EC3-751_65087_EN_R04.doc 

Replacement for R03 

1 / 5 

DWG Nr.: 864 915     26.09.2007 

 

 

EC3-751 Condenser Controller with LON Interface 

Operating Instructions 

GB 

 

Contents: 

Safety instructions: 

Technical data: 

Mounting 1 
Electrical Installation 

Setup and Parameter Modification 
  using the Keypad 

Temporary Display of Data: 

Load Default Parameters: 

Special Functions 

Indications On The Display 

Alarm Codes and Messages 

Parameter List 

Visualising Data 

 
 
Note: This document contains short form instructions for experienced users. 
Use last column in List of Parameters to document your individual settlings. 
More detailed information can be found in the User Manual.  

 

 

 
 

The 

EC3-751

 condenser controller is a digital controller for air cooled condensers. 

The condenser may consist of up to 6 fans, one of which is continuously speed 
controlled. The control target is to maintain the condensing pressure at a defined 
value by varying the available fan capacity.  

 

For the measurement of the condensing pressure, a PT4 pressure sensor (3) with 4 
– 20 mA interface can be connected to the controller. The condenser controller has 
eight relay outputs, six to command the fans (7), one for the heat recovery solenoid 
(9) and one for General Alarm. Eight digital inputs for 24V AC/DC or 230V AC 
are available, six for fan serial alarm (4), one for high pressure alarm (5) and one 
for heat recovery demand (6). The first fan (8) can be continuously speed 
controlled by the analogue output 0 to 10V with an ALCO FSP Fan Speed 
Controller or directly with the onboard TRIAC. The fan power supply must be 
connected to the Triac. To meet the EMC compliance in this case, an external filter 
must be fitted. Two analogue inputs (1) can be used to measure a control 
temperature and the ambient temperature. A 4…20mA input (2) is reserved for the 
relative humidity sensor.  
The optional 

ECD-000

 Display Unit can be connected to the EC3-751 for local 

display of control parameters and for controller setup without the use of a PC. 
Because the EC3-751 is fully functional without display unit the ECD-000 may be 
removed at any time. 
 

!

  Safety instructions:  

 

Read installation instructions thoroughly. Failure to comply can result in 
device failure, system damage or personal injury. 

 

It is intended for use by persons having the appropriate knowledge and skill.  

 

Ensure electrical ratings per technical data are not exceeded.  

 

Disconnect all voltages from system before installation. 

 

Keep temperatures within nominal limits.  

 

Comply with local electrical regulations when wiring 

Technical Data

 

EC3 Series Controller 

Power supply 

24VAC ±10%; 50/60Hz; Class II 
6.3mm spade earth connector 

Power consumption 

20VA max. 

Communication LON 

FTT10 

Plug-in connector size 

Removable screw terminals 
wire size 0.14 … 1.5 mm

2

 

Temperature storage
  

operating 

   -20 … +65°C 
 

0 … +60°C 

Humidity 

0…80% r.h.  non condensing 

Protection class 

IP20 

Pressure transmitter inputs 

24VDC, 4...20mA 

2 Temp. inputs for Ambient and
Control Temperature (1) 

NTC 10 k

 @ 25°C, -50 … +50°C

 

Humidity transmitter input (2)  24VDC, 4...20mA, 2 wires 
Digital Inputs 

24VAC/DC or 230VAC 

Fan output relays  

Inductive (AC15) 250V/2A 

(6x) + General alarm  

Resistive (AC1) 250V/8A 

Heat recovery output 

 

Triac rating 

 250V AC, max. 2A 

ECD-000 Display Unit 

Power Supply 

From EC3-751 via connecting cable 

Display 

2½-digit red LED with decimal point 
reversible between °C and °F 

LED indicators 

Controller 1, Controller 2, p bar, Alarm, IR status 

Temp & Humidity 

Identical to EC3-751 specifications above 

Protection class 

IP65 (front protection with gasket) 

Connecting cable 

ECC-N10 (1m), ECC-N30 (3m), ECC-N50 (5m) or 
CAT5 cable with RJ45 connectors 

Mounting 

The EC3-751 can be mounted onto a standard DIN rail. 

 

 
The ECD-000 can be mounted in panels 
with a 71x29 mm cutout. See dimensional 
drawing below for space requirements 
including rear connectors. 
Push controller into panel cutout. (1) 
Make sure that mounting lugs are flush with 
outside of controller housing 
Insert allen key into front panel holes and 
turn clockwise. Mounting lugs will turn and 
gradually move towards panel (2) 
Turn allen key until mounting lug barely 
touches panel. Then move other mounting 
lug to the same position (3) 
Tighten both sides very carefully until 
display is secured. Do not over tighten as 
mounting lugs will break easily. 

 

 

 

Содержание EC3-751

Страница 1: ...nal without display unit the ECD 000 may be removed at any time Safety instructions Read installation instructions thoroughly Failure to comply can result in device failure system damage or personal injury It is intended for use by persons having the appropriate knowledge and skill Ensure electrical ratings per technical data are not exceeded Disconnect all voltages from system before installation...

Страница 2: ...needed when using controller in a LON network Display Press the button for app 1 second to send the Neuron ID An LED Service in the left upper corner will indicate the transmission of the Neuron ID Controller ECD 001 There is a small hole left of the network connector Use a small pen or screwdriver to press the switch behind the hole An LED close to the switch will light to indicate the transmissi...

Страница 3: ...0 disable 1 enable 0 1 1 u4 Fan enable 4 0 disable 1 enable 0 1 1 u5 Fan enable 5 0 disable 1 enable 0 1 1 u6 Fan enable 6 0 disable 1 enable 0 1 1 1 Resolution of the local ECD 000 display is 10sec E g value 2 means 20sec 2 Resolution of the local ECD 000 display is 10 000h E g value 2 means 20 000h EMS allows data entry in sec 1000hr c APPLICATION PARAMETERS Min Max Unit Def Individ c1 Number of...

Страница 4: ...ter a major change of the configuration parameter the condenser controller is disabled for 20 seconds After this delay the controller restart automatically The condenser controller is disabled with object status or with the network variable nviContEnable N B When cleaning the display use damp cloth and neutral detergent Visualising Data LON Monitoring Server The EC3 751 has a LON communication int...

Отзывы: