EC3-751_65087_EN_R04.doc 

Replacement for R03 

2 / 5 

DWG Nr.: 864 915     26.09.2007 

 

 

EC3-751 Condenser Controller with LON Interface 

Operating Instructions 

GB 

Electrical Installation 

Refer to the electrical wiring diagram (below) for electrical connections. A copy of 
this diagram is labeled on the controller. Use connection wires/cables suitable for 
90°C operation (EN 60730-1). Ground the metal housing with a 6.3mm spade 
connector. 

Important:

 Keep controller and sensor wiring well separated from mains wiring. 

Minimum recommended distance 30mm..

  

Warning:

 Use a class II category transformer for 24VAC power supply 

(EN 60742). Do not ground the 24VAC lines. We recommend to use one 
transformer per EC3 controller and to use separate transformers for 3

rd

 party 

controllers, to avoid possible interference or grounding problems in the power 
supply. Connecting any EC3 inputs to mains voltage will permanently damage the 
EC3. 

Setup and Parameter Modification Using the Keypad of the ECD-000 

For convenience, an infrared receiver for the optional 

IR remote control unit

 is 

build-in, enabling quick and easy modification of the system parameters when a 
computer interface is not available. 
Alternatively, the parameters can be accessed via the 4-button keypad. The 
configuration parameters are protected by a numerical password. The default 
password is “12”. To select the parameter configuration: 

 

Press the 

PRG

 button for more than 5 seconds  

  A flashing 0 is displayed 

 

Press   or   until 12 is displayed; (password) 

 

Press 

SEL

 to confirm password 

  The first modifiable parameter code is displayed (/1). 
To modify parameters see Parameters modification below. 

Parameter Modification: Procedure 

 

Press   or   to show the code of the parameter that has to be changed; 

 

Press 

SEL

 to display the selected parameter value;  

 

Press   or   to increase or decrease the value; 

 

Press 

SEL

 to temporarily confirm the new value and display its code;  

 

Repeat the procedure from the beginning "

press 

 or 

to show...

To exit and save the new settings: 

 

Press 

PRG

 to confirm the new values and exit the parameters modification 

procedure. 

To exit without modifying any parameter: 

 

Do not press any button for at least 60 seconds (TIME OUT). 

 

Press “

ESC

” on IR remote control. 

Neuron Id / Service Pin: 

 

The service pin is available on ECD display and on the controller. It is only 
needed, when using controller in a LON network. 

 

Display:  
Press the   button for app. 1 second to send the Neuron ID. An LED (Service) in 
the left upper corner will indicate the transmission of the Neuron ID.  

 

Controller: 

ECD-001

 

There is a small hole left of the network connector. Use a small pen or 
screwdriver to press the switch behind the hole. An LED close to the switch will 
light to indicate the transmission of the Neuron ID.  

 

Load Default Parameters: 

 

Use a small pen or screwdriver to press the service pin switch on the controller 
and switch on the power supply on. The EC3-751 will be reset to its default 
settings. 

 

 

Special Functions: 

The Clear Alarm function has been replaced by the Special Functions mode. The 
Special Functions can be activated by:

 

 

Press   and   together for more than 5 seconds. 

 

 

A flashing 0 is displayed. 

 

Press   or   until the password is displayed (default = 12). If password was 
changed, select the new password. 

 

Press 

SEL

 to confirm password 

 

 

A 0 is displayed and the Special Function mode is activated. 

 

Press   or   to select the function. The number of special functions is dynamic 
and controller dependent. See list below. 

 

Press 

SEL

 to activate the function without leaving the special function mode. 

 

Press 

PRG

 to activate the function and leave the special function mode. 

Most of the Special Functions work in a toggle mode, the first call activates the 
function, and the second call deactivates the function. 
The indication of the function can only be displayed after exiting the special 
function mode. 

 

0: Display test function 

 

1: Resets all parameters to the factory default setting. The controller will 
indicate “oF” during the reset. 

Display of Data: 

The data to be permanently shown on the display can be selected by the user (parameter 
/1). In case of an alarm, the alarm code is displayed alternately with the selected data. 
The user can inhibit the alarm code.  
It is possible to temporarily display these values. This is a useful feature when 
initially setting-up the system without the aid of the WebPages. Press the 

SEL

 

button to scroll through all possible displayable data.. The display will show for one 
second the numerical identifier of the data (see /1 parameter) and then the selected data. 
After two minutes the display will return to the by parameter /1 selected data. This 
action is only valid when parameter H2 = 3 
 IR 

LED 

 

Fan 7 On

Controller LED

Service LED

Press. Sensor LED

Pressure LED

Alarm LED

Fan 6 On

Fan 5 On

Fan 1 On 

Fan 2 On 

 

 

 

 

 

Fan 3 On 

Fan 4 On 

 
 

Wiring Diagram (controller label) 

 

 

 

 

 

Содержание EC3-751

Страница 1: ...nal without display unit the ECD 000 may be removed at any time Safety instructions Read installation instructions thoroughly Failure to comply can result in device failure system damage or personal injury It is intended for use by persons having the appropriate knowledge and skill Ensure electrical ratings per technical data are not exceeded Disconnect all voltages from system before installation...

Страница 2: ...needed when using controller in a LON network Display Press the button for app 1 second to send the Neuron ID An LED Service in the left upper corner will indicate the transmission of the Neuron ID Controller ECD 001 There is a small hole left of the network connector Use a small pen or screwdriver to press the switch behind the hole An LED close to the switch will light to indicate the transmissi...

Страница 3: ...0 disable 1 enable 0 1 1 u4 Fan enable 4 0 disable 1 enable 0 1 1 u5 Fan enable 5 0 disable 1 enable 0 1 1 u6 Fan enable 6 0 disable 1 enable 0 1 1 1 Resolution of the local ECD 000 display is 10sec E g value 2 means 20sec 2 Resolution of the local ECD 000 display is 10 000h E g value 2 means 20 000h EMS allows data entry in sec 1000hr c APPLICATION PARAMETERS Min Max Unit Def Individ c1 Number of...

Страница 4: ...ter a major change of the configuration parameter the condenser controller is disabled for 20 seconds After this delay the controller restart automatically The condenser controller is disabled with object status or with the network variable nviContEnable N B When cleaning the display use damp cloth and neutral detergent Visualising Data LON Monitoring Server The EC3 751 has a LON communication int...

Отзывы: