Emerson dixell XR02CX Скачать руководство пользователя страница 2

 

SZ 1598030250 XR02CX RWA GB r1.2 29.08.2013.doc 

                           XR02CX 

2/2 

dA 

Exclusion of temperature alarm at startup: (0 to 99min) time interval between the detection 
of the temperature alarm condition after instrument power on and alarm signalling. 

OTHER 

d1 

Room probe instant value (read only) 

d2 

Evaporator probe instant value (read only) 

rS 

Real Set Poin value (read only) 

Pt 

Parameter code table (read only) 

rL 

Software release (read only) 

INSTALLATION AND MOUNTING 

 

Instrument  XR02CX  shall  be  mounted  on  vertical  panel,  in  a 
29x71 mm hole, and fixed using the special bracket supplied. 
The temperature range allowed for correct operation is 0 to 60°C. 
Avoid  places  subject  to  strong  vibrations,  corrosive  gases, 
excessive  dirt  or  humidity.  The  same  recommendations  apply  to 
probes. Let air circulate by the cooling holes. 

 

 

ELECTRICAL CONNECTIONS 

The  instrument  is  provided  with  screw  terminal  block  to  connect  cables  with  a  cross  section  up  to 
2.5mm

2

.  Before  connecting  cables  make  sure  the  power  supply  complies  with  the  instrument’s 

requirements.  Separate  the  probe  cables  from  the  power  supply  cables,  from  the  outputs  and  the 
power  connections.  Do  not  exceed  the  maximum  current  allowed  on  each  relay,  in  case  of  heavier 
loads use a suitable external relay. 

8.1 

PROBES 

The  probes  shall  be  mounted  with  the  bulb  upwards  to  prevent  damages  due  to  casual  liquid 
infiltration.  It  is  recommended  to  place  the  thermostat  probe  away  from  air  streams  to  correctly 
measure  the  average  room  temperature.  Place  the  defrost  termination  probe  among  the  evaporator 
fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during 
defrost, to prevent premature defrost termination. 

HOW TO USE THE HOT KEY 

9.1 

HOW TO PROGRAM THE HOT KEY FROM THE INSTRUMENT 
(UPLOAD) 

1.

 

Program one controller with the front keypad. 

2.

 

When the controller is ON, insert the “Hot-key” and push UP key; the  "uP" message appears followed 
a by flashing “En” 

3.

 

Push “SET” key and the “En” will stop flashing. 

4.

 

Turn OFF the instrument and then remove the “Hot-key”. After that turn it ON again. 

 
NOTE:  the  “Er”  message  is  displayed  for  failed  programming.  In  this  case  push  again  o  key  if  you  want  to 
restart the upload again or remove the “Hot-key” to abort the operation. 

9.2 

HOW TO PROGRAM AN INSTRUMENT USING HOT KEY 
(DOWNLOAD) 

1.

 

Turn OFF the instrument. 

2.

 

Insert a programmed Hot Key into the 5 PIN receptacle and then turn the Controller ON. 

3.

 

Automatically  the  parameter  list  of  the  “Hot-key”  is  downloaded  into  the  Controller  memory,  the  “do” 

message is blinking followed a by flashing “En”. 
4.

 

After 10 sec the instrument will restart working with the new parameters.  

5.

 

Remove the “Hot-key”. 

 
NOTE:  the  “Er”  message  is  displayed  for  failed  programming.  In  this  case  push  again  o  key  if  you  want  to 
restart the upload again or remove the “Hot-key” to abort the operation. 

10 

ALARM SIGNALLING 

Mess.  Cause 

Outputs 

P1 

Room probe failure 

Compressor output according to Cy e Cn  

P2 

Evaporator probe failure 

Defrost end is timed 

HA 

Maximum temperature alarm 

Outputs unchanged 

LA 

Minimum temperature alarm 

Outputs unchanged 

5.1 

ALARM RECOVERY 

Probe alarms “P1” and “P2” start some seconds after the fault in the related probe; they automatically 
stop some seconds after the probe restarts normal operation. Check connections before replacing the 
probe. Temperature alarms  “HA” and  “LA” automatically stop as soon as the temperature returns to 
normal values. 

11 

TECHNICAL DATA 

Housing: self extinguishing ABS 
Case: 
frontal 32x74 mm; depth 60mm 
Mounting: panel mounting in a 71x29mm panel cut-out 
Protection: IP20  
Frontal protection: IP65 
Connections: disconnectable terminal block 

 2.5 mm

2

 wiring and 6.3mm fast-on  

Power supply: according to the model ±10%; 230Vac 

10%, 50/60Hz, 110Vac 

10%, 50/60Hz 

Power absorption: 3.5 VA max 
Display:
 2 digits, red LED, 14.2 mm high; Inputs: 2 NTC 
Relay outputs: compressor 
SPST 8(3) A, 250Vac; 20(8)A 250Vac 
Data storing:
 on the non-volatile memory (EEPROM). 
Kind of action: 1B  
Pollution degree: 2  
Software class: 
Rated impulsive voltage: 2500V  
Overvoltage Category: II 
Operating temperature: 
0 to 60°C (32 to 140°F) 
Storage temperature: -30 to 85°C (-22 to 185°F) 
Relative humidity: 20 to 85% (not condensing) 
Measuring and regulation range: NTC -40 to 110°C (-40 to 230°F). 

Resolution: 0.1°C or 1°C or 1°F (selectable)  
Accuracy (ambient temp. 25°C): ±0.7°C ±1 digit 

12 

CONNECTIONS 

12.1 

20A COMPRESSOR RELAY 

 

 
NOTE: 
in case of 110Vac model, connect power supply to terminals 6-7. 

13 

DEFAULT SETTING VALUES 

LABEL 

DESCRIPTION 

RANGE 

 

REGULATION 

 

Hy 

Differential 

0.1 to 25°C; 1 to 45°F 

LS 

Minimum Set Point 

-55°C to SET; -67°F to SET 

US 

Maximum Set Point 

SET to 99°C; SET to 210°F 

ot 

First probe calibration 

-9.9 to 9.9°C; -17 to 17°F  

P2 

Second probe presence 

n; Y 

oE 

Second probe calibration 

-9.9 to 9.9°C; -17 to 17°F 

F5 

Filter probe enabling 

nu; AL; do 

od 

Outputs activation delay at start up 

0 to 99 min 

AC 

Anti-short cycle delay 

0 to 50 min 

Cy 

Compressor ON time faulty probe 

0 to 99 min 

Cn 

Compressor OFF time faulty probe 

0 to 99 min 

 

DISPLAY 

 

CF 

Measurement units 

°C; °F 

rE 

Resolution (only for °C) 

dE; in 

Ld 

Default Display 

P1; P2 

dy 

Display delay 

0 to 15 min 

 

DEFROST 

 

dE 

Defrost termination temperature 

-50 to 50°C; -58 to 122°F 

id 

Interval between defrost cycles 

0 to 99 hours 

Md 

Maximum length for defrost 

0 to 99 min. 

dF 

Display during defrost 

rt; in; dE 

 

ALARMS 

 

AU 

Maximum temperature alarm 

ALL to 99°C; ALL to 210°F 

AL 

Minimum temperature alarm 

-55°C to ALU; -67°F to ALU 

Ad 

Temperature alarm delay 

0 to 99 min 

dA 

Exclusion  of  temperature  alarm  at 
startup 

0 to 99 min 

 

OTHER 

 

d1 

Room probe display 

Read Only 

d2 

Evaporator probe display 

Read Only 

rS 

Real set point 

Read Only 

Pt 

Parameter code table 

Read Only 

rL 

Firmware release 

Read Only 

 