EC3-932_65149_EN_R02.doc  Replacement for R01 

3 / 4  

PCN: 865 874      22.09.2009 

 

 

EC3-932 Rack and Condenser Controller and ECD-000 Display Unit 

Operating Instructions 

GB 

List Of Parameters 

 

/ DISPLAY 

PARAMETERS 

Min Max

 

Unit Def. Custom

/1  Value to show 

 

  0 = Compressors and fans states (controller 1 and controller 2) 

1 = Suction pressure (bar) 
2 = Saturation temperature (°C) calculated from suction pressure  
3 = Condensing pressure (bar) 
4 = Saturation temperature (°C) calculated from discharge pressure 
5 =  Digital Scroll capacity (%); 6 = Variable fan speed capacity % 

  Controller C1 (Rack Controller) 

 

 

 

 

 

P SET-POINT PARAMETERS (C1) 

 

 

 

 

 

P0

 

Suction pressure set point 

-1 

50 

bar 

3.0 

 

P1

 

Suction band 

50 

bar 

2.0 

 

P3

 

Fast recovery from low pressure 

-9.9

50 

bar 

-9.9 

 

P4

 

Suction shift (0=disabled, 1=enabled) 

 

P5

 

Suction shift max 

3.0 

bar 

3.0 

 

P8  High discharge pressure recovery 

-9.9

50 

bar 

50.0

 

P9  Discharge recovery step 

5.0 

bar 

1.0 

 

t  TIME PARAMETERS (C1) 

 

 

 

 

 

t0  Integration time 

30 

99  10 sec*  60 

 

t1  Time delay before adding capacity 

99  10 sec* 

 

t2  Time delay before removing capacity 

99  10 sec*  0.2 

 

t3  Compressor min on time 

99  10 sec* 

 

t4  Compressor min off time 

99  10 sec* 

 

t5  Maximum compressor switching 

(0=number of switching unrestricted) 

0 199 1/hr  0 

 

A ALARM-PARAMETERS (C1) 

 

 

 

 

 

A0  Alarm delay LP 

99  10 sec* 

 

A1  Alarm delay HP 

99  10 sec* 

 

A2  Suction alarm min. limit 

-1.0

50 

bar 

1.0 

 

A3  Suction alarm max. limit 

-1.0

50 

bar 

6.0 

 

A4  Alarm delay suction min. limit 

99  10 sec* 

 

A5  Alarm delay suction max. limit 

99  10 sec* 

0  

 

A6  Maximum discharge temperature 

50 

150 

°C 

130 

 

A7  Maximum discharge temperaturedelay 

99  10 sec* 

 

A8  Alarm delay serial alarm comp. 

99  10 sec* 

 

A9  Compressor service interval 

99 

10,000hr** 

 

u  STEP ENABLE PARAMETERS (C1) 

 

u0  Compressor service interval reset 

 

  0 = do nothing 

1 = reset operating time compr. 1 
2 = reset operating time compr. 2 

3 = reset operating time compr. 3
4 = reset operating time compr. 4
5 = reset op. time all compressors

u1  Compressor 1:     0=disable, 1=enable 

flag 

 

u2  Compressor 2 enable      (  - " -  ) 

flag 

 

u3  Compressor 3 enable      (  - " -  ) 

flag 

 

u4  Compressor 4 enable      (  - " -  ) 

flag 

 

c  APPLICATION PARAMETERS (C1) 

 

 

 

 

 

c1  Number of compressors 

 

c3  Compr. control mode (0 = P mode,  

0 3  - 

 

  1 = PI mode, 

2 = dead band mode

  3 = binary mode) 

c4  Compressor 1 control mode 

 

  0 = in standard control loop      1 = act as base load compressor 

2 = act as modulating capacity

; function defined by parameter F5 

c5 Compressor rotation 

flag 

 

  0 = FILO logic (First In, Last Out)  1 = FIFO logic (First In, First Out) 

c6  Sensor fail  

 

  (number of compressors in case of sensor failure) 

 

h0  Discharge pressure sensor  

0 = not available; 1 = available 

0 1 flag 1 

 

SENSOR PARAMETERS (C1) 

 

 

 

 

 

r0  Suction sensor 0% 

-1.0

50 

bar 

-0.8 

 

r1  Suction sensor 100% 

-1.0

50 

bar 

 

r2  Suction sensor offset 

-1.0

1.0 

bar 

0.0 

 

r3 Refrigerant 

 

  0 = R 22 

1 = R 134a 

2 = R 507 
3 = R 404A 

4 = R 407C 
5 = R 410A 

6 = R 124 
7 = R 744 

 

 

*  Resolution = 10 sec,

 

on the local display. Example a value 2 means 20 sec. 

** Resolution = 10,000 hrs.

 

on the local display. Example a value 2 means 2.000 hours.

 

 

F MODULATING PARAMETERS (C1) 

Min

 

Max

 

Unit Def.

 

Custom

F2 Minimum output value (F5 = 0 or 1) 

10 

100 

10 

 

F3 Maximum output value (F5 = 0 or 1) 

10 

100 

100 

 

F3 PWM rate if F5 = 2 (Digital Scroll) 

10 

20 

sec 

10 

 

F5 Analogue output mode for Comp. 1 

0 or 1 = 0 … 10V; 2 = PWM (digital) 

0 2  -  2 

 

  Controller C2 (Condenser Controller) 

P SET-POINT PARAMETERS (C2) 

 

 

 

 

 

P0 Condensing pressure set point 

-1 

50 

bar 

14.0 

 

P1 Cond. pressure band 

50 

bar 

4.0 

 

P2 Condensing pressure set point 2 

-1 

50 

bar 

14.0 

 

P3 Condensing recovery min 

-9.9  50.0 

bar 

-9.9 

 

P4 Condensing shift (0 = off, 1 = on) 

 

P5 Condensing shift max 

0.0 

3.0 

bar 

3.0 

 

P6 Condensing shift temp min 

-50 

50 

°C 

30°C 

 

P7 Condensing shift temp max 

-50 

50 

°C 

15°C 

 

P8 Condensing recovery max 

-9.9 

50 

bar 

50 

 

t  TIME PARAMETERS (C2) 

 

 

 

 

 

t0  Integration time 

30 

99  10 sec*

60 

 

t1  Time delay before adding capacity 

99  10 sec*

 

t2  Time delay before removing capacity 

99  10 sec*

 

A ALARM-PARAMETERS (C2) 

 

 

 

 

 

A1 Alarm delay HP 

99  10 sec*

 

A2 Condensing alarm limit min 

-1.0 50  bar  10 

 

A3 Condensing alarm limit max 

-1.0 50  bar  27 

 

A4 Alarm delay condensing limit min 

0 99 

10 

sec*

 

A5 Alarm delay condensing limit max 

0 99 

10 

sec*

 

A8 Alarm delay serial alarm fan 

0 99 

10 

sec*

 

A9 Service interval 

0 99 

1,000 hr**

 

u  STEP ENABLE PARAMETERS (C2)

 

u0 Fan service interval reset 

 

  0 = do nothing 

1 = reset operating time fan 1 
2 = reset operating time fan 2 

3 = reset operating time fan 3 
4 = reset op. time all fans 

u1 Fan 1 enable      (0=disable, 1=enable)  0 

flag 

 

u2 Fan 2 enable      (0=disable, 1=enable)  0 

flag 

 

u3 Fan 3 enable      (0=disable, 1=enable)  0 

flag 

 

c  APPLICATION PARAMETERS (C2) 

 

 

 

 

 

c1 Number of fans 

 

c3 Control mode (0 = P mode,  

1 = PI mode, 2 = dead band mode) 

0 2  -  2 

 

c4 First fan control mode 

 

  0 = in standard control loop,  

1 = act as base load fan,  

2 = act as modulating capacity (0…10V 
for inverter command or TRIAC output)

c5 Fan rotation 

flag 

 

0 = FILO logic (First In, Last Out)  1 = FIFO logic (First In, First Out) 

c6 Sensor fail 

(nr. of fans in case of sens fail)

 0  3 

 

r  SENSOR PARAMETERS (C2) 

 

 

 

 

 

r0 Condensing sensor  0% 

-1.0 

50 

bar 

0.0 

 

r1 Condensing sensor 100% 

-1.0 

50 

bar 

30 

 

r2 Condensing sensor offset 

-1.0  1.0 

bar 

0.0 

 

F  MODULATING PARAMETERS (C2) 

 

 

 

 

 

F2 Fan 1 min speed (if controlled) 

100 

 

F3 Fan 1 max speed (if controlled) 

100 

100 

 

F4 Fan 1 at min: (0=off; 1 =min speed) 

flag 

 

F7 Output mode for modulating fan 1:  

flag 

 

 

0 = 0 – 10V analogue output;  1 = Phase cutting with Triac 

H  OTHER PARAMETERS  

 

 

 

 

 

H2 ECD Display access   

 

  0 =  all disabled (Caution, access 

to controller only via TCP/IP 
network possible) 

 

1 =  Keyboard enabled 
2 =  IR remote control enabled 
3 =  Keyboard and IR remote 

control enabled 

H3 IR access code 

199 

 

H5 Password 0 

199 

12

 

 

Содержание EC3-932

Страница 1: ...l display of control parameters and for controller setup without the use of a PC Because the EC3 932 is fully functional without display unit the ECD 000 may be removed at any time Safety instructions Read installation instructions thoroughly Failure to comply can result in device failure system damage or personal injury The product is intended for use by persons having the appropriate knowledge a...

Страница 2: ...meters modification procedure To exit without modifying any parameter Do not press any button for at least 60 seconds TIME OUT Press ESC on IR remote control Special Functions The Clear Alarm function has been replaced by the Special Functions mode The Special Functions can be activated by Press and together for more than 5 seconds A flashing 0 is displayed Press or until the password is displayed...

Страница 3: ...0 50 bar 7 r2 Suction sensor offset 1 0 1 0 bar 0 0 r3 Refrigerant 0 7 3 0 R 22 1 R 134a 2 R 507 3 R 404A 4 R 407C 5 R 410A 6 R 124 7 R 744 Resolution 10 sec on the local display Example a value 2 means 20 sec Resolution 10 000 hrs on the local display Example a value 2 means 2 000 hours F MODULATING PARAMETERS C1 Min Max Unit Def Custom F2 Minimum output value F5 0 or 1 10 100 10 F3 Maximum outpu...

Страница 4: ...nabling the controller to be directly connected to a PC or network via the standard Ethernet port The EC3 932 controller has embedded WebPages to enable the user to easily visualise the parameter lists using real text labels No special software or hardware is required Connect the EC3 932 using the optional ECX N60 cable assembly to a network or hub that enables the controller to receive a dynamic ...

Отзывы: