Setting Position Limits for Electrical Operation
September 2018
Quick-Start Guide
E2K-210-05-18 Rev. 3
5
Setting Position Limits for Electrical Operation
Setting Position Limits for
Electrical
Operation
STEP 2:
OPEN Valve Position
Turn the selector knob to the
“LOCAL”
position. Hold the control knob in the
“OPEN”
position until
desired position is reached. Dis-engage motor drive by setting the declutch lever in
“HAND”
mode. Using
handwheel, move the valve in the close direction for one handwheel turn to allow for motor coasting. Re-
engage motor drive by setting the declutch lever out of
“HAND”
mode.
Return the selector knob to the
“STOP”
position. Select
“YES”
to set new open limit.
2
3
4
YES
LOCAL
OPEN
Hold until
desired
position is
reached.
1
STOP