Operating instruction 

EC3-P33 Superheat Controller and  

ECD-002 Keypad / Display Unit  

Installation in non explosive environment 

 

 

 

Emerson Climate Technologies GmbH  

www.emersonclimate.eu

 

Am Borsigturm 31 I 13507 Berlin I Germany 

Date: 04.05.2017 

EC3-P33_OI_ML_R01_865919.docx 

G e n e r a l   i n f o r m a t i o n :  
EC3-P33

  is the superheat controller for systems with flammable refrigerants 

(A2L/A3) and able to drive EMERSON Valves EX4-7-…FLR via M12 Connector 
ECV05A. 

Note: This document contains short form instructions for experienced users.

 

 

Warning:

 

 

EC3-P33 has a potential ignition source and does not comply with ATEX 
requirements. Installation only in non-explosive environment. 

 

EX4-7…FLR are currently released for R290 in term of compatibility. The 
other listed refrigerants are subject to qualification at later stage. No 
warranty or product liability if EX4-7…FLR to be used with other 
refrigerants stored in software of EC3-P33.

 

  S a f e t y   i n s t r u c t i o n s :  

 

Read operating instructions thoroughly. Failure to comply can result in device 
failure, system damage or personal injury. 

 

According to EN 13313 it is intended for use by persons having the 
appropriate knowledge and skill. 

 

Ensure that the system is correctly labeled with applied refrigerant type and 
a warning for explosion risk. 

 

Do not exceed the specified maximum ratings for temperature (max.+60°C), 
voltage and current. 

 

Before installation or service disconnect all voltages from system and device. 

 

Do not operate system before all cable connections are completed. 

 

Entire electrical connections have to comply with local regulations. 

Note

: The EC3-P33 series contains 

a VRLA battery = valve regulated rechargeable 

lead-acid battery. 

The battery must NOT be disposed of with other commercial waste. 

Instead, it is the user’s responsibility to pass it to a designated collection point for the 
safe recycling of batteries (harmonized directive 2012/19/EU). For further 
information contact your local environmental recycling center. 

 

M o u n t i n g   p o s i t i o n :  

The EC3-P33 is designed to be mounted onto a standard DIN rail. Mounting position: 
on vertical walls, with stepper motor connector on top side only. 
 

M o u n t i n g   o f   E C D - 0 0 2 :  

 

ECD-002 can be installed at any time also during operation. 

 

ECD-002 can be mounted in panels with 
71x29 mm cutout. 

 

Push controller into panel cut-out.(1) 

 

Make sure that mounting lugs are flush with 
outside of controller housing 

 

Insert Allen key into front panel holes and turn 
clockwise. Mounting lugs will turn and gradually 
move towards panel (2) 

 

Turn Allen key until mounting lug barely touches 
panel. Then move other mounting lug to the same 
position (3) 

 

Tighten both sides very carefully until keypad is 
secured. Do not over tighten as mounting lugs 
will break easily.

 

 

 

  E l e c t r i c a l   I n s t a l l a t i o n :  

 

Refer to the electrical wiring diagram for electrical connections. 

 

Do not apply voltage to the controller before completion of wiring. 

 

Ground the metal housing with a 6.3 mm spade connector. 

 

Keep controller and sensor wiring well separated from mains wiring. 
Minimum recommended distance 30 mm!

 

 

 

Ensure that cables are not mounted near sharp edges. 

 

Use a class II category transformer for 24 VAC power supply. Do not ground the 
24 VAC lines. We recommend using individual transformers for EC3 controller(s) 
and for 3

rd

 party controllers to avoid possible interference or grounding problems 

in the power supply. 

 

Connecting any EC3 inputs to mains voltage will permanently damage the EC3. 

 

The use of the relay is essential to protect the system in case of power failure if the 
communications interface or the ECD-002 are not utilized. 

 

If the output relay is not utilized, the user must ensure appropriate safety pre-
cautions are in place to protect the system against damage caused by a power 
failure. 

 

In order to provide system protection in the event of power loss, it is recommended 
to change the battery annually. 

 
Digital input status is dependent to operation of compressor/thermostat 

Commander 

Operating condition 

Digital input (I) 

Compressor 

Compressor starts 

Closed / 24 V (Start) 

Compressor stops 

Open / 0 V (Stop) 

Thermostat 

Demand (compressor must be ON) 

Closed / 24 V (Start) 

No demand 

Open / 0 V (Stop) 

 

W i r i n g :

 

 

 

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

2

White wire  

4

:  Black wire 

3

:  Blue wire 

1

: Brown wire 

G

Remote control panel, system controller 

H

Alarm relay, dry contact. Relay coil is not energized at alarm or power off. 

I

Digital input (0V/open = Stop; 24 V/closed = Start) 

J

Transformer Class II, 24 VAC secondary / 25 VA 

K

Third party controller (can use the analog output signal from EC3) 

 

P r e p a r a t i o n   f o r   S t a r t - u p :  

 

Vacuum the entire refrigeration system 

 

Note:

  EX4-7-…FLR  are delivered at half open position. Do not charge system 

before closure of valve. 

 

Apply supply voltage 24 V to EC3 while the digital input is 0 V (open). The valve 
will be driven to close position.

 

 

 

After closure of valve, start to charge the system with refrigerant. 

 

Start the system and check the superheat and operating conditions.  

 

!

Non-explosiv  
environment 

Содержание ECD-002

Страница 1: ...controller housing Insert Allen key into front panel holes and turn clockwise Mounting lugs will turn and gradually move towards panel 2 Turn Allen key until mounting lug barely touches panel Then move other mounting lug to the same position 3 Tighten both sides very carefully until keypad is secured Do not over tighten as mounting lugs will break easily Electrical Installation Refer to the electr...

Страница 2: ...G to activate the function and leave the special function mode Control valve start up behavior Parameter uu and u9 EX4 5 6 FLR 1 5 seconds EX7 FLR 3 2 seconds Main parameters must be checked and modified if necessary Code Parameter description and choices Min Max Factory setting Field setting H5 Password 1 199 12 u0 System refrigerant 0 6 0 0 R290 1 R32 2 R1234ze 3 R1234yf 4 R1270 5 R227 6 R600a u...

Страница 3: ...fter 5 minutes the display will return to the value selected by parameter 1 Service Troubleshooting Symptom Cause Action Operating superheat is several degrees higher or lower than set point Incorrect signal from pressure or temperature sensors 1 Check the sensors 2 Make sure ECN N60 temperature sensor is used 3 For optimum accuracy please use PT5 30L FLR 4 Make sure the sensor cables are not inst...

Страница 4: ...den Imbusschlüssel in die Löcher auf der Frontseite einstecken und im Uhrzeigersinn drehen Die Halterungen treten aus dem Gehäuse hervor und bewegen sich in Richtung Frontplatte 2 Imbusschraube drehen bis die erste Halterung die Frontplatte leicht berührt Dann zweite Halterung in diese Position bringen 3 Beide Seiten gleichmäßig und nicht zu fest anziehen Hinweis durch zu festes Anziehen können di...

Страница 5: ...r werden auf Werkseinstellung zurückgesetzt PRG drücken die gewählte Funktion wird aktiviert und die Betriebsart Spezial funktionen verlassen Startverhalten der Regelventile Parameter uu und u9 EX4 5 6 FLR 1 5 Sekunden EX7 FLR 3 2 Sekunden Haupt Parameter müssen ggf angepasst werden Code Beschreibung und Wahlmöglichkeiten Min Max Werk Kunde H5 Passwort 1 199 12 u0 Kältemittel 0 6 0 0 R290 1 R32 2 ...

Страница 6: ...angezeigt Service Fehlersuche Fehlerbeschreibung Ursache Aktion Überhitzung ist einige Grad höher oder niedriger als der Einstellwert Fehlerhaftes Signal von Druck oder Temperatursensoren 1 Sensoren überprüfen 2 ECN N60 als Temperatursensor einsetzen 3 EMERSON Drucktransmitter verwenden PT5 30L FLR 4 Sensorkabel nicht zusammen mit stromführenden Leitungen verlegen Überhitzung ist zu niedrig Verdic...

Страница 7: ...I Germany Date 04 03 2017 EC3 P33_OI_ML_R01_865919 docx 2 2a 2b 0 R290 4 R1270 1 R32 5 R227 2 R123ze 6 600a 3 R123yf 2 3 3a 3b PT5 30L FLR R290 3c 4 4a 4b 0 EX4 FLR 1 EX5 FLR 2 EX6 FLR 3 EX7 FLR 4c 4d 4e Display of Data 0 1 1a 1b 1c 1d 1e EX7 FLR 5 sec 1 199 88 12x EX4 EX5 EX6 EX7 EX8 Po To Ts Vo Ts C To C SH Ts To K 100 0 Po barg EC3X_65130 cdr R22 ...

Отзывы: