XEV20D 

          2/5 

 

 

3.

 

GENERAL RULES 

Comply with the following recommendations during the installation process in order to 
prevent the device from malfunctioning. 

 

Separate the signal cables from the power cables (it is recommended to use 
BELDEN 8772-type shielded cables). 

 

Separate the cables of the analogue inputs from those of the digital inputs and 
the serial line cables from the power cables (resistive as well as inductive), in 
order to prevent malfunction due to electromagnetic interference. 

 

Separate the power of the device from that of the other electrical components. 

 

Never connect the secondary of the supply transformer to the earth. 

 

The low voltage connections must have reinforced insulation. 

 

4.

 

INSTALLATION AND MAINTENANCE 

XEV20D  is  a  slave  device,  which  means  that  it  receives  commands  from  another 
“master”  device;  in  particular,  instructions  are  given  by  an  iPro  controller  through  a 
CANBUS (10DIN version) or LAN (4DIN version) connection. 
Operating  parameters  are  sent  by  an  iPro  and  then  they  are  stored  in  a  special 
retentive memory area inside the driver. 
The necessary parameters for operation are: 
This memory stores the values of the following parameters:  

1) 

valve type

 (0= disabled valves; 1= both unipolar valves / 2= both bipolar 

valves and Wavemode type of command; 18 = both bipolar valves and 
Normal mode type of command) 

2) 

valve 1 step rate

 (expressed in tens of ms 16-10000) 

3) 

valve 2 step rate

 (expressed in tens of ms 16-10000) 

4) 

valve 1

 

maximum number of steps

 (0-8500) 

5) 

valve 2 maximum number of steps

 (0-8500) 

6) 

valve 1 movement current

 (0-100 *10mA) 

7) 

valve 2 movement current

 (0-100 *10mA) 

8) 

valve 1 maintenance current

 (1-100 *10mA) 

9) 

valve 2 maintenance current

 (1-100 *10mA) 

10) 

unipolar valve 1 configuration

 (Current/ no current with valve in position 

– adjustment steps expressed in whole steps/half steps) 

11) 

unipolar valve 2 configuration

 (Current/ no current with valve in position 

– adjustment steps expressed in whole steps/half steps) 

 

Whenever the master device (iPro) tells the driver a new value for one 
of the aforementioned parameters, the driver itself proceeds with the 
complete closure of the valve. 

 
The  XEV20D  drivers issued by Dixell  are tested  but not  configured: this  means that 
the parameters in the fla

sh memory are set to a default value (specifically, the “valve 

type” parameter = 0). 
 

4.1  VALVES CONNECTIONS TABLE 

 
Read  carefully the table  below to learn how to connect valves  produced by  different 
OEMs: 
 

4-WIRE VALVES (BIPOLAR) 

 

Terminal number 

ALCO 

EX* 

ALCO 

EX5/6 

SPORLAN 

SEI-SHE 

DANFOSS 

ETS 

WHITE 

BLUE 

WHITE 

BLACK 

YELLOW 

BROWN 

BLACK 

WHITE 

BROWN 

BLACK 

RED 

RED 

GREEN 

WHITE 

GREEN 

GREEN 

– Common 

---- 

----- 

----- 

----- 

  

5-WIRE VALVES (UNIPOLAR) 

 

Terminal number 

SPORLAN 

SAGINOMIYA 

ORANGE 

ORANGE 

RED 

RED 

YELLOW 

YELLOW 

BLACK 

BLACK 

– Common 

GREY 

GREY 

 

 

The maximum distance between a XEV valve driver and the valve 

must not exceed 

10  meters

shielded  cables

  with  a  section  greater  than  or  equal  to  0.325  mm² 

(AWG22) must be used.  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

4.2  DRIVER POWER-ON 

 
At power-on XEV20D reads the parameters in the flash memory. 
At this point: 

 

If  “valve  type”  =  0,  no  action  is  taken  on  the  valve  and  both  “PWR  ON”  and 
“ALARM” leds remain on steady. 

 

 

 

 

If “valve type” ≠ 0, the driver itself commands the complete closure of the valve. 
During this phase the 

“Close” led blinks. 

 

 

 
Once the valve has been closed (the “Close” led remains on steady), the driver waits 
to receive instructions from iPro. 
 

4.3  IPRO+XEV20D TESTING PROCEDURE 

 
During the first connection, the replacement of a valve body or the first test of a unit, it 
is necessary to follow the procedure below: 

 

1. 

Disable any unit adjustment; 

2. 

Cut off power to the whole unit; 

3. 

Disconnect the connector dedicated to valve wiring. 

 

4. 

In case the connection of the valve body involves the modification of its 
operating parameters, proceed as follows: 
a. 

Power the unit, disconnecting the body valve from XEV20D. 

b. 

Set the new parameters of the valve using the iPro application. 

c. 

Remove power from the unit. 

5. 

Connect the body valve to XEV20D driver. 

6. 

Power the unit. 

 

 

Valve wires must not be connected or disconnected, whenever the 
driver is powered. This action may damage the driver and the valve 
windings. 

“PWR ON” and 

“ALARM” leds 

“Open” and 

“Close” leds 

Valve 1 and 2 

terminals 

Содержание Dixell XEV20D

Страница 1: ...nserted inside an electrical panel that can only be accessed by authorized personnel For safety purposes the keyboard must be the only part that can be reached The device must never be hand held while being used It is good practice to bear the following in mind for all Dixell products o Prevent the electronic circuits from getting wet as contact made with water humidity or any other type of liquid...

Страница 2: ...e iPro tells the driver a new value for one of the aforementioned parameters the driver itself proceeds with the complete closure of the valve The XEV20D drivers issued by Dixell are tested but not configured this means that the parameters in the flash memory are set to a default value specifically the valve type parameter 0 4 1 VALVES CONNECTIONS TABLE Read carefully the table below to learn how ...

Страница 3: ...0 mA input resistance 100Ω Precision at 25 C NTC PTC PT1000 1 C 0 5V 100mV 4 20mA 0 30mA Measurement and adjustment field 50 C 110 C 58 F 230 F NTC probe 50 C 150 C 32 F 302 F PTC probe 50 C 100 C 32 F 212 F PT1000 probe 0 bar 50 bar 0 psi 302 psi pressure probe Resolution 0 1 C 1 F 0 1 bar 6 2 DIGITAL INPUTS Digital inputs can be configured via software as digital inputs Type configurable via sof...

Страница 4: ...he diagram of the device used for the numbering the configuration is determined by the application 7 4 3 Pressure transducers and ratiometric pressure transducers 0 5V 3 row sensors that require 5Vdc power supply Recommendations follow the diagram of the device used for the numbering the configuration is determined by the application 8 CONNECTION TO XEC SUPERCAP The XEC device and the XEV20D drive...

Страница 5: ...y the ISaGRAF software refer to the documentation on https www ipro academy website 10 MEANING OF THE LED LIGHTS The following table illustrates LED light operation LED MODE MEANING PWR ON On The instrument is powered correctly ALARM On There is an alarm TX RX Blinking CAN Bus or LAN activity communication enabled TX RX On No link OPEN V1 Blinking Valve 1 in opening mode OPEN V1 On Valve 1 fully o...

Отзывы: