© 2017 Emerson Climate Technologies, Inc.
33
AE5-1377 R3
Table 12 - Sensor Information
In the event there is fault code referencing a possible issue with any one of the four unit control temperature sensors,
see this table to assess the fault code condition. If the resistance of the sensor in question does not compare to the
information provide in the table for the applicable sensor, then that sensor will need replaced.
DLT
Coil-in
Amb/Mid-Coil
VIT/VOT
Temp
(F)
Temp
(C)
R
(kohm)
Temp
(F)
Temp
(C)
R
(kohm)
Temp
(F)
Temp
(C)
R
(kohm)
Temp
(F)
Temp
(C)
R
(kohm)
140
60
22.99
50
10
207.6
-22
-30
121.9
5
-15
56.48
142
61
22.13
52
11
197.2
-20
-29
115.5
7
-14
53.78
144
62
21.31
54
12
187.5
-18
-28
109.5
9
-13
51.24
145
63
20.51
55
13
178.4
-17
-27
103.9
10
-12
48.84
147
64
19.78
57
14
169.7
-15
-26
98.54
12
-11
46.56
149
65
19.06
59
15
161.5
-13
-25
93.52
14
-10
44.4
151
66
18.36
61
16
153.7
-11
-24
88.78
16
-9
42.36
153
67
17.7
63
17
146.4
-9
-23
84.32
18
-8
40.42
154
68
17.06
64
18
139.4
-8
-22
80.1
19
-7
38.58
156
69
16.45
66
19
132.8
-6
-21
76.12
21
-6
36.84
158
70
15.87
68
20
126.6
-4
-20
72.38
23
-5
35.08
160
71
15.31
70
21
120.6
-2
-19
68.82
25
-4
33.62
162
72
14.78
72
22
115.1
0
-18
65.48
27
-3
32.12
163
73
14.26
73
23
109.8
1
-17
62.3
28
-2
30.7
165
74
13.77
75
24
104.7
3
-16
59.3
30
-1
29.36
167
75
13.29
77
25
100
5
-15
56.48
32
0
28.08
169
76
12.83
79
26
95.47
7
-14
53.78
34
1
26.86
171
77
12.39
81
27
91.19
9
-13
51.24
36
2
25.7
172
78
11.97
82
28
87.1
10
-12
48.84
37
3
24.6
174
79
11.57
84
29
83.24
12
-11
46.56
39
4
23.56
176
80
11.18
86
30
79.55
14
-10
44.4
41
5
22.46
178
81
10.8
88
31
76.05
16
-9
42.36
43
6
21.6
180
82
10.44
90
32
72.73
18
-8
40.42
45
7
20.7
181
83
10.1
91
33
35.12
19
-7
38.58
46
8
19.84
183
84
9.761
93
34
66.56
21
-6
36.84
48
9
19.02
185
85
9.443
95
35
63.7
23
-5
35.08
50
10
18.24
187
86
9.135
97
36
60.98
25
-4
33.62
52
11
17.49
189
87
8.836
99
37
58.4
27
-3
32.12
54
12
16.78
190
88
8.55
100
38
55.92
28
-2
30.7
55
13
16.11
192
89
8.275
102
39
53.59
30
-1
29.36
57
14
15.46
194
90
8.01
104
40
51.34
32
0
28.08
59
15
14.84
196
91
7.754
106
41
49.21
34
1
26.86
61
16
14.25
198
92
7.508
108
42
47.18
36
2
25.7
63
17
13.69
199
93
7.272
109
43
45.25
37
3
24.6
64
18
13.15
201
94
7.044
111
44
43.39
39
4
23.56
66
19
12.64
Содержание Copeland Scroll Series
Страница 9: ... 2017 Emerson Climate Technologies Inc 9 AE5 1377 R3 Figure 1 Nomenclature and Features ...
Страница 10: ... 2017 Emerson Climate Technologies Inc 10 AE5 1377 R3 Figure 2 Physical and Installation Requirements ...
Страница 14: ... 2017 Emerson Climate Technologies Inc 14 AE5 1377 R3 Drawings ...
Страница 15: ... 2017 Emerson Climate Technologies Inc 15 AE5 1377 R3 ...
Страница 16: ... 2017 Emerson Climate Technologies Inc 16 AE5 1377 R3 ...
Страница 17: ... 2017 Emerson Climate Technologies Inc 17 AE5 1377 R3 ...
Страница 18: ... 2017 Emerson Climate Technologies Inc 18 AE5 1377 R3 ...
Страница 19: ... 2017 Emerson Climate Technologies Inc 19 AE5 1377 R3 ...
Страница 20: ... 2017 Emerson Climate Technologies Inc 20 AE5 1377 R3 ...
Страница 21: ... 2017 Emerson Climate Technologies Inc 21 AE5 1377 R3 ...
Страница 22: ... 2017 Emerson Climate Technologies Inc 22 AE5 1377 R3 ...
Страница 23: ... 2017 Emerson Climate Technologies Inc 23 AE5 1377 R3 ...
Страница 39: ...APPENDIX 2 ...