ControlWave Instruction Manual (CI-ControlWave)
Table 3-15. Jumper Assignments: Non-isolated HSC Module
Jumper Purpose
Description
W1
Enables/disables LEDs on
module
Pins 1-2 installed = Enable LEDs (Factory
default
).
Pins 2-3 installed = Disable LEDs
Wiring the Module
shows field wiring assignments for locally terminated
isolated RTD modules.
shows field wiring assignments for
remotely terminated isolated RTD modules.
provides wiring diagrams for 2-wire, 3-wire, and 4-wire
RTDs to the local RTD module terminal blocks; wiring assignments,
such as +RTD#_3/4W, -RTD#_4W, +RTD# and –RTD# are similar to
those assigned to the Remote DIN-rail mountable terminal blocks.
Note:
To maintain specified accuracy with a 3-wire RTD, you must
match the two field wires that source and sink the RTD current
within 0.01 ohms (matched in length and matched in wire type)
and the ambient temperature on these wires must be the same.
Figure 3-30. Isolated RTD Module - 2-Wire, 3-Wire & 4-Wire Wiring Diagram
3-36
I/O Modules
Revised Nov-2010