background image

 

 

1592009130 XW570L GB r1.0 03.08.2015                      

     XW570L 

4/5 

 

   

 

 

 

 

 

NOTE

: When the defrost is in progress, the analogue output is set to the minimum value (4 mA). This condition 

lasts until the defrost terminates. 

 

9.

 

INSTALLATION AND MOUNTING 

Instruments 

XW570L

 shall be mounted on vertical panel, in a 150x31 mm hole, and fixed using two screws 

 3 

x 2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-L). The temperature 
range  allowed  for  correct  operation  is  0  -  60  °C.  Avoid  places  subject  to  strong  vibrations,  corrosive  gases, 
excessive  dirt  or  humidity.  The  same  recommendations  apply  to  probes.  Let  the  air  circulate  by  the  cooling 
holes. 

 

9.1

 

CUT OUT 

 

165

150

31

+0.5

-0

+0

.5

-0

+1

-1

Ø3 x2

 

 

9.2

 

MOUNTING WITH KEYBOARD COVER OPENING DOWNWARD 

 

CLICK!

1

2

2

3

3

1

1

 

 

9.3

 

MOUNTING WITH KEYBOARD COVER OPENING UPWARD 

CLICK!

1

2

2

2

3

3

1

1

 

10.

 

ELECTRICAL CONNECTIONS 

The instruments are provided with screw terminal block to connect cables with a cross section up to 2,5 mm

for 

the digital and analogue inputs.  Relays and power supply have a Faston connection (6,3mm). Heat-resistant 
cables have to be used. Before connecting cables make sure the power supply complies with the instrument’s 
requirements.  Separate  the  probe  cables  from  the  power  supply  cables,  from  the  outputs  and  the  power 
connections. Do not exceed the maximum current allowed on each relay, in case of heavier loads use a suitable 
external relay. 

N.B.

 Maximum current allowed for all the loads is 20A. 

10.1

 

PROBE CONNECTIONS 

The probes shall be mounted with the bulb upwards to prevent damages due  to casual liquid infiltration. It is 
recommended  to  place  the  thermostat  probe  away  from  air  streams  to  correctly  measure  the  average  room 
temperature. Place the defrost termination probe among the evaporator fins in the coldest place, where most ice 
is formed, far from heaters or from the warmest place during defrost, to prevent premature defrost termination. 

11.

 

TTL SERIAL LINE 

The TTL connector allows, by means of the external module TTL/RS485, to connect the unit to a network line 

ModBUS-RTU

 compatible as the Dixell monitoring system XJ500 (Version 3.0). 

The  same  TTL  connector  is  used  to  upload  and  download  the  parameter  list  of  the  “

HOT  KEY

“.  These 

instruments can be ordered with direct serial output 

RS485

 (Optional). 

 

12.

 

USE OF THE PROGRAMMING “HOT KEY “ 

The Wing units can UPLOAD or DOWNLOAD the parameter list from its own E2 internal memory to the 

“Hot 

Key” 

and vice-versa. 

12.1

 

DOWNLOAD (FROM THE “HOT KEY” TO THE INSTRUMENT) 

1.

 

Turn OFF the instrument by means of the ON/OFF key, remove the TTL serial cable if present, insert 
the 

“Hot Key” 

and then turn the Wing ON. 

2.

 

Automatically  the  parameter  list  of  the 

“Hot  Key”

  is  downloaded  into  the  Wing  memory,  the  “

DoL

” 

message is blinking. After 10 seconds the instrument will restart working with the new parameters. 

3.

 

Turn OFF the instrument remove the 

“Hot Key”, 

plug in  the TTL serial cable, then turn it ON again. 

At the end of the data transfer phase the instrument displays the following messages: 

end

 “ for right programming. The instrument starts regularly with the new programming. 

err

” for failed programming. In this case turn the unit off and then on if you want to restart the download again 

or remove the “

Hot key

” to abort the operation. 

12.2

 

UPLOAD (FROM THE INSTRUMENT TO THE “HOT KEY”) 

1.

 

Turn OFF the instrument by means of the ON/OFF key and remove the TTL serial cable if present; then 
turn it ON again. 

2.

 

When the Wing unit  is ON, insert the “

Hot key

” and push 

o

 

key; the  

"uPL" 

message appears. 

3.

 

Push “

SET”

 key to start the UPLOAD; the “

uPL

” message is blinking. 

4.

 

Turn OFF the instrument remove the 

“Hot Key”, 

plug in  the TTL serial cable, then turn it ON again. 

At the end of the data transfer phase the instrument displays the following messages: 

end

 “ for right programming. 

err

”  for  failed  programming.  In  this  case  push  “SET”  key  if  you  want  to  restart  the  programming  again  or 

remove the not programmed “

Hot key

”. 

13.

 

ALARM SIGNALS 

Message  Cause 

Outputs 

“P1” 

Thermostat probe failure  Alarm  output  ON;  Compressor  output  according  to  parameters  “COn” 

and “COF” 

“P2” 

Evaporator probe failure  Alarm output ON; Other outputs unchanged 

“P3” 

Auxiliary probe failure 

Alarm output ON;  
Other outputs unchanged 

“HA” 

Max. temperature alarm  Alarm output ON; Other outputs unchanged 

“LA” 

Min. temperature alarm 

Alarm output ON; Other outputs unchanged 

“EE”  

Data or memory failure 

Alarm output ON; Other outputs unchanged 

“dA” 

Door switch alarm 

Alarm output ON; Other outputs unchanged 

“EAL” 

External alarm 

Alarm output ON; Other outputs unchanged 

“BAL” 

Serious external alarm 

Alarm output ON; Other outputs OFF 

“PAL” 

Pressure switch alarm 

Alarm output ON; Other outputs OFF

 

“rtc” 

Real time clock alarm 

Alarm output ON; Other outputs unchanged; Defrosts according to par. 

IdF

” 

 
The alarm message is displayed until the alarm condition is recovery. 
All the alarm messages are showed alternating with the room temperature except for the “P1” which is flashing. 
To reset the “EE” alarm and restart the normal functioning press any key, the “

rSt

” message is displayed for 

about 3s. 

13.1

 

SILENCING BUZZER / ALARM RELAY OUTPUT 

If “

tbA = y

”, once the alarm signal is detected the buzzer and the relay are is silenced by pressing any key.  

If “

tbA 

n

”, only the buzzer is silenced while the alarm relay is on until the alarm condition recovers. 

13.2

 

“EE” ALARM 

The  Dixell  instruments  are  provided  with  an  internal  check  for  the  data  integrity.  Alarm  “EE”  flashes  when  a 
failure in the memory data occurs. In such cases the alarm output is enabled. 

13.3

 

ALARM RECOVERY 

Probe alarms : “

P1

” (probe1 faulty), “

P2

” and “

P3

”; they automatically stop 10s after the probe restarts normal 

operation. Check connections before replacing the probe. 
Temperature alarms “

HA

” and “

LA

” automatically stop as soon as the thermostat temperature returns to normal 

values or when the defrost starts. 
Door switch alarm “

dA

”  stop as soon as the door is closed. 

External alarms “

EAL

”, “

BAL

”  stop as soon as the external digital input is disabled “

PAL

” alarm is recovered by 

switching OFF the instrument. 
 
 
 
 
 
 
 

Содержание Dixell Wing XW570L

Страница 1: ...is control by means of parameter EdF Edf rtc the defrost is made in real time depending on the hours set in the parameters Ld1 Ld8 on workdays and in Sd1 Sd8 in holidays EdF in the defrost is made every IdF time EdF Sd the interval IdF is calculate through Smart Defrost algorithm only when the compressor is ON and the evaporator temperature is bigger than SdF parameter At the end of defrost the dr...

Страница 2: ...tting the current hour minutes day and the weekly holidays up to 3 will be possible 4 To exit press SET UP or wait 15s without pressing any key 5 3 TO SET THE DEFROST TIMES 1 Push the n key for more than 3 seconds 2 eLED switches ON and the current time is displayed 3 By pushing DEF key the DEF led will start flashing and setting defrost time will be possible 4 To exit press SET UP or wait 15s wit...

Страница 3: ...AL If I2F EAL or bAL external alarms did parameter defines the time delay between the detection and the successive signalling of the alarm TO SET CURRENT TIME AND WEEKLY HOLIDAYS 3SEC afterward Hur Current hour 0 23 h Min Current minute 0 59min dAY Current day Sun SAt Hd1 First weekly holiday Sun nu Set the first day of the week which follows the holiday times Hd2 Second weekly holiday Sun nu Set ...

Страница 4: ...l cable then turn it ON again At the end of the data transfer phase the instrument displays the following messages end for right programming The instrument starts regularly with the new programming err for failed programming In this case turn the unit off and then on if you want to restart the download again or remove the Hot key to abort the operation 12 2 UPLOAD FROM THE INSTRUMENT TO THE HOT KE...

Страница 5: ...perature 50 0 110 C 58 230 F 2 35 Pr2 ALARMS ALC Temperature alarms configuration rE Ab rE Pr2 ALU MAXIMUM temperature alarm 50 0 110 C 58 230 F 10 20 Pr1 ALL minimum temperature alarm 50 0 110 C 58 230 F 10 20 Pr1 AFH Temperature alarm and fan differential 0 1 25 5 C 1 45 F 2 4 ALd Temperature alarm delay 0 255 min 15 Pr2 dAO Delay of temperature alarm at start up 0 23h 50 min 1 3 Pr2 EdA Alarm d...

Отзывы: