Emerson dixell XR02CX Скачать руководство пользователя страница 1

 

SZ 1598030250 XR02CX RWA GB r1.2 29.08.2013.doc 

                           XR02CX 

1/2 

DIGITAL CONTROLLER 

XR02CX 

1

 

GENERAL WARNINGS ................................................................................................................................... 1

 

2

 

GENERAL DESCRIPTION .............................................................................................................................. 1

 

3

 

REGULATION .................................................................................................................................................. 1

 

4

 

DEFROST ........................................................................................................................................................ 1

 

5

 

FRONT PANEL COMMANDS ......................................................................................................................... 1

 

6

 

PARAMETERS ................................................................................................................................................ 1

 

7

 

INSTALLATION AND MOUNTING.................................................................................................................. 2

 

8

 

ELECTRICAL CONNECTIONS ....................................................................................................................... 2

 

9

 

HOW TO USE THE HOT KEY ........................................................................................................................ 2

 

10

 

ALARM SIGNALLING ...................................................................................................................................... 2

 

11

 

TECHNICAL DATA .......................................................................................................................................... 2

 

12

 

CONNECTIONS............................................................................................................................................... 2

 

13

 

DEFAULT SETTING VALUES ........................................................................................................................ 2

 

 

GENERAL WARNINGS 

1.1  PLEASE READ BEFORE USING THIS MANUAL 

 

This  manual  is  part  of  the  product  and  should  be  kept  near  the  instrument  for  easy  and  quick 
reference. 

 

The instrument shall not be used for purposes different from those described hereunder. It cannot be 
used as a safety device. 

 

Check the application limits before proceeding. 

1.2  SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden 
temperature changes with high atmospheric humidity to prevent  formation of condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be opened. 

 

In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.r.l.” (see 
address) with a detailed description of the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure that the wires for probes, loads and the power supply are separated and far enough from each 
other, without crossing or intertwining. 

 

In  case  of  applications  in  industrial  environments,  the  use  of  mains  filters  (our  mod.  FT1)  in  parallel 
with inductive loads could be useful. 

 

Dixell  Srl  reserves  the  right  to  change  the  composition  of  its  products,  even  without  notice,  ensuring 
the same and unchanged functionality. 

GENERAL DESCRIPTION 

Model  XR02CX,  format  32  x  74  x  50  mm,  is  a  digital  thermostat,  with  off  cycle  defrost,  designed  for 
refrigeration  applications  at normal temperature. It provides a relay output to drive the compressor.  It is also 
provided with 2 NTC probe input. The instrument is fully configurable through special parameters that can be 
easily programmed through the keyboard or the by HOT-KEY

REGULATION 

3.1  THE REGULATION OUTPUT 

The  regulation  is  performed  according  to 
the  temperature  measured  by  the 
thermostat probe with a positive differential 
from  the  set  point:  if  the  temperature 
increases  and  reaches  set  point  plus 
differential  the  compressor  is  started  and 
then  turned  off  when  the  temperature 
reaches the set point value again. 

 

In case of fault in the thermostat probe the start and stop of the compressor are timed through parameters CY 
and Cn

DEFROST 

Defrost  is  performed  through  a  simple  stop  of  the  compressor.  Parameter  id  controls  the  interval 
between defrost cycles, while its length is controlled by parameter Md

FRONT PANEL COMMANDS 

 

 

 

To display target set point, in  programming  mode it selects  a parameter or confirm  an 
operation 

 

(DEF) To start a manual defrost 

 

(UP) In programming mode it browses the parameter codes or increases the displayed 
value 

 

AUX 

(DOWN)  In  programming  mode  it  browses  the  parameter  codes  or  decreases  the 
displayed value 

 
KEYS COMBINATION 

 

+

 

 

To lock or unlock the keyboard

 

 

+

 

 

To enter in programming mode 

 

+

 

 

To return to room temperature display

 

 

LED 

MODE 

MEANING 

 

On 

Compressore enabled 

Flashing 

Anti short cycle delay enabled (AC parameter) 

 

On 

Defrost in progress 

Flashing 

Dripping in progress 

 

On 

Measurement unit  

Flashing 

Programming mode 

 

On 

Measurement unit 

Flashing 

Programming mode 

5.1 

HOW TO SEE THE SET POINT 

1.

 

Push and immediately release the SET key, the set point will be showed; 

2.

 

Push and immediately release the SET key or wait about 5 sec to return to normal visualisation. 

5.2 

HOW TO CHANGE THE SETPOINT 

1.

 

Push the SET key for more than 2 sec to change the Set point value; 

2.

 

The value of the set point will be displayed and the “°C” or “°F” LED starts blinking; 

3.

 

To change the Set value, push the o or n arrows within 10 sec. 

4.

 

To memorise the new set point value push the SET key again or wait for 10 sec. 

5.3  HOW TO START A MANUAL DEFROST 

Push the DEF key for more than 2 sec and a manual defrost will start. 

5.4  HOW TO CHANGE A PARAMETER VALUE 

To change the parameter’s, value operate as follows:  
1.

 

Enter the Programming mode by pressing the SET+DOWN keys for 3 sec (“°C” or “°F” LED starts 

blinking). 

2.

 

Select the required parameter. Press the SET key to display its value 

3.

 

Use UP or DOWN to change its value. 

4.

 

Press SET to store the new value and move to the following parameter. 

 
To exit
: press SET+UP buttons or wait for 15 sec without pressing any key. 
NOTE: the set value is stored even when the procedure is exited by waiting the time-out to expire. 

5.5  TO LOCK THE KEYBOARD 

1.

 

Keep pressed for more than 3 sec the UP and DOWN keys. 

2.

 

The “OF” message will be displayed and the keyboard will be locked. If a key is pressed more 
than 3 sec the “OF” message will be displayed. 

5.6  TO UNLOCK THE KEYBOARD 

Keep  pressed  together  for  more  than  3  sec  the  UP  and  DOWN  keys  till  the  “on  message  will  be 
displayed. 

PARAMETERS 

REGULATION 

Hy 

Differential: (0.1  to  25°C;  1 to 45°F) differential for set point. Compressor Cut IN is SET POINT + 
differential (Hy). Compressor Cut OUT is when the temperature reaches the set point. 

LS 

Minimum SET POINT: (-55°C to SET; -67°F to SET) sets the minimum value for the set point. 

US 

Maximum SET POINT: (SET to 99°C; SET to 99°F) set the maximum value for set point. 

ot 

First probe calibration: (-9.9 to 9.9°C; -17 to 17°F) allows to adjust possible offset of the first probe. 

P2 

Evaporator probe presence: n= not present; y= the defrost stops by temperature. 

oE 

Second probe calibration: (-9.9 to 9.9°C; -17 to 17°F) allows to adjust possible offset of the second 
probe. 

F5 

Filter probe enabling: (nu; AL; do) set the field of action of the internal measurement filter. nu=not 
used; AL=the filter will always works on all probes; do=the filter will only works on all  probes for 30 
sec after opening of the door. 

od 

Outputs activation delay at start up: (0 to 99min) this function is enabled at the initial start up of the 
instrument and inhibits any output activation for the period of time set in the parameter. 

AC 

Anti-short  cycle  delay:  (0  to  50  min)  minimum  interval  between  the  compressor  stop  and  the 
following restart. 

Cy 

Compressor ON time with faulty probe: (0 to 99min) time during which the compressor is active in 
case of faulty thermostat probe. With Cy=0 compressor is always OFF. 

Cn 

Compressor OFF time with faulty probe: (0 to 99min) time during which the compressor is OFF in 
case of faulty thermostat probe. With Cn=0 compressor is always active. 

DISPLAY 

CF 

Measurement  unit:  (°C;  °F)  °C  =Celsius;  °F  =Fahrenheit.  WARNING:  When  the 
measurement unit is changed the SET point and the values of the parameters Hy, LS, US, oE, 
o1, AU, AL have to be checked and modified if necessary. 

rE 

Resolution (only for °C): (dE; in) dE= decimal between -9.9 and 9.9°C; in= integer. 

Ld 

Default display: (P1; P2) P1= thermostat probe; P2= evaporator probe. 

dy 

Display delay: (0 to 15min) when the temperature increases, the display is updated of 1°C or 
1°F after this time. 

DEFROST 

dE 

Defrost termination temperature: (-55 to 50°C; -67 to 99°F) if P2=Y it sets the temperature 
measured by the evaporator probe, which causes the end of defrost. 

id 

Interval  between  defrost  cycles:  (0  to  99min)  Determines  the  time  intervals  between  two 
consecutives cycles of defrost. 

Md 

Maximum length for defrost: (0 to 99min, 0 means no defrost) when P2=n, (not evaporator 
probe:  timed  defrost)  it  sets  the  defrost  duration,  when  P2  =  y  (defrost  end  based  on 
temperature) it sets the maximum length for defrost. 

dF 

Display  during  defrost:  (rt;  it;  SP;  dF)  rt=  real  temperature;  it=  start  defrost  temperature; 
SP= SET-POINT; dF= label dF. 

ALARMS

 

AU 

Maximum temperature alarm: (AL to 99°C; AL to  99°F) when this temperature is reached  
the alarm is enabled, after the “Ad” delay time. 

AL 

Minimum temperature alarm: (-55°C to AU; -67°F to AU) when this temperature is reached  
the alarm is enabled, after the Ad delay time. 

Ad 

Temperature  alarm  delay:  (0  to  99min)  time  interval  between  the  detection  of  an  alarm 
condition and alarm signalling. 