эту процедуру можно...

Страница 6: ... сопротивление датчика Авто 2Ed Ошибка датчика2 температуры нагнетания Сигнализирует Закрыт Проверьте правильность электрических подключений и измерьте сопротивление датчика Авто 1Π Ошибка электрического подключения ЭРВ 1 Сигнализирует Проверьте правильность электрических подключений и измерьте сопротивление проводов Авто 2Π Ошибка электрического подключения ЭРВ 2 Сигнализирует Проверьте правильно...

Отзывы: