Operating instruction 

EC3-P33 Superheat Controller and  

ECD-002 Keypad / Display Unit  

Installation in non explosive environment 

 

 

 

Emerson Climate Technologies GmbH  

www.emersonclimate.eu

 

Am Borsigturm 31 I 13507 Berlin I Germany 

Date: 04.05.2017 

EC3-P33_OI_ML_R01_865919.docx 

E C D - 0 0 2   d i s p l a y / k e y p a d   u n i t :   ( L E D s   a n d   b u t t o n   f u n c t i o n s )  
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

S e t u p   o f   m a i n   p a r a m e t e r s   u s i n g   E C D - 0 0 2 :  
(need to be checked/modified before start-up)  

 

Make sure that digital input is 0 V (open). Turn the power supply ON. 

 

Important:

 Three main parameters i.e. refrigerant type (u0), pressure sensor type 

(uP) and valve type (ut) can be set only when digital input is open (0 V) while the 
power supply is ON (24 V). This feature is for added safety to prevent accidental 
damage of compressors and other system components. 

 

For easy setting of main parameters, follow the pictorial procedure of 

“Quick 

start-up”

 on the attached individual paper. 

 

Once the main parameters have been selected/saved the EC3 is ready for 
startup. All other parameters can be modified at any time during operation 
or standby if it is necessary. 

 

P r o c e d u r e   f o r   p a r a m e t e r s   m o d i f i c a t i o n   u s i n g   E C D - 0 0 2 :  

 

The parameters can be accessed via the 4-button keypad. The configuration 
parameters are protected by a numerical password. The default password is “12”. 
To select the parameter configuration: 

 

Press the 

PRG

 button for more than 5 seconds. A flashing “0” is displayed 

 

Press 

 or 

 until “12” is displayed; (password) 

 

Press 

SEL

 to confirm password 

 

Press 

 or 

 to show the code of the parameter that has to be changed; 

 

Press 

SEL

 to display the selected parameter value;  

 

Press 

 or 

 to increase or decrease the value; 

 

Press 

SEL

 to temporarily confirm the new value and display its code;  

 

Repeat the procedure from the beginning "press  

 or 

 to show..." 

 

To exit and save the new settings

: Press 

PRG

 to confirm the new values and exit 

the parameters modification procedure. 

 

To exit without modifying any parameters: 

Do not press any button for at least 

60 seconds (TIME OUT). 

 

R e s e t   a l l   p a r a m e t e r s   t o   f a c t o r y   s e t t i n g :  

 

Make sure that digital input is 0 V (open). 

 

Press 

 and 

 together for more than 5 seconds. A flashing “0” is displayed. 

 

Press 

 or 

 until the password is displayed (Factory setting = 12).  

If password was changed, select the new password. 

 

Press 

SEL

 to confirm password 

“0” is displayed. 

 

Press 

SEL

 to reset all parameters to factory setting 

 

Press 

PRG

 to activate the function and leave the special function mode. 

 

C o n t r o l   ( v a l v e )   s t a r t - u p   b e h a v i o r :   ( P a r a m e t e r   u u   a n d   u 9 )  

 
 
EX4/5/6-…FLR  

≤ 1.5 seconds 

EX7-…FLR  

≤ 3.2 seconds 

 

 

 

M a i n   p a r a m e t e r s :    
(must be checked and modified if necessary) 

Code  Parameter description and choices 

Min

 

Max

 

Factory 
setting

 

Field 
setting 

H5  Password 

199 

12 

 

u0  System refrigerant 

 

 

0 = R290;  

1 = R32;    

2 = R1234ze;  

3 = R1234yf;   4 =  R1270;  
5 = R227;  

6 = R600a 

 

uP  Installed pressure sensor type 

 

 

 

 

 

PT5-30L-FLR 
 

 

ut 

Installed valve type 

 

 

0=EX4-…FLR;  

1=EX5-…FLR;  

2=EX6-…FLR;  

3=EX7-…FLR 

 

 

O p t i o n a l   p a r a m e t e r s :  
(recommended factory setting for majority of applications) 

 
After selecting the parameters the EC3-P33 is fully functional without 
keypad/display unit. ECD-002 may be removed or connected at any time. 
 

 

 

Code  Parameter description and choices 

Min

 

Max

 

Factory 
setting

 

Field 
setting 

uu  Start valve opening (%) 

100 

10 

 

u9  Start opening duration (second) 

120 

 

uL  Low superheat alarm function 

 

 

0 = disable (for flooded evaporator)   
1 = enable auto reset  
2 = enable manual reset 
Cut-out at 0.5K (if it maintains 1 min.); Cut-in immediately at 3K 

 

u5  Superheat set-point (K) 

If uL enabled (auto or manual) 
If uL disabled 

 

0.5 

 

30 
30 

 


 
 

u2  MOP function 

 

 

0 = disable 

 

1 = enable 

 

u3  MOP set-point (°C) saturation temperature 

 

 

Factory setting is according to selected refrigerant (u0): 
+13°C for R290 

 

 

+15°C for R32 

+15°C for R1234ze   

 

+15°C for R1234yf    

+13°C for R1270 

 

 

+15°C for R227 

+15°C for R600a 

 

┌┘

5  Units conversion (only for u3, u5, 

┌┘

1) 

 

 

0 = °C, K, bar   
1 = °F, R, psig 
(Psig values are divided by 10. Example: Display 12.5 is 125 psig) 

 

┌┘

1  Value to show 

 

0 = Measuredsuperheat (K)  

 

1 = Measured evaporating pressure, (bar); 
2 = Valve opening (%)     
3 = Measured coil-out temperature (°C) 
4 = Calculated evaporating temperature (°C) from the pressure  

 

u4  Superheat control mode 

 

 

0 = Standard,  
1 = Slow 

 

 

 

 

b1  Battery error management, when battery is 

defective, see below 

 

 

 

value 

Alarm 

display 

 

Alarm relay 

 

Valve 

Reset possibility after 
recovery/replacement 

 

Regulating 

 

 

Ab 

Regulating 

 

 

Ab 

Signalling 

Fully close 

Auto 

 

 

Ab 

(blinking) 

Signalling 

Fully close 

Manual 

 

 

When setting b1 to option 0 or 1, the user must ensure appropriate safety 
precautions are in place to protect the system against damage caused by 
a power failure. 

!

Blinking:

 valve is closing 

ON:

 valve is fully close 

Blinking:

 valve is opening 

ON:

 valve is fully open 

ON

: demand 

OFF

: no demand 

ON

: alarm 

OFF

: no alarm 

Parameters setting/saving 

Selecting/confirming 

Next parameter/ 
value (higher) 

Next parameter/ 
value (lower) 

Prg&Sel (5 sec) 
Manual reset for 
blinking alarm codes 

Sec.

 

uu

u9

%

E

C

3-

X

3 B

A

.c

dr

Содержание ECD-002

Страница 1: ...controller housing Insert Allen key into front panel holes and turn clockwise Mounting lugs will turn and gradually move towards panel 2 Turn Allen key until mounting lug barely touches panel Then move other mounting lug to the same position 3 Tighten both sides very carefully until keypad is secured Do not over tighten as mounting lugs will break easily Electrical Installation Refer to the electr...

Страница 2: ...G to activate the function and leave the special function mode Control valve start up behavior Parameter uu and u9 EX4 5 6 FLR 1 5 seconds EX7 FLR 3 2 seconds Main parameters must be checked and modified if necessary Code Parameter description and choices Min Max Factory setting Field setting H5 Password 1 199 12 u0 System refrigerant 0 6 0 0 R290 1 R32 2 R1234ze 3 R1234yf 4 R1270 5 R227 6 R600a u...

Страница 3: ...fter 5 minutes the display will return to the value selected by parameter 1 Service Troubleshooting Symptom Cause Action Operating superheat is several degrees higher or lower than set point Incorrect signal from pressure or temperature sensors 1 Check the sensors 2 Make sure ECN N60 temperature sensor is used 3 For optimum accuracy please use PT5 30L FLR 4 Make sure the sensor cables are not inst...

Страница 4: ...den Imbusschlüssel in die Löcher auf der Frontseite einstecken und im Uhrzeigersinn drehen Die Halterungen treten aus dem Gehäuse hervor und bewegen sich in Richtung Frontplatte 2 Imbusschraube drehen bis die erste Halterung die Frontplatte leicht berührt Dann zweite Halterung in diese Position bringen 3 Beide Seiten gleichmäßig und nicht zu fest anziehen Hinweis durch zu festes Anziehen können di...

Страница 5: ...r werden auf Werkseinstellung zurückgesetzt PRG drücken die gewählte Funktion wird aktiviert und die Betriebsart Spezial funktionen verlassen Startverhalten der Regelventile Parameter uu und u9 EX4 5 6 FLR 1 5 Sekunden EX7 FLR 3 2 Sekunden Haupt Parameter müssen ggf angepasst werden Code Beschreibung und Wahlmöglichkeiten Min Max Werk Kunde H5 Passwort 1 199 12 u0 Kältemittel 0 6 0 0 R290 1 R32 2 ...

Страница 6: ...angezeigt Service Fehlersuche Fehlerbeschreibung Ursache Aktion Überhitzung ist einige Grad höher oder niedriger als der Einstellwert Fehlerhaftes Signal von Druck oder Temperatursensoren 1 Sensoren überprüfen 2 ECN N60 als Temperatursensor einsetzen 3 EMERSON Drucktransmitter verwenden PT5 30L FLR 4 Sensorkabel nicht zusammen mit stromführenden Leitungen verlegen Überhitzung ist zu niedrig Verdic...

Страница 7: ...I Germany Date 04 03 2017 EC3 P33_OI_ML_R01_865919 docx 2 2a 2b 0 R290 4 R1270 1 R32 5 R227 2 R123ze 6 600a 3 R123yf 2 3 3a 3b PT5 30L FLR R290 3c 4 4a 4b 0 EX4 FLR 1 EX5 FLR 2 EX6 FLR 3 EX7 FLR 4c 4d 4e Display of Data 0 1 1a 1b 1c 1d 1e EX7 FLR 5 sec 1 199 88 12x EX4 EX5 EX6 EX7 EX8 Po To Ts Vo Ts C To C SH Ts To K 100 0 Po barg EC3X_65130 cdr R22 ...

Отзывы: