Downstream Control Line Installation

!

WARNING

Failure to install a downstream control line 

could result in a hazardous condition. Install 

downstream control line(s) to the slam-shut 

device when construction uses external 

pressure registration. The regulator and 

slam-shut device will not control pressure 

or shut off if a downstream control line is 

not installed on those constructions where 

external pressure registration is required.

CSB700 Series regulators with an “ET” or “EN” in the type 

number use external pressure registration. To communicate 

the downstream pressure to the regulator, connect a 

downstream control line tubing to the 3/4 NPT control line 

tapping in the lower diaphragm casing and connect the other 

end of the tubing downstream of the regulator outlet with a 

minimum distance of 6 times the outlet pipe diameter.
For all types with external control lines, use tubing with an 

inner diameter of 16 mm / 0.63 in. or larger. 

Downstream Control Line Installation with 

Slam-Shut Device

Refer to Figure 1. When installing the Types CSB704ET, 

CSB704FET, CSB704FEN CSB704EN, CSB724ET, 

CSB724EN, CSB724FEN and CSB754EN regulators, 

connect downstream control line tubing to the lower casing 

of the regulator and run the tubing downstream of the 

regulator outlet with a minimum distance of 6 times the outlet 

pipe diameter. Connect a second, separate downstream 

control line tubing to the lower casing of the slam-shut and 

run the tubing downstream of the regulator outlet a minimum 

distance of 6 times the outlet pipe diameter.
For all types with external control lines, use tubing with an 

inner diameter of 16 mm / 0.63 in. or larger for the primary 

regulator and 6.4 mm / 0.25 in. or larger for the slam-shut.

Installation with External Overpressure Protection

If the regulator is used in conjunction with a Type 289H 

relief valve, it should be installed as shown in Figure 6. 

The outside end of the vent line should be protected 

with a rainproof assembly. The Type 289H is typically 

set 25 mbar / 10 in. w.c. higher than the outlet pressure 

setting of the regulator, up to 75 mbar / 30 in. w.c. outlet 

pressure. For pressure greater than this, set the Type 289H 

0.05 bar / 0.73 psi higher than the outlet pressure setting 

of the regulator. Refer to the 289 Series Instruction Manual 

(D100280X012) for more information. 

Installation

!

WARNING

Only qualified personnel shall install or 

service a regulator. Regulators should 

be installed, operated and maintained 

in accordance with international and 

applicable codes and regulations and 

Emerson instructions.
If the regulator vents fluid or a leak develops 

in the system, it indicates that service 

is required. Failure to take the regulator 

out of service immediately may create a 

hazardous condition.
Personal injury, equipment damage or 

leakage due to escaping gas or bursting of 

pressure containing parts may result if this 

regulator is overpressured or is installed 

where service conditions could exceed the 

limits given in the Specifications section or 

where conditions exceed any ratings of the 

adjacent piping or piping connections.
To avoid such injury or damage, provide 

pressure-relieving or pressure-limiting 

devices (as required by the appropriate code, 

regulation or standard) to prevent service 

conditions from exceeding limits.
Additionally, physical damage to the 

regulator could result in personal injury and 

property damage due to escaping fluid. To 

avoid such injury and damage, install the 

regulator in a safe location.

Clean out all pipelines before installation of the regulator 

and check to be sure the regulator has not been damaged 

or has collected foreign material during shipping. For NPT 

bodies, apply pipe compound to the external pipe threads. 

For flanged bodies, use suitable line gaskets and approved 

piping and bolting practices. Install the regulator in any 

position desired, unless otherwise specified, but be sure flow 

through the body is in the direction indicated by the arrow on 

the body.

Note

It is important that the regulator be installed 

so that the vent hole in the spring case 

is unobstructed at all times. For outdoor 

installations, the regulator should be located 

away from vehicular traffic and positioned 

so that water, ice and other foreign materials 

cannot enter the spring case through the 

vent. Avoid placing the regulator beneath 

eaves or downspouts and be sure it is above 

the probable snow level.

Содержание CSB700 Series

Страница 1: ...tions and Pressure Ratings 1 See Table 4 Operating Pressure Range 1 Regulator See Table 5 Slam Shut Module See Tables 7a 7b 7c and 7d Maximum Outlet Pressure 1 Emergency Casing Type CSB700 CSB700F CSB720 CSB720F 4 0 bar 58 0 psig Type CSB750 5 0 bar 72 5 psig To Avoid Internal Metallic Parts Damage Type CSB700 CSB700F CSB720 CSB720F 0 34 bar 5 0 psig over set pressure Type CSB750 1 5 bar 21 8 psig...

Страница 2: ...regarding the Type VSX8 Slam shut Module 2 The pressure temperature limits in this Installation Guide and any applicable standard or code limitation should not be exceeded 3 Token relief not available for outlet pressure above 500 mbar 8 psig TYPE MAXIMUM ALLOWABLE PRESSURE MAXIMUM EMERGENCY INLET PRESSURE MAXIMUM OPERATING INLET PRESSURE 2 PS PUMAX bar psig bar psig CSB700 and CSB704 4 0 58 0 4 0...

Страница 3: ...URE RANGES Wd PART NUMBER SPRING COLOR SPRING WIRE DIAMETER SPRING FREE LENGTH mbar psig mm In mm In CSB700 CSB704 CSB700F and CSB704F 9 to 14 3 6 to 5 6 in w c GE30336X012 Silver 3 00 0 118 224 8 82 13 to 24 5 2 to 9 6 in w c ERSA01138A0 Red 3 50 0 138 264 10 4 22 to 39 8 8 to 15 7 in w c GE30338X012 Black Stripe 4 32 0 170 172 6 78 32 to 50 12 8 to 20 1 in w c GE30339X012 Purple 4 34 0 171 187 7...

Страница 4: ...50 1600 to 5000 1 3400 4000 3100 to 4000 4400 Gray areas indicate that token relief is not available above 500 mbar setpoint 1 Max OPSO setpoint truncated to reflect maximum outlet pressure for spring range Table 7a North American Overpressure Shut off OPSO Only Ranges REGULATOR SLAM SHUT DEVICE Type Typical Setpoint Spring Range Type Maximum Operating Inlet Token Relief Set Relief Range Shown as ...

Страница 5: ... 750 460 to 932 375 835 to 1120 1 1050 CSB724F 300 270 to 325 VSX8L 8 6 bar 100 to 500 179 to 386 200 379 to 586 400 CSB754 GrDF 1 bar 0 7 to 1 19 bar VSX8L 16 bar 100 to 500 460 to 932 750 1210 to 1682 1210 CSB754 1 bar 0 7 to 1 19 bar 100 to 500 460 to 932 500 960 to 1432 1320 1 2 bar 1 05 to 2 7 bar VSX8H 16 bar 500 to 2000 1050 to 1570 600 1650 to 2170 1650 1 5 bar 750 1800 to 2320 1900 2 bar ...

Страница 6: ... in w c outlet pressure For pressure greater than this set the Type 289H 0 05 bar 0 73 psi higher than the outlet pressure setting of the regulator Refer to the 289 Series Instruction Manual D100280X012 for more information Installation WARNING Only qualified personnel shall install or service a regulator Regulators should be installed operated and maintained in accordance with international and a...

Страница 7: ...tlet pressure rating Overpressure protection should also be provided if the regulator inlet pressure is greater than the safe working pressure of the downstream equipment Regulator operation below the maximum pressure limitations does not preclude the possibility of damage from external sources or debris in the line The regulator should be inspected for damage after any overpressure condition Star...

Страница 8: ...alve Seat Nut Zinc plated steel 41 Token Relief Spring Music Wire 42 Spring Retainer Zinc plated steel with token relief 43 Spring Seat Zinc plated steel 44 Stem Zinc plated steel with token relief Recommended spare part Lustran is a mark owned by INEOS ABS USA Limited 45 Screw Zinc plated steel without token relief 46 Token Relief Nut Steel 50 Pusher Post Aluminum 51 Relief Valve Seat Aluminum 52...

Страница 9: ...ator Installed with the Vent Pointed Downward and with a Type 289H Relief Valve for High Capacity Relief CSB700 SERIES REGULATOR PROTECT VENT PIPE WITH RAIN CAP DN 50 NPS 2 TYPE 289H RELIEF VALVE Note Install with vent pointed vertically down Otherwise regulator must be installed under a separate protective cover ...

Страница 10: ...RQUE 6 TO 8 N m 4 TO 6 FT LBS 111C 111D 111B 111F L1 25 L2 82 L2 36 71 80 20 21 L2 L2 L1 65 62 L1 L2 100 8 TORQUE 1 7 TO 3 4 N m 15 TO 30 IN LBS 95 6 111E 111A TORQUE 10 TO 13 N m 7 TO 10 FT LBS 111G 43 55 9 1 4 7 5 TORQUE 1 7 TO 3 4 N m 15 TO 30 IN LBS 51 44 52 TORQUE 6 TO 7 N m 50 TO 60 IN LBS L2 50 54 53 68 112 13 14 10 TORQUE 3 5 TO 4 N m 31 TO 35 IN LBS 18 17 11 L2 76 77 75 19 96 74 L2 L2 L2 ...

Страница 11: ...1C 111G 111D 111B 111E 55 1 9 43 105 TORQUE 10 TO 13 N m 7 TO 10 FT LBS L2 53 19 L2 75 L2 54 L2 77 76 74 96 10 14 13 112 11 18 68 TORQUE 3 5 TO 4 N m 31 TO 35 IN LBS L2 L2 82 L1 25 TORQUE 34 TO 47 N m 25 TO 35 FT LBS 80 TORQUE 6 TO 8 N m 4 TO 6 FT LBS TORQUE 6 TO 7 N m 50 TO 60 IN LBS TORQUE 12 N m 9 FT LBS MAX 51 45 40 L1 38 63 66 36 71 TORQUE 14 TO 18 N m 10 TO 13 FT LBS 70 17 16 15 INITIAL TORQ...

Страница 12: ...rson Automation Solutions D103483X014 2017 2018 Emerson Process Management Regulator Technologies Inc All rights reserved 07 18 The Emerson logo is a trademark and service mark of Emerson Electric Co All other marks are the property of their prospective owners Fisher is a mark owned by Fisher Controls International LLC a business of Emerson Automation Solutions The contents of this publication are...