144
Digitax ST User Guide
Issue Number: 5
12.10 Menu 10: Status and trips
*The value given for the range is that obtained via serial communication. For the text string displayed on the drive, see Chapter 14
Parameter
Range(
Ú
)
Default(
Ö
)
Type
10.01
Drive ok
OFF (0) or On (1)
RO Bit
NC PT
10.02
Drive active
OFF (0) or On (1)
RO Bit
NC PT
10.03
Zero speed
OFF (0) or On (1)
RO Bit
NC PT
10.04
Running at or below minimum
speed
OFF (0) or On (1)
RO Bit
NC PT
10.05
Below set speed
OFF (0) or On (1)
RO Bit
NC PT
10.06
At speed
OFF (0) or On (1)
RO Bit
NC PT
10.07
Above set speed
OFF (0) or On (1)
RO Bit
NC PT
10.08
Load reached
OFF (0) or On (1)
RO Bit
NC PT
10.09
Drive output is at current limit
OFF (0) or On (1)
RO Bit
NC PT
10.10
Regenerating
OFF (0) or On (1)
RO Bit
NC PT
10.11
Braking IGBT active
OFF (0) or On (1)
RO Bit
NC PT
10.12
Braking resistor alarm
OFF (0) or On (1)
RO Bit
NC PT
10.13
Direction commanded
OFF (0) or On (1) [0 = FWD, 1 = REV]
RO Bit
NC PT
10.14
Direction running
OFF (0) or On (1) [0 = FWD, 1 = REV]
RO Bit
NC PT
10.15
Line power supply loss
OFF (0) or On (1)
RO Bit
NC PT
10.16
Under voltage active
OFF (0) or On (1)
RO Bit
NC PT
10.17
Overload alarm
OFF (0) or On (1)
RO Bit
NC PT
10.18
Drive over temperature alarm
OFF (0) or On (1)
RO Bit
NC PT
10.19
Drive warning
OFF (0) or On (1)
RO Bit
NC PT
10.20
Trip 0
0 to 230*
RO Txt
NC PT PS
10.21
Trip 1
0 to 230*
RO Txt
NC PT PS
10.22
Trip 2
0 to 230*
RO Txt
NC PT PS
10.23
Trip 3
0 to 230*
RO Txt
NC PT PS
10.24
Trip 4
0 to 230*
RO Txt
NC PT PS
10.25
Trip 5
0 to 230*
RO Txt
NC PT PS
10.26
Trip 6
0 to 230*
RO Txt
NC PT PS
10.27
Trip 7
0 to 230*
RO Txt
NC PT PS
10.28
Trip 8
0 to 230*
RO Txt
NC PT PS
10.29
Trip 9
0 to 230*
RO Txt
NC PT PS
10.30
Full power braking time
0.00 to 400.00 s
RW Uni
US
10.31
Full power braking period
0.0 to 1500.0 s
RW Uni
US
10.32
External trip
OFF (0) or On (1)
OFF (0)
RW Bit
NC
10.33
Drive reset
OFF (0) or On (1)
OFF (0)
RW Bit
NC
10.34
No. of auto-reset attempts
0 to 5
0
RW Uni
US
10.35
Auto-reset delay
0.0 to 25.0 s
1.0
RW Uni
US
10.36
Hold drive ok until last
attempt
OFF (0) or On (1)
OFF (0)
RW Bit
US
10.37
Action on trip detection
0 to 15
0
RW Uni
US
10.38
User trip
0 to 255
0
RW Uni
NC
10.39
Braking energy overload
accumulator
0.0 to 100.0 %
RO Uni
NC PT
10.40
Status word
0 to 32,767
RO Uni
NC PT
10.41
Trip 0 time: years.days
0.000 to 9.365 years.days
RO Uni
NC PT PS
10.42
Module number for trip 0, or, Trip 0
time: hours.minutes
00.00 to 23.59 hours.minutes
RO Uni
NC PT PS
10.43
Module number for trip 1, or, Trip 1 time
0 to 600.00 hours.minutes
RO Uni
NC PT PS
10.44
Module number for trip 2, or, Trip 2 time
0 to 600.00 hours.minutes
RO Uni
NC PT PS
10.45
Module number for trip 3, or, Trip 3 time
0 to 600.00 hours.minutes
RO Uni
NC PT PS
10.46
Module number for trip 4, or, Trip 4 time
0 to 600.00 hours.minutes
RO Uni
NC PT PS
10.47
Module number for trip 5, or, Trip 5 time
0 to 600.00 hours.minutes
RO Uni
NC PT PS
10.48
Module number for trip 6, or, Trip 6 time
0 to 600.00 hours.minutes
RO Uni
NC PT PS
10.49
Module number for trip 7, or, Trip 7 time
0 to 600.00 hours.minutes
RO Uni
NC PT PS
10.50
Module number for trip 8, or, Trip 8 time
0 to 600.00 hours.minutes
RO Uni
NC PT PS
10.51
Module number for trip 9, or, Trip 9 time
0 to 600.00 hours.minutes
RO Uni
NC PT PS
RW Read / Write
RO
Read only
Uni
Unipolar
Bi
Bi-polar
Bit
Bit parameter
Txt
Text string
FI
Filtered
DE
Destination
NC
Not copied
RA
Rating dependent
PT
Protected
US
User save
PS
Power down save