Electrical Field Connections—Downflow Models
71
Liebert
®
CW
™
System Design Manual
Figure 6-5 Electrical field connections, downflow, CW146 and CW181 with EC fans
Refer to descriptions that follow for explanation of numbered items.
6.1.1
Standard Electrical Connections
for Downflow Models CW146 and CW181
Refer to
. Source: DPN001699, Rev. 4.
1.
Primary high voltage entrance—2-1/2”
(64mm); 1-3/4” (44mm); 1-3/8” (35mm) diameter concentric
knockouts in bottom of box.
2.
Primary low voltage entrance
—Quantity (3) 1-1/8” (28mm) diameter knockouts in bottom of box
3.
Three-phase electrical service
—Terminals are on main fuse block (disregard if unit has optional
disconnect switch). Three-phase service not by Emerson.
4.
Earth ground
—Terminal for field-supplied earth grounding wire.
5.
Remote unit shutdown
—Replace existing jumper between Terminals 37 and 38 with field-supplied
normally closed switch having a minimum 75VA, 24VAC rating. Use field-supplied Class 1 wiring.
6.
Customer alarm inputs
—Terminals for field-supplied, normally open contacts, having a minimum
75VA, 24VAC rating, between Terminals 24 and 50, 51, 55, 56. Use field-supplied Class 1 wiring.
Terminal availability varies by unit options.
7.
Common alarm
—On any alarm, normally open dry contact is closed across Terminals 75 and 76 for
remote indication. 1A, 24VAC maximum load. Use Class 1 field-supplied wiring.
A
B
C
D
37C 38C 37B38B 37 38
24 50 51 55 56 11 12
58 59 84 85 94 95 96 97 75 76
91 92 93 80 81 82 83
88 89
13
12
19
7
15
6
17
5
18
14
106 107 110 111
16
11
2
1
10
8
4 50Hz
3
4
B
A
C
D
Note: Typical orientation of components shown.
Component location varies by option and unit.
Electric Panel Layout
CW 60Hz
Condensate
Pump Fuses
Reheat
Fuses
Humidifier Fuses
Main
Fan
Fuses
Control
Fuses
Power
Block
Ground Lug
Ground
Current
Detector
Reheat
Contactors
Backup
Reheat
Contactor
Humidifier
Contactor
Main Fan
Contactor
T1 Transformer
T6 Transformer
Filter Clog
Switch
Remote
Humidifier
Relay
CPAR
Relay
Smoke Detector
Power Supply
Liebert iCOM
Fuse Board
Terminals for
Field Low Voltage
Wiring Connections
Liebert
IntelliSlot
Housings
Liebert IntelliSlot
Power Supply
Large Liebert iCOM
I/O Board
High
Temp
Stat
R3 Relay
Liebert Liqui-tect
Shutdown
Relay
EM1 Relay
Field High Voltage
Entrance
Cover Plate /
Reversing Starter
Location
Main
Fuses
Disconnect
Power Block
Fan Transformer Fuses
(B) Voltage Only
DPN001699
Pg. 3 Rev. 4
Содержание CW089
Страница 2: ......
Страница 8: ...Liebert CW System Design Manual vi ...
Страница 10: ...Liebert CW System Design Manual vi Page intentionally left blank ...
Страница 18: ...Nomenclature and Components Liebert CW System Design Manual 8 Page intentionally left blank ...
Страница 62: ...Dimensions Liebert CW System Design Manual 52 Page intentionally left blank ...
Страница 76: ...Piping Liebert CW System Design Manual 66 Page intentionally left blank ...
Страница 90: ...Electrical Field Connections Liebert CW System Design Manual 80 Page intentionally left blank ...
Страница 114: ...Optional Liebert Air Economizer for Liebert CW Liebert CW System Design Manual 104 Page intentionally left blank ...