background image

 

CC7.8.15/1019/E 

Ident number 3272062 

– P/N 052-3306-00/Rev00 

1/2

 

Date of last update: Oct-19 

 

Ref: CC7.8.15/1019/E 

 

 

Application Engineering Europe 

L

ARGE 

O

UTDOOR 

C

ONDENSING 

U

NITS 

 

Q

UICK 

I

NSTALLATION 

G

UIDE

 

 

1.  Install  the  condensing  unit  according  to  Application  Guidelines  C6.1.9  "Copeland  EazyCool

™  Large  Outdoor 

Condensing Units". 

2.  Prefill the unit with refrigerant and set all valves into the operating position. 

3.  Set up the unit controller (XMC25D) for the required application. 

NOTE: The value of parameter D29 must be lower than the value C16-C17/2 (unit switching-off point) to avoid 
the low-pressure alarm. 

NOTE:

 

The  liquid  line  in  OL(T)E  units  must  be  insulated  to  avoid  air-moisture  condensation  and  lack  of 

performance.

 

The XMC25D controller provides 2 programming levels: 

 

Pr1

 with direct access 

 

Pr2

 protected with a password: 

321

 (intended for experts) 

Explanation of LED functionalities: 

LED 

Mode 

Function 

 

On 

Compressor 1 enabled 

Flashing 

Anti-short cycle delay enabled 

 

On 

Condensing fans enabled 

 

On 

Bar display 

Flashing 

Programming mode 

 

On 

PSI display 

Flashing 

Programming mode 

 

On 

When browsing the service menu 

Flashing 

In fast access menu 

 

On 

When browsing the alarm menu 

Flashing 

A new alarm occurred 

 

On 

An alarm is occurring 

 

On 

Digital unloader solenoid On 

 

On 

In defrost 

 

On 

Evaporator fans - Liquid line solenoid valve On 

 

How to program the "Pr1" parameters: 

Access pre-

program level 

 

Press simultaneously for about 3 seconds to access the pre-programming 
level. The message 

rtC

 (real time clock) is displayed. 

Access 

program level 

 or 

 

Press the 

Up

 or 

Down

 key until the message 

Par

 is displayed. 

Access Pr1 

 

Press the 

SET

 button to enter the program level. First parameter 

C01

 is 

displayed. 

Select item 

 or 

 

Select the parameter or submenu using the arrows. 

Show value 

 

Press the 

SET

 button. 

Modify 

 or 

 

Use the arrows to modify the value. 

Confirm and 

store 

 

Press the 

SET

 button: the value will blink for 3 seconds, then the display 

will show the next parameter. 

EXIT 

 

Press simultaneously to exit the programming mode, or wait 
for 30 seconds (MTO) without pressing any key. 

Отзывы: