Network Wiring
Dixell XWEB300D Serial Address
•
Connect to the ModBUS network using cable with 2 or 3 shielded wires, minimum section 0.5mm2
(e.g. BELDEN8772)
•
Do not connect shield to ground.
•
Do not connect the “Gnd” terminal.
•
Remember to draw a map of the line. This will help you to find an error if something is wrong.
•
RS485 devices are polarity sensitive.
Figure 5.
Correct Network Wiring
Figure 6 .
Incorrect Network Wiring
Download the Program from Hot-Key to Controller
Step
Action
Phenomenon and Description
1
Turn-off the controller
2
Insert Hot-Key
3
Turn-on the controller
The “doL” message will blink followed a by a flashing “End” label (Note: if display “Err”,
it means it fails to download program to the controller. Please restart the process.)
4
Controller will restart working with the new parameters after 10 seconds
5
Remove Hot-Key