Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual
Section 4: Configuration
3-9000-765 Rev H
June 2017
Using AMS Device Manager to configure the meter
91
Action parameters. Click
Apply
, after you enter the data to write the parameters to the
meter.
6.
Click the
Frequency/Digital
Outputs tab. Follow the configuration instructions in the
AMS Device Manager - Guided Setup
,
). (Refresh Note: If changes are made to
any Source variable on this page, apply the changes and navigate to the Guided Setup
page. Navigate back to the Manual Setup for the changes to be reflected in other
Manual Setup pages). Click
Apply
, after you enter the data to write the parameters to
the meter.
7.
Click the
Frequency and Digital Output 1
tab. Follow the configuration instructions in the
AMS Device Manager - Guided Setup,
. Click
Apply
, after you enter the data to
write the parameters to the meter.
8.
Click the
Frequency and Digital Output 2
tab. Follow the instructions in the
to configure the Frequency and Digital Output 2
parameters. Click
Apply
, after you enter the data to write the parameters to the meter.
9.
Click the
Temperature
tab. Configure the input parameters including: Source (Live
Analog or Fixed), Min and Max input limits corresponding to 4 mA and 20 mA
respectively and the Low and High alarm limits. Click
Apply
, after you enter the data to
write the parameters to the meter.
10.
Click the
Pressure
tab. Configure the input parameters including: Source (Live Analog or
Fixed), Min and Max input limits corresponding to 4 mA and 20 mA respectively and the
Low and High alarm limits. Select either
Gage
or
Absolute
for the type of pressure
reading desired. If a live pressure transmitter is connected, select the type of reading
the transmitter outputs. If Absolute is selected, you must also enter the Atmospheric
pressure. Click
Apply
, after you enter the data to write the parameters to the meter.
11.
Click the
Digital Input
tab. The default Digital Input 1 polarity is set to
Normal
for general
purpose or set to
Inverted
when used for calibration. Click
Apply
, after you choose the
calibration data to write the parameters to the meter.
a.
Calibration Polarity configuration parameter selections are:
–
Digital Input 1 Calibrate Active High
–
Digital Input 1 Calibrate Active Low