32 • Control Link ACC I&O Manual
026-4704 Rev 6
12 Specifications
Temperature Range
Storage Temp: -40°C to 65°C (-40°F to 149°F)
Ambient Operating Temperatures
(UL Listed)
P/N 815-6100
-40°C to +40°C (-40°F to 104°F)
up to 10A (indoor, freestanding with no additional heat sink)
-40°C to +65°C (-40°F to 149°F)
up to 7A (indoor, freestanding with no additional heat sink)
Ambient Operating
Temperatures
(UL Recognized)
P/N 815-6105
-40°C to +25°C (-40°F to 77°F) up to 30A (with additional heat sink with max
thermal resistance of 0.51°C/Watt (0.92°F/Watt)
-40°C to +40°C (-40°F to 104°F) up to 26A (with additional heat sink with
max thermal resistance of 0.51°C/Watt (0.92°F/Watt)
-40°C to +65°C (-40°F to 149°F) up to 18A (with additional heat sink with max
thermal resistance of 0.51°C/Watt (0.92°F/Watt)
Input Voltage
120/240 Nominal (102VAC to 264VAC) 50/60 Hz
Humidity
5% to 95% non-condensing
Door Frame Temp Sensor
+/- 0.4°C of 0 to 80°C (+/- .72°F of 32°F to 176°F)
up to +/- 0.6°C at -40°C and 120°C (+/- 1.08°F at -40°F and 248°F)
Dewpoint Sensor
+/- 1°C (+/- 1.8°F) over RH of 40 to 95% RH
+/- 4°C (+/- 7.2°F) over RH of 10 to 40% RH
Agency Approvals
UL916 Open Energy Management Equipment, File E118489, FCC Part 15
Class A (non-intentional radiators), CE, RoHS
Table 12-1
- Control Link ACC Specifications