8.4

 

TO START A EXTRACTION CYCLE MANUALLY 

 

Hold pushed the UP key for more than 2 sec.  

To stop manually the cycle: 

when the cycle is running, hold pushed the UP key for more 

than 2 sec. 

8.5

 

TO ENTER IN PARAMETERS LIST “PR1” 

To enter the parameter list “Pr1” (user accessible parameters) operate as follows: 
 

 

+

 

 
1.

 

Enter  the  Programming  mode  by  pressing  the

  SET_RH

for  few 

seconds. (LED2&3 start flashing) 

2.

 

The instrument will show the first parameter present in “Pr1” 

 
 
 
 

8.6

 

TO ENTER IN PARAMETERS LIST “PR2” 

To access parameters in “

Pr2

”: 

1.

 

Enter the “Pr1” level. 

2.

 

Select “Pr2” parameter and press the “

 SET_RH

 ” key.  

3.

 

The “PAS” flashing message is displayed, shortly followed by “0 - -” with a flashing zero. 

4.

 

Use 

o

  or 

n

  to  input  the  security  code  in  the  flashing  digit;  confirm  the  figure  by  pressing  “

 

SET_RH

 ”.  

The security code is “321“. 

5.

 

If the security code is correct the access to “Pr2” is enabled by pressing “

 SET_RH

 ” on the last 

digit. 

Another possibility

 is the following: after switching ON the instrument the user can push 

SET_RH

 + 

n

 keys within 30 seconds. 

 

NOTE

: each parameter in “Pr2” can be removed or put into “Pr1” (user level) by pressing 

SET_RH

 + 

n

. When a parameter is present in “Pr1” LED 4 is on. 

8.7

 

TO CHANGE PARAMETER VALUES 

1.

 

Enter the Programming mode. 

2.

 

Select the required parameter with 

o

 or 

n

3.

 

Press the “

 SET_RH

 ” key to display its value (LED2&3 start blinking). 

4.

 

Use 

o

 or 

n

 to change its value. 

5.

 

Press “

 SET_RH

 ” to store the new value and move to the following parameter. 

To exit

: Press 

SET_RH

 

+ UP 

or wait 15s without pressing a key. 

NOTE

: the new programming is stored even when the procedure is exited by waiting the time-out. 

8.8

 

HOW TO LOCK THE KEYBOARD 

 

 

1.  

Keep the 

o

 and 

n

 keys pressed together for more than 3 s the 

o

 and 

n

 keys. 

2.  

The “

POF

” message will be displayed and the keyboard is locked. At this point it is 

only possible the viewing of the set point or the MAX o Min temperature stored and 
to switch ON and OFF the light, the auxiliary output and the instrument. 

 

TO UNLOCK THE KEYBOARD 

Keep the 

o

 and 

n

 keys pressed together for more than 3s. 

 

8.9

 

ON/OFF FUNCTION 

 

By  pushing the 

ON/OFF

 key, the instrument  shows “OFF” for 5 sec. and the  ON/OFF 

LED is switched ON. 
During the OFF status, all the relays are switched OFF and the regulations are stopped;  

N.B. During the OFF status the LED4  button is lighted. 

 

9.

 

PARAMETER LIST 

REGULATION 

dbt

  half  dead  band  width  for  temperature:

  (0,1÷25,5°C;  1÷45°F)  this  band  is  place  below  and 

above  the  temperature  set  point  (SET_T).  The  compressor  is  enabled  when  the  temperature 
increases and reaches the SET_T + dbt value. It is turned off when it comes back to the SET_T. 
The  heating  output  is  enabled  when  temperature  is  less  than  SET_T  -dbt  value  and  disabled 
when the SET_T is reached.

 

dbH

 half  dead  band  width  for  humidity:

  (0,5÷25,5RH)  this  band  is  place  below  and  above  the 

humidity set point (SET_RH). The dehumidifying action is enabled when the humidity increases 
and reaches the  dbH value. It is stopped when it comes back to the SET_RH. The 
humidifying  output is enabled when humidity is less than SET_RH -dbH value and disabled when 
the SET_RH is reached.

 

LS  Minimum  temperature  set  point  limit: 

(-50,0°C

SET;  -58°F÷SET)  Sets  the  minimum 

acceptable value for the set point. 

US  Maximum temperature set point limit: 

(SET

110°C; SET÷230°F) Set the maximum acceptable 

value for set point. 

OdS Outputs activation delay at start up:

 (0÷255 min) This function is enabled at the initial start up 

of  the  instrument  and  inhibits  any  output  activation for the period of  time set in the parameter. 
(Light can work) 

AC  Anti-short  cycle  delay: 

(0÷30  min)  interval  between  the  compressor  stop  and  the  following 

restart. 

tHu  Kind of de-humidifying: db

: only with de-humidifier relay (oA1= dEH) 

cHu

 with de-humidifier and compressor relay (oA1= dEH) 

c-H: 

without de-humidifier relay, by means of compressor and heating relays

 

(oA1

 dEH)

LSH  Minimum humidity set point limit: 

(

Lci ÷ Set H

) Sets the minimum acceptable value for the 

humidity set point. 

uSH  Maximum  humidity  set  point  limit: 

(

Set  H  ÷  uci

)  Set  the  maximum  acceptable  value  for 

humidity set point. 

DISPLAY AND KIND OF REGULATION 
CF  Measurement unit: °C

= Celsius; 

°F

= Fahrenheit 

rES  Resolution (for °C)

: allows decimal point display. 

dE

 = 0,1°C; 

in

 = 1 °C  

rEH  Resolution for RH%:

 in = integer; Hd= half digit. 

trC  Kind of behaviour after the end of the cycle 
 

trC=co 

the controller goes on working, and maintains the temperature and humidity of the running 

phase, till the controller is stopped. 

 

trC=in 

at  the  end  of  the  stopping  phase  the  controller  gives  the  “End” message,  the buzzer is 

turned on, and the regulation is stopped. 

 

trC=cL 

at  the end of the stopping phase the controller gives the “End” message, the buzzer is 

turned on, and the regulation restarts from the running phase 

 

trC=cLE 

at the end of the stopping phase the regulation restarts from the running phase.

 

DEFROST 
tdF   Defrost type: rE

 = electrical heater (Compressor OFF) 

in

 = hot gas (Compressor and defrost relays ON) 

EdF  Defrost mode:

  

in

 = 

interval mode

. The defrost starts when the time “

Idf

” is expired. 

Sd

  = 

Smartfrost  mode

.  The  time  IdF  (interval  between  defrosts)  is  increased  only  when  the 

compressor is running (even non consecutively).  

SdF  Set point for SMARTFROST

: (-30

30 °C/ -22

86 °F) evaporator temperature which allows the 

IdF counting (interval between defrosts) in SMARTFROST mode. 

dtE   Defrost  termination  temperature:

  (-50,0÷110,0°C;  -58÷230°F)  (Enabled  only  when  the 

evaporator  probe  is  present)  sets  the  temperature  measured  by  the  evaporator  probe  which 
causes the end of defrost. 

IdF  Interval between defrosts: 

(1÷120h) Determines the time interval between the beginning of two 

defrost cycles. 

MdF  Duration  of  defrost: 

(0÷255  min)  When 

P2P  =  n

,  no  evaporator  probe,  it  sets  the  defrost 

duration,  when 

P2P  =  y

,  defrost  end  based  on  temperature,  it  sets  the  maximum  length  for 

defrost. 

dFd  Display during defrost:  
 

rt

 = real temperature; 

it

 = temperature reading at the defrost start; 

Set

 = set point; 

dEF

 = “dEF” label; 

 

dEG

 = “dEG” label;

 

dAd  Defrost display time out:

 (0

255 min) Sets the maximum time between the end of defrost and 

the restarting of the real room temperature display. 

Fdt   Drain  down  time:

  (0÷60  min.)  time  interval  between  reaching  defrost  termination  temperature 

and the restoring of the control’s normal operation. This time allows the evaporator to eliminate 
water drops that might have formed due to defrost.

 

dPO First defrost after start-up:  y 

= Immediately; 

n

 = after the IdF time 

Hud  Humidity control during defrost:

 

no

: the humidity control is stopped during the defrost; 

yES

 the 

humidity control works also during the defrost. 

FANS 
FnC  Fan operating mode: C-n

 = running when a load is on, OFF during the defrost;  

C-y

 = running when a load is on, ON during the defrost; 

O-n

 = continuous mode, OFF during the defrost; 

O-y

 = continuous mode, ON during the defrost; 

EXTRACTOR FANS 
rFi  Interval between 2 cycles of change of air 

(0÷120 ore; 0 = only manual starting) 

rFd  Duration of change of air cycle 

(0÷250min; 0 =  only manual stopping) 

 

TEMPERATURE ALARMS 
ALC Temperature alarm configuration: rE

 = High and Low alarms related to Set Point  

Ab

 = High and low alarms related to the absolute temperature. 

ALL  Low temperature alarm setting:

 

ALC = rE 

, 0 

 50 °C or 90°F 

 

ALC = Ab 

, - 50°C or -58°F 

 ALU 

 

when this temperature is reached and after the ALd delay time, the LA alarm is enabled,. 

ALU High temperature alarm setting:

  

ALC= rE

, 0 

 

50°C or 90°F 

 

ALC= Ab

, ALL 

 110°C or 230°F 

 

when this temperature is reached and after the ALd delay time the HA alarm is enabled. 

 

ALH Temperature  alarm  recovery  differential: 

(0,1÷25,5°C;  1÷45°F)  Intervention  differential  for 

recovery of temperature alarm.

 

ALd  Temperature alarm delay:

 (0÷255 min) time interval between the detection of an alarm condition 

and the corresponding alarm signalling. 

dAO Delay of temperature alarm at start-up:

 (0min÷23h 50min) time interval between the detection 

of the temperature alarm condition after the instrument power on and the alarm signalling.

 

EdA  Alarm  delay  at  the  end  of  defrost: 

(0

255  min)  Time  interval  between  the  detection  of  the 

temperature alarm condition at the end of defrost and the alarm signalling. 

dot   Delay  of  temperature  alarm  after  closing  the  door  : 

(0

255  min)  Time  delay  to  signal  the 

temperature alarm condition after closing the door. 

HUMIDITY ALARMS 
AHC Humidity alarm configuration: rE

 = High and Low alarms related to humidity Set Point  

Ab

 = High and low alarms related to the “absolute” humidity. 

AHL Low humidity alarm setting: 

(with AHC = rE: 

0 ÷ 50

. With AHC = Ab: 

Lci ÷ AHu)

 

 

when this humidity is reached and after the AHd delay time, the HLA alarm is enabled,. 

AHu High humidity alarm setting:

 (with AHC = rE: 0÷50°C. with AHC = Ab: 

AHL ÷ uci

 

 

when this humidity is reached and after the AHd delay time the HHA alarm is enabled. 

AHH Humidity  alarm  recovery  differential: 

(0.5÷20.0)  Intervention  differential  for  recovery  of 

humidity alarm.

 

AHd Humidity alarm delay:

 (0÷255 min) time interval between the detection of an alarm condition and 

the corresponding alarm signalling. 

dHo Delay of humidity alarm at start-up:

 (0min÷23h 50min) time interval between the detection of 

the humidity alarm condition after the instrument power on and the alarm signalling.

 

doH  Alarm  delay  at  the  end  of  defrost: 

(0

255  min)  Time  interval  between  the  detection  of  the 

humidity alarm condition at the end of defrost and the alarm signalling. 

doA  Open door alarm delay:

(0÷255 min) delay between the detection of the open door condition and 

its alarm signalling: the flashing message “

dA

” is displayed. 

tbA  Alarm relay status after pushing a key: on= 

the relay remains on

; off= 

the relay is switched off. 

nPS  Pressure switch number:

 (0 

15) Number of activation of the pressure switch, during the “

did

” 

interval, before signalling the alarm event (I1F= PAL). 

If  the  nPS  activation  in  the  “did”  time  is  reached,  switch  off  and  on  the  instrument  to 

restart normal regulation. 

 

PROBE INPUTS 
Ot  Thermostat probe calibration: 

(-12.0

12.0°C/ -21

21°F) allows to adjust possible offset of the 

thermostat probe. 

OE    Evaporator probe calibration: 

(-12.0

12.0°C/ -21

21°F) allows to adjust possible offsets of the 

evaporator probe. 

O3    Humidity probe calibration: 

(-10

10 RH) allows to adjust possible offsets of the humidity probe. 

P2P  Evaporator  probe  presence:  n

=  not  present:  the  defrost  stops  only  by  time; 

y=

  present:  the 

defrost stops by temperature and time. 

P3P  Humidity probe presence: n

= not present; 

y=

 present. 

LCI   Readout with 4 mA

 : (-999 ÷ 999). Adjustment of  read out corresponding to 4mA signal. 

UCI   Readout with 20 mA

 : (-999 ÷ 999). Adjustment of  read out corresponding to 20mA signal. 

 
  

 

Содержание Dixell XH360L-V

Страница 1: ...INALS 3 4 XH360V TERMINALS 11 12 In this case the dehumidifying action is performed by setting the following parameters in this way tHu c H kind of dehumidifying by means of heating and compressor relays oA1 different from dEH XH360L terminals 3 4 XH360V terminals 11 12 The heating and compressor outputs are activated together when humidity is higher than SET_RH dbH value Outputs are disabled when...

Страница 2: ...the setting of the running cycle temperature SET_T humidity SET_RH or remaining time CLOCK 1 Push twice the corespondent key the setting value of the current phase dripping or running will be displayed 2 Modify it using the UP and DOWN keys 3 Confirm the value using the corespondent key temperature SET_T humidity SET_RH or remaining time CLOCK NOTE the changes made will be memorised So the next cy...

Страница 3: ... the compressor is running even non consecutively SdF Set point for SMARTFROST 30 30 C 22 86 F evaporator temperature which allows the IdF counting interval between defrosts in SMARTFROST mode dtE Defrost termination temperature 50 0 110 0 C 58 230 F Enabled only when the evaporator probe is present sets the temperature measured by the evaporator probe which causes the end of defrost IdF Interval ...

Страница 4: ...n a 150x31 mm hole and fixed using two screws 3 x 2mm To obtain an IP65 protection grade use the front panel rubber gasket mod RG L Instrument XH360V shall be mounted on vertical panel in a 72x56 mm hole and fixed using screws 3 x 2mm To obtain an IP65 protection grade use the front panel rubber gasket mod RG V The temperature range allowed for correct operation is 0 60 C Avoid places subject to s...

Страница 5: ...t holding in stop regulation cL restart the first phase End message cLE restart the first phase tdF rE Pr2 Defrost type rE rT in EdF in Pr2 Defrost mode In Sd SdF 0 0 Pr2 Set point for SMART DEFROST 30 30 C 22 86 F dtE 8 0 Pr2 Defrost termination temperature 50 0 110 C 58 230 F Label Value Menu Description Range idF 6 Pr1 Interval between defrosts 1 120 h MdF 20 Pr1 Duration of defrost 0 250 min d...

Отзывы: