Set Up Echelon Network
Setup
•
15
put boards on this E2’s I/O Network.
4AO Boards
Enter the number of 4AO analog out-
put boards on this E2’s I/O Network.
IRLDS Controllers
Enter the number of leak detec-
tor units on this E2’s I/O Network.
(Options will vary depending on the type of controller
used.)
3.6.2
Checking Online Status
Figure 3-11
- Network Summary Screen
You can check all boards that are on either the Echelon
Network (E2 controllers) or the I/O Network from the Net-
work Status screen (See
). The Network Sum-
mary screen displays information such as the Subnet and
Node addresses for each board, and the status of Echelon
and I/O boards.
To get to the Network Summary Screen:
1.
Press
to open the Main Menu.
2.
Press
(System Configuration).
3.
Press
(Network Setup).
4.
Press
(Network Summary).
From the Network Summary screen you can see the
total (E2) devices online or offline, status, setup screens,
change board or controller names, configure and commis-
sion devices, delete a device, and view detailed status
screens of controllers.
After determining if a board is offline, turn to
3.7
Set Up Echelon
Network
3.7.1
Specifying Number of
Devices
To specify the number of devices on the Echelon Net-
work, navigate to the Connected I/O screen:
1.
Press
to open the Main Menu.
2.
Press
(System Configuration).
3.
Press
(Network Setup).
4.
Press
(Connected I/O Boards & Controllers).
Figure 3-12
- Connected I/O Screen (RX version shown)
After logging in for the first time, the Connected I/O
screen will ask you to specify how many of each type of
device will be connected to the E2 you are currently pro-
gramming. (Options will vary depending on the type of
controller used.)
Unit Number (Echelon Subnet)
Each E2 on the
Echelon Network must have a different unit number.
This can be any number from 1 to 255, but each E2’s
number must be unique. No two E2s on the network
may have the same unit number.
Enter this number in the Unit Number field. It is rec-
ommended you number the first E2 “1” and number
the other E2s on the network sequentially (2, 3, 4,
etc.).
Unit Name
Type a name for the E2 in the Unit
Name field.
Unit Controllers (Echelon)
Liquid Ctrls (CC100P/CC100LS)
Enter the com-
bined number of pulse valve case controllers