Emerson Dixell XM660K Скачать руководство пользователя страница 3

 

 

1592023220 XM660K_XM670K GB r5.4 2021.09.01 

XM660K - XM670K  

          3/9 

 

Use  

 

 

 or 

 

 

arrows to 

select an 

entry, 

then press 

  

 

to see the 

value or to 

go on with 

other value. 

MAP 

Current map (0÷3): it shows which map is used 

HM

  Access to clock menu or reset of the RTC alarm; 

An

 

Value of analog output; 

dP1

   (Pb1) Value read by probe 1. 

dP2

   (Pb2) Value read by probe 2. 

dP3

   (Pb3) Value read by probe 3. 

dp4

   (Pb4) Value read by probe 4. 

rCP  

 Value of P4 remote probe for heaters. It is displayed only with P4C = LAn. If the 

value is not available “noP” label is displayed.

 

dPr  R

egulation probe value 

rSE 

Real thermoregulation set point: the value includes the sum of SET, HES and/or 

the dynamic set point if the functions are enabled. 

L°t

  Minimum room temperature; 

H°t

  Maximum room temperature; 

tMd 

Time to next defrost (mins) 

LSn 

Number of devices in the LAN 

LAn 

Address list of devices in the LAN 

GAL 

To see all the active alarms in each device connected to the LAN 

 

Exit 

 

Pressed together or wait the timeout of about 60 sec 

9.

 

MENU FOR MULTIMASTER FUNCTION: SEC 

The function “section” 

SEC

 is enabled when icon 

 is lit. It allows entering in the remote programming 

mode, from a keyboard not physically connected to the board, through the LAN functionality. 

 

 

 

Action 

Button or display 

Notes 

Enter menu 

 

Press UP arrow for about 3 sec, the 

 icon will be 

ON. 

Waiting for action 

SEC 

The menu to change the section will be entered. 

SEC 

label will be displayed. 

Enter section list 

 

Press 

SET 

to confirm. The following list will be 

available to select the proper network function. 

Select proper 

function 

 

 

Or 

 

 

 

LOC 

GLb 

 

To gain access only to the local device. 

To share global commands to all the devices 

connected to the LAN. 

 

Confirm 

 

Select and confirm an entry by pressing 

SET

 button. 

Exit menu 

 

Press 

SET

 and 

UP

 together or wait about 10 seconds. 

(*) The devices on the LAN are indexed by using the 

Adr

 parameter (in ascending order).  

 

EXAMPLES: 

1.

 

To send a command to in all the devices connected to the LAN: enter multimaster menu. Select 

and  confirm 

GLb

.  Exit  from  multimaster  menu.  Enter  the  programming  menu  and  set  the 

parameter of global commands (from LMd to ACE).  

The new setting will be shared among the controllers connected to the LAN. 

 

 

AT THE END OF THE PROGRAMMING PROCEDURE, SELECT THE SECTION “LOC”. IN 

THIS WAY THE ICON 

 

WILL BE SWITCHED OFF!! 

9.1

 

SYNCHRONIZED DEFROST 

The synchronized defrost allow to manage multiple defrost from different boards connected through the 

LAN connection. In this way, the boards can perform simultaneous defrosts with the possibility to end 

them in a synchronized way. 

 The 

Adr

 parameter cannot be duplicated because in this case the defrost cannot be correctly 

managed. 

 

BEGIN 

 

Press for 3 seconds, the 

rtC

 or other will be showed. The 

measurement unit blinks. 

Find Adr 

 

Press more than once the DOWN arrow to find the 

Adr 

parameter, the press 

SET

Modify Adr 

 or 

 

Set the value of 

Adr

 parameter, then press 

SET

 to confirm the 

parameter. 

EXIT 

 

Press the two keys together to exit from menu or wait for about 

10 seconds. 

 

The 

LSn

 and 

LAn

 parameter are only to show the actual settings (read only). See the following example 

of configuration

 

DAILY DEFROST FROM RTC: : [CbP= y] & [EdF = rtC]

 

 

IdF

 

Parameter

: for safety reason force the value of 

Idf

 at +1 respect to the interval between two 

Ld

 

parameters. The 

IdF

 timer is reinitialized after defrost and at every power-on. 

DEFROST START:

 at the time selected by the parameters 

Ld1 

to 

Ld6

 or 

Sd1 

to 

Sd6

DEFROST END: 

if the probes reach the 

dtE

 temperature

 

or for maximum 

MdF

 time. 

SAFETY and RtC or RtF ALARM: 

with clock alarm

 

the device will use the parameter 

IdF, dtE

 and 

MdF

 

WARNING: don’t set [EdF = rtC] and [

CbP= n]. 

 

MULTIMASTER DEFROST

: all the probes with clock 

Table for example 

Par. 

Unit A (RTC)

 

Unit B (RTC)

 

Unit C (RTC) 

Adr 

N + 1 

N + 2 

EdF 

rtC (clock) 

rtC (clock) 

rtC (clock) 

IdF 

9 hours safety 

9 hours safety 

9 hours safety 

MdF 

45 min safety 

45 min safety 

45 min safety 

dtE 

12°C safety 

12°C safety 

12°C safety 

Ld1 

06:00    1°  

06:00    1°  

06:00    1°  

Ld2 

14:00    2°  

14:00    2°  

14:00    2°  

Ld3 

22:00   3°  

22:00   3°  

22:00   3°  

 

10.

 

COMMISSIONING 

10.1

 

CLOCK SETTING AND RTC ALARM RESET 

If the clock is present: [

EdF = rtC

] enable the defrost from rtc [

Ld1 

to 

Ld6

]. 

 

BEGIN 

 

UP arrow (press once) to access the fast access menu 

Display 

HM

 identify the clock RTC submenu; press 

 

Display 

HUr 

= hour 

 press 

 to confirm/modify 

Min 

= minutes 

 press 

 to confirm/modify 

……  

don’t use

 other parameters if present. 

EXIT 

  Press for about 10 sec. The operation resets the RTC alarm. 

 

Note:

 the 

rtC

 clock menu is present also on the second level of parameters. 

Warning

: if the board 

shows the 

rtF

 alarm, the device has to be changed. 

 

11.

 

DISPLAY MESSAGES 

Display 

Causes 

Notes 

 

KEYBOARD 

 

nod 

No display: the keyboard is trying to work 

with another board that is not working or 

not present 

Press for 3 sec UP arrow, enter the 

SEC

 menu and select 

LOC

 entry. 

Pon 

Keyboard is unlocked 

 

PoF 

Keyboard is locked 

 

rSt 

Alarm reset 

Alarm output deactivated 

noP, nP 

nA 

Not present (configuration) 

Not available (evaluation) 

 

noL 

The keyboard is not able to communicate 

with the XM660K-XM670K 

Verify the connection. Call the Service 

 

ALARM FROM PROBE INPUT 

 

P1 

P2 

P3 

P4 

CPF 

Sensor brake down, value out of range or 

sensor incorrectly configured 

P1C

P2C 

to 

P6C

 

CPF

 is showed when the remote probe 4 

is not working. 

P1

: the cooling output works with 

Con

 

and 

COF

With defrost probe on error the defrost 

is performed only at interval. 

 

 

 

TEMPERATURE ALARM 

 

HA 

Temperature alarm from parameter ALU 

on probe 

rAL

Outputs unchanged. 

LA 

Temperature alarm from parameter ALL on 

probe 

rAL

Outputs unchanged. 

HA2 

Second high temperature alarm 

Outputs depends on setting. 

LA2 

Second low temperature alarm 

Outputs depends on setting. 

 

DIGITAL INPUT ALARM 

 

dA 

Door open alarm from input 

i1F

i2F

 or 

i3F

 

= after delay 

d1d

d2d

 or 

d3d

Cooling relay and fan follow the 

odc

 

parameter. Cooling restart as 

specified on 

rrd

 parameter. 

EA 

Generic alarm from digital input 

i1F

i2F

i3F

 = 

EAL

 

CA 

Severe alarm of regulation lock from digital 

input 

i1F

i2F

i3F

 = 

bAL

Regulation output OFF. 

PAL 

Pressure switch lock 

i1F

i2F

 o 

i3F

 = 

PAL

.  All the outputs are OFF. 

 

CLOCK ALARM 

 

rtC 

Clock settings lost. 

Defrost will be performed with 

IdF

 till 

restoring the settings of RTC. 

rtF 

Clock damaged. 

Defrost will be performed with 

IdF

Содержание Dixell XM660K

Страница 1: ...TKEY connector can be used to connect X REP display Depending on the model 4 INSTALLATION AND MOUNTING This device can operate without any user interface but normal application is with Dixell CX660 or CH660 keyboard CX660 CH660 Fig A The CX660 or CH660 keyboard shall be mounted on vertical panel in a 29x71 mm hole and fixed using the special bracket supplied as shown in Fig A The temperature range...

Страница 2: ... SET POINT FOR AIR TEMPERATURE REGULATION The thermostat set point is the value that will be used to regulate the air temperature The regulation output is controlled by the electronic valve or by the relay BEGIN Press SET button for 3 sec the measurement units will blink together Value modification or With the arrows it s possible to change the value within the LS and US parameters value EXIT By p...

Страница 3: ... The LSn and LAn parameter are only to show the actual settings read only See the following example of configuration DAILY DEFROST FROM RTC CbP y EdF rtC IdF Parameter for safety reason force the value of Idf at 1 respect to the interval between two Ld parameters The IdF timer is reinitialized after defrost and at every power on DEFROST START at the time selected by the parameters Ld1 to Ld6 or Sd...

Страница 4: ...work making all the other controllers start their own cycle This allows a perfect synchronisation of the defrost in the whole multiplexed cabinet according to LMd parameter Selecting dPA and dPb probes and by changing the dtP and ddP parameters the defrost can be started when the difference between dPA and dPb probes is lower than dtP for all ddP time This is useful to start defrost when a low the...

Страница 5: ...om temperature If rPb nP the regulation is performed with real value of rPA rP3 Regulation probe 3 nP P1 P2 P3 P4 P6 third probe used to regulate room temperature with rPd rAb Aur LoE HiE rP4 Regulation probe 4 nP P1 P2 P3 P4 P6 fourth probe used to regulate room temperature with rPd rAb Aur LoE HiE rPd Temperature Regulation Strategy rPA rAb Aur LoE HiE rPA temperature detected by the probe set i...

Страница 6: ...saving nt second map enabling cLn clean function dEn defrost off CP1 compressor 1 safety CP2 compressor 2 safety d1d Time interval delay for digital input alarm 0 255 min Time interval to calculate the number of the pressure switch activation when i1F PAL If I1F EAL or bAL external alarms d1d parameter defines the time delay between the detection and the successive signalling of the alarm If i1F d...

Страница 7: ...N LIG This function allows to turn ON and OFF the light relay by using the digital input as external switch 14 8 REMOTE ON OFF ONF This function allows to switch ON and OFF the instrument 14 9 FHU NOT USED This function allows to change the kind of regulation from cooling to heating and viceversa 14 10 ENERGY SAVING INPUT ES The Energy Saving function allows to change the set point value as the re...

Страница 8: ...AL tEr Pr2 Probe for temperature alarm ALC Ab Pr1 Temperature alarm configuration relative absolute Label M1 M2 M3 M4 Menù Parameter description ALU 10 10 10 10 Pr1 High temperature alarm setting ALL 30 30 30 30 Pr1 Low temperature alarm setting AHy 1 0 Pr2 Differential for temperature alarm ALd 15 15 15 15 Pr1 Temperature alarm delay rA2 nP Pr2 Probe for temperature alarm 2 A2U 150 150 150 150 Pr...

Страница 9: ...tion LCL y Pr2 Light on during cleaning mode FCL y Pr2 Fan on during cleaning mode MAP 1 M Pr2 Map selection MP1 1 M Pr2 Map selection loaded by digital input Adr 1 Pr1 Modbus address br 96 Pr2 Baud Rate selection for ModBus 9600 or 19200 EMU nu Pr2 Emulation previous version 2V8 3V8 4V2 rEL 5 4 Pr2 Release code firmware only read SrL Pr2 Sub release firmware only read Ptb Pr2 Map EEPROM ID Pr2 32...

Отзывы: