background image

 

1592009040 XW263L GB R1.0 04.08.2015 

                           XW263L 

1/4 

W

ING

 

XW263L 

1.

 

GENERAL WARNING 

1.1

 

PLEASE READ BEFORE USING THIS MANUAL 

 

This manual is part of the product and should be kept near the instrument for easy and quick reference. 

 

The instrument shall not be used for purposes different from those described hereunder. It cannot be used 
as a safety device. 

 

Check the application limits before proceeding. 

 

Dixell Srl reserves the right to change the composition of its products, even without notice, ensuring the 
same and unchanged functionality. 

1.2

 

 SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden 
temperature changes with high atmospheric humidity to prevent  formation of condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be opened. 

 

In case of  failure or faulty operation send the instrument back to the distributor or to “Dixell s.r.l.” (see 
address) with a detailed description of the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure that the wires for probes, loads and the power supply are separated and far enough from each 
other, without crossing or intertwining. 

 

In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel with 
inductive loads could be useful. 

2.

 

GENERAL DESCRIPTION 

Model 

XW263L

38x185

 mm format, is microprocessor based controller suitable for applications on medium or 

low temperature refrigerating units. It is provided with four relay outputs to control compressor, defrost - which 
can be either electrical or hot gas  - the evaporator fans and the lights. 
It  is  also  provided  with  two  NTC  probe  inputs,  one  for  temperature  control,  one  to  control  the  defrost  end 
temperature of the evaporator. There are two digital inputs (free contact) for the door switch and configurable by 
parameter. 
The  RS485  output  allows  the  user  to  connect  a 

ModBUS-RTU 

compatible  monitoring  system  and  the  TTL 

output allows to programme the parameter list with the 

“Hot Key”.

 

3.

 

CONTROLLING LOADS 

3.1

 

THE COMPRESSOR 

The  regulation  is  performed  according  to  the  temperature  measured  by  the  thermostat  probe  with  a  positive 
differential from the set point: if the temperature increases and reaches set point plus differential the compressor 
is started and then turned off when the temperature reaches the set point value again. 
In  case  of  fault  in  the  thermostat  probe  the  start  and  stop  of  the  compressor  are  timed  through  parameters 

COn

” and “

COF

”. 

3.2

 

FAST FREEZING 

When  defrost  is  not  in  progress,  it  can  be  activated  the  keypad  by  holding  the 

o

  key  pressed  for  about  3 

seconds. The compressor operates in continuous mode for the time set through the “

CCt

” parameter. The cycle 

can be terminated before the end of the set time using the same activation key, 

o

 for about 3 seconds. 

3.3

 

DEFROST 

Three  defrost  modes  are  available  through  the  “

tdF

”  parameter:  defrost  with  electrical  heater,  hot  gas  or 

thermostatic defrost. The defrost interval is control by means of parameter “

EdF

”: (EdF=in) the defrost is made 

every  “

IdF

”  time,  (EdF=Sd)  the  interval  “IdF”  is  calculate  through  Smart  Defrost  algorithm  (only  when  the 

compressor is ON and the evaporator temperature is bigger than “SdF” parameter). 
At the end of defrost the drip time is controlled through the “

Fdt

” parameter. 

 

3.4

 

CONTROL OF EVAPORATOR FANS 

The fan control mode is selected by means of the “

FnC

” parameter: 

FnC=C-n

   fans will switch ON and OFF with the compressor and

 not run

 during defrost

:

FnC=C-y

   fans will run continuously, but not during defrost  

After defrost, there is a timed fan delay allowing for drip time, set by means of the “Fnd” parameter. 

FnC=O-n

   fans will switch ON and OFF with the compressor and 

run

 during defrost; 

FnC=O-y

   fans will run continuously also during defrost 

 

An  additional  parameter  “FSt”  provides  the  setting  of  temperature,  detected  by  the  evaporator  probe,  above 
which the fans are always OFF. This can be used to make sure circulation of air only if his temperature is lower 
than set in “FSt”. 
 

 
 

4.

 

KEYBOARD 

 

 

 

 

To display and modify target set point; in programming mode it selects a parameter or confirm an 
operation.  
By holding it pressed for 3s when max or min temperature is displayed it will be erased. 
 

 

To  see  the  max.  stored  temperature;  in  programming  mode  it  browses  the  parameter  codes  or 
increases the displayed value. By holding it pressed for 3s the fast freezing cycle is started. 

 

To  see  the  min  stored  temperature;  in  programming  mode  it  browses  the  parameter  codes  or 
decreases the displayed value. 
 

 

 
By holding it pressed for 3s the defrost is started. 
 

 

 
Switch ON and OFF the cold room light. 

 

 
Switch ON and OFF the instrument. 

 

KEY COMBINATIONS 

 

 

 

 

To lock and unlock the keyboard.

 

 

 

 

To enter the programming mode. 

 

 

 

 

To exit the programming mode.

 

 

4.1

 

USE OF LEDS 

Each LED function is described in the following table. 

LED 

MODE 

Function 

 

ON 

The compressor is running 

 

FLASHING 

- Programming Phase (flashing with LED 

- Anti-short cycle delay enabled 

 

ON 

The fan is running 

 

FLASHING 

Programming Phase (flashing with LED 

 

ON 

The defrost is enabled 

 

FLASHING 

Drip time in progress 

 

ON 

The Fast Freezing cycle is enabled 

  

ON 

- ALARM signal 
- In “Pr2” indicates that the parameter is also present in “Pr1” 

 
Function of the LEDs placed on the left top side of buttons: 
 

BUTTON 

MODE 

FUNCTION 

SET 

FLASHING 

The Set point is displayed and it can be modified  

SET 

FAST FLASHING  The Energy Saving is enabled  

DEFROST 

ON 

The Manual Defrost is activated 

LIGHT 

ON 

The Light is ON 

ON/OFF 

ON 

The instrument is OFF 

 

4.2

 

HOW TO SEE THE MIN TEMPERATURE 

 

1.  

Press and release the 

n

 key. 

2.  

The “Lo” message will be displayed followed by the minimum temperature recorded. 

3. 

By pressing the 

n

 key or waiting for 5s the normal display will be restored. 

4.3

 

HOW TO SEE THE MAX TEMPERATURE 

 

1.  

Press and release the 

o

 key. 

2.  

The “Hi” message will be displayed followed by the maximum  temperature recorded. 

3. 

By pressing the 

o

 key or waiting for 5s the normal display will be restored. 

4.4

 

HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED 

To reset the stored temperature, when max or min temperature is displayed : 
1.

 

Press SET key until “rST” label starts blinking. 

 

N.B. After the installation RESET the temperature stored .

 

4.5

 

HOW TO SEE AND MODIFY THE SET POINT 

 

 

1. 

Push and immediately release the 

SET 

key: the display will show the Set point value; 

2. 

The SET LED start blinking; 

3. 

To change the Set value push the 

or 

n

 arrows within 10s. 

4. 

To memorise the new set point value push the 

SET

 key again or wait 10s. 

4.6

 

TO START A MANUAL DEFROST  

 

 
1. 

Push the 

DEF 

key for more than 2 seconds and a manual defrost will start. 

4.7

 

TO ENTER IN PARAMETERS LIST “PR1”  

To enter the parameter list “Pr1” (user accessible parameters) operate as follows: 
 

 
1.  Enter  the  Programming  mode  by  pressing  the  Set  and  DOWN  key  for  few 

seconds (

 and 

 start blinking). 

 

Содержание Dixell Wing XW263L

Страница 1: ...ature is bigger than SdF parameter At the end of defrost the drip time is controlled through the Fdt parameter 3 4 CONTROL OF EVAPORATOR FANS The fan control mode is selected by means of the FnC parameter FnC C n fans will switch ON and OFF with the compressor and not run during defrost FnC C y fans will run continuously but not during defrost After defrost there is a timed fan delay allowing for ...

Страница 2: ...s less than the value in SdF set point for SMARTFROST SdF Set point for SMARTFROST 30 30 C 22 86 F evaporator temperature which allows the IdF counting interval between defrosts in SMARTFROST mode dtE Defrost termination temperature 50 0 110 0 C 58 230 F Enabled only when the evaporator probe is present sets the temperature measured by the evaporator probe which causes the end of defrost IdF Inter...

Страница 3: ...ntil the digital input is activated 6 7 CONFIGURABLE INPUT REMOTE ON OFF ONF This function allows to switch ON and OFF the instrument 6 8 DIGITAL INPUTS POLARITY The digital inputs polarity depends on I1P and I2P parameters CL the digital input is activated by closing the contact OP the digital input is activated by opening the contact 7 INSTALLATION AND MOUNTING Instruments XW263L shall be mounte...

Страница 4: ...rescent lights fans relay SPST 8 3 A 250Vac defrost relay SPDT 16 3 A 250Vac Other output alarm buzzer Hot Key output Serial output RS485 standard Communication protocol Modbus RTU Data storing on the non volatile memory EEPROM Kind of action 1B Pollution grade normal Software class A Operating temperature 0 60 C Storage temperature 25 60 C Relative humidity 20 85 no condensing Measuring and regul...

Отзывы: