1592009000 XW220L GB r1.2 03.08.2015 

                           XW220L 

3/4 

 

6.3

 

CONFIGURABLE INPUT - SERIOUS ALARM MODE (BAL) 

When the digital input is activated, the unit will wait for “

did

” delay before signalling the “

BAL

” alarm message. 

The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-activated. 
 

6.4

 

CONFIGURABLE INPUT - PRESSURE SWITCH (PAL) 

If during the interval time set by “

did

” parameter, the pressure switch has reached the number of activation of  

the “

nPS

” parameter, the “

PAL

” pressure alarm message will be displayed. The compressor and the regulation 

are stopped. When the digital input is ON the compressor is always OFF. 
 

6.5

 

CONFIGURABLE INPUT - START DEFROST (DFR) 

It  executes  a  defrost  if  there  are  the  right  conditions.  After  the  defrost  is  finished,  the  normal  regulation  will 
restart only if the digital input is disabled otherwise the instrument will wait until the “Mdf” safety time is expired. 
 

6.6

 

CONFIGURABLE INPUT - ENERGY SAVING (ES) 

The Energy Saving function allows to change the set point value as the result of the SET+ HES (parmeter) sum. 
This function is enabled until the digital input is activated. 
 

6.7

 

CONFIGURABLE INPUT -  REMOTE ON/OFF (ONF) 

This function allows to switch ON and OFF the instrument. 
 

6.8

 

DIGITAL INPUTS POLARITY  

The digital inputs polarity depends on “

I1P

” and “

I2P

” parameters. 

 

CL

 : the digital input is activated by closing the contact.

 

 

OP

 : the digital input is activated by opening the contact 

 

 

7.

 

INSTALLATION AND MOUNTING 

Instruments 

XW220L

 shall be mounted on vertical panel, in a 150x31 mm hole, and fixed using two screws 

 3 

x 2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-L). The temperature 
range  allowed  for  correct  operation  is  0  -  60  °C.  Avoid  places  subject  to  strong  vibrations,  corrosive  gases, 
excessive  dirt  or  humidity.  The  same  recommendations  apply  to  probes.  Let  the  air  circulate  by  the  cooling 
holes. 

7.1

 

CUT OUT 

 

165

150

31

+0.5

-0

+0

.5

-0

+1

-1

Ø3 x2

 

 

7.2

 

MOUNTING WITH KEYBOARD COVER OPENING DOWNWARD 

 

CLICK!

1

2

2

3

3

1

1

 

7.3

 

MOUNTING WITH KEYBOARD COVER OPENING UPWARD 

 

CLICK!

1

2

2

2

3

3

1

1

 

 
 

8.

 

ELECTRICAL CONNECTIONS 

The instruments are provided with screw terminal block to connect cables with a cross section up to 2,5 mm

for 

the digital and analogue inputs.  Relays and power supply have a Faston connection (6,3mm). Heat-resistant 
cables have to be used. Before connecting cables make sure the power supply complies with the instrument’s 
requirements.  Separate  the  probe  cables  from  the  power  supply  cables,  from  the  outputs  and  the  power 
connections. Do not exceed the maximum current allowed on each relay, in case of heavier loads use a suitable 
external relay. 

N.B.

 Maximum current allowed for all the loads is 20A. 

 

8.1

 

PROBE CONNECTIONS 

The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration. It is 
recommended  to  place  the  thermostat  probe  away  from  air  streams  to  correctly  measure  the  average  room 
temperature. 
 

9.

 

TTL SERIAL LINE 

The TTL connector allows, by means of the external module TTL/RS485, to connect the unit to a network line 

ModBUS-RTU

 compatible as the Dixell monitoring system XJ500 (Version 3.0). 

The same TTL connector is used to upload and download the parameter list of the “

HOT KEY

“. 

 

 

10.

 

USE OF THE PROGRAMMING “HOT KEY “ 

The Wing units can UPLOAD or DOWNLOAD the parameter list from its own E2 internal memory to the 

“Hot 

Key” 

and vice-versa. 

 

10.1

 

DOWNLOAD (FROM THE “HOT KEY” TO THE INSTRUMENT) 

1.

 

Turn OFF the instrument by means of the ON/OFF key, remove the TTL serial cable if present, insert 
the 

“Hot Key” 

and then turn the Wing ON. 

2.

 

Automatically  the  parameter  list  of  the 

“Hot  Key”

  is  downloaded  into  the  Wing  memory,  the  “

DoL

” 

message is blinking. After 10 seconds the instrument will restart working with the new parameters. 

3.

 

Turn OFF the instrument remove the 

“Hot Key”, 

plug in  the TTL serial cable, then turn it ON again. 

At the end of the data transfer phase the instrument displays the following messages: 

end

 “ for right programming. The instrument starts regularly with the new programming. 

err

” for failed programming. In this case turn the unit off and then on if you want to restart the download again 

or remove the “

Hot key

” to abort the operation. 

 

10.2

 

UPLOAD (FROM THE INSTRUMENT TO THE “HOT KEY”) 

1.

 

Turn OFF the instrument by means of the ON/OFF key and remove the TTL serial cable if present; then 
turn it ON again. 

2.

 

When the Wing unit  is ON, insert the “

Hot key

” and push 

o

key; the  

"uPL" 

message appears. 

3.

 

Push “

SET”

 key to start the UPLOAD; the “

uPL

” message is blinking. 

4.

 

Turn OFF the instrument remove the 

“Hot Key”, 

plug in  the TTL serial cable, then turn it ON again. 

At the end of the data transfer phase the instrument displays the following messages: 

end

 “ for right programming. 

err

”  for  failed  programming.  In  this  case  push  “SET”  key  if  you  want  to  restart  the  programming  again  or 

remove the not programmed “

Hot key

”. 

 
 

11.

 

ALARM SIGNALS 

Message  Cause 

Outputs 

“P1” 

Thermostat probe failure 

Alarm  output  ON;  Compressor  output  according  to 
parameters “COn” and “COF” 

“P3” 

Auxiliary probe failure 

Alarm output ON; Other outputs unchanged 

“HA” 

Maximum temperature alarm 

Alarm output ON; Other outputs unchanged 

“LA” 

Minimum temperature alarm 

Alarm output ON; Other outputs unchanged 

“EE”  

Data or memory failure 

Alarm output ON; Other outputs unchanged 

“dA” 

Defrost timeout alarm 

Alarm output ON; Other outputs unchanged 

“dAL” 

Door switch alarm 

Alarm output ON; Other outputs unchanged 

“EAL” 

External alarm 

Alarm output ON; Other outputs unchanged 

“BAL” 

Serious external alarm 

Alarm output ON; Other outputs OFF 

“PAL” 

Pressure switch alarm 

Alarm output ON; Other outputs OFF

 

The alarm message is displayed until the alarm condition is recovery. 
All the alarm messages are showed alternating with the room temperature except for the “P1” which is flashing. 
To reset the “EE” alarm and restart the normal functioning press any key, the “

rSt

” message is displayed for 

about 3s. 

11.1

 

SILENCING BUZZER  

Once the alarm signal is detected the buzzer and the relay are is silenced by pressing any key.  
 

11.2

 

“EE” ALARM 

The  Dixell  instruments  are  provided  with  an  internal  check  for  the  data  integrity.  Alarm  “EE”  flashes  when  a 
failure in the memory data occurs. In such cases the alarm output is enabled. 
 

11.3

 

ALARM RECOVERY 

Probe  alarms  :  “

P1

”  (probe1  faulty),  and  “

P3

”;  they  automatically  stop  10s  after  the  probe  restarts  normal 

operation. Check connections before replacing the probe. 
Temperature alarms “

HA

” and “

LA

” automatically stop as soon as the thermostat temperature returns to normal 

values or when the defrost starts. 
Door switch alarm “

dA

”  stop as soon as the door is closed. 

External alarms “

EAL

”, “

BAL

”  stop as soon as the external digital input is disabled “

PAL

” alarm is recovered by 

switching OFF the instrument. 
 
 
 
 
 
 
 
 
 
 

Содержание Dixell WING XW220L

Страница 1: ...cles while its length is controlled by parameter MdF 4 KEYBOARD To display and modify target set point in programming mode it selects a parameter or confirm an operation By holding it pressed for 3s when max or min temperature is displayed it will be erased To see the max stored temperature in programming mode it browses the parameter codes or increases the displayed value By holding it pressed fo...

Страница 2: ...t Ab High and low alarms related to the absolute temperature ALU High temperature alarm setting ALC rE 0 50 C or 90 F ALC Ab ALL 110 C or 230 F when this temperature is reached and after the ALd delay time the HA alarm is enabled ALL Low temperature alarm setting ALC rE 0 50 C or 90 F ALC Ab 50 C or 58 F ALU when this temperature is reached and after the ALd delay time the LA alarm is enabled AFH ...

Страница 3: ...OGRAMMING HOT KEY The Wing units can UPLOAD or DOWNLOAD the parameter list from its own E2 internal memory to the Hot Key and vice versa 10 1 DOWNLOAD FROM THE HOT KEY TO THE INSTRUMENT 1 Turn OFF the instrument by means of the ON OFF key remove the TTL serial cable if present insert the Hot Key and then turn the Wing ON 2 Automatically the parameter list of the Hot Key is downloaded into the Wing...

Страница 4: ...ressor ON time with faulty probe 0 255 min 15 Pr2 COF Compressor OFF time with faulty probe 0 255 min 30 Pr2 CH Type of action CL Ht CL Pr2 DISPLAY CF Temperature measurement unit C F C Pr2 rES Resolution integer decimal point in de de Pr1 Lod Local display P1 1r2 P1 Pr2 Red Remote display P1 1r2 P1 Pr2 DEFROST EdF Defrost mode In Sd In Pr2 IdF Interval between defrost cycles 1 120h 8 Pr1 MdF Maxi...