1592012000 XF330M XF331M XF332M GB REL1.0 31.08.2015
XF330M XF331M XF332M
7/12
2.
With
single cycle
(
ccy=sin
) the time display shows
the duration of the steam injection. Use the UP and
DOWN keys to set the value (0÷60s).
3.
With
repetitive cycle
(
ccy=riP
) the TIME display
shows 4 for digits. The 2 digits on the right indicate
the injection time, the 2 digits on the left indicate the
time during which the output is off.
Use the UP and DOWN keys to set the value. The
OFF time is
automatically
calculated according to
the following formula: 60 – ON TIME.
ES.
The
4020 number
means that the instrument
do a injection cycle of 20s and then stays off for
40s.
4.
To exit:
push again the key
or wait the
timeout to expire.
NOTE1:
The steam injection can be stopped pushing
again the INJECTION key
.
NOTE2:
Setting the HSi parameter to 0, the steam is
injected continuously as long as key is pushed.
NOTE3:
If ccY= riP (repetitive cycle) and the inhibition
time (TcY) added to the injections time (tco) is grater than
60s, the instrument does cycles with the following period
T= tcY + tco, instead of 60s cycles.
It means that he steam is injected for tco seconds and is
disabled for tcY seconds.
9.
The steam extractor (Not present in
XF331M)
The steam extractor can be activated by keyboard or
automatically before the end of a cooking cycle.
9.1
How to activate the extractor by means of
the keyboard
By pushing the
EXTRACTOR
key
the relay of the
extractor is switched. The status of the extractor is
monitored by the led: if the led is ON the extractor is
working, if the LED is off the extractor is off.
9.2
Automatic activation of the steam extractor
before the end of a cooking cycle
The extractor can be activated automatically
some
minutes before
the end of a cooking cycle.
To set the time, act as follow:
1.
Push the
EXTRACTOR
key
till the time
display will show the activation time in the following
format: h:mm.
2.
Use the UP and DOWN keys to set the value.
(0÷1h30m).
5.
To exit:
push again
EXTRACTOR
key
or
wait the timeout to expire.
NOTE
: By setting the time to 0, only the manual activation
is enabled.
10.
The fan relay (Only for XF332M)
The XF332M is provide with a relay for the fan (terminals
17-18).
The relay is activated when the controller is switched on.
During the steam injection the relay is switched off.
After the steam injection it stays off according to the
setting of the
tFS
parameters (0÷90m)
11.
The Energy Saving function
The Energy Saving function is enabled by pushing the
key. It avoids Ceiling and Bottom outputs from
working together. The 2 outputs are switched on
alternatively.
The
tcE
and
dcy
parameters control this function:
1.
The
tcE
par. (1÷999s) set the Energy Saving
cycle
time.
2.
The
dcy
(0÷100) set the
switching on percentage
of the Ceiling output during the Energy Saving
cycle.
ES.
With Energy Saving function enabled, tcE=100s and
dcy=60, when there is a contemporary request of
switching on of the ceiling and bottom outputs, the 2
outputs work as explained in the following graph:
Cielo
Tempo
Tempo
Platea
If only a output is requested to be switched on, it is
switched on for all the time is necessary.