background image

NOTE: Take care not to scratch fan housing when
installing blades.

9.

Remove two of the four screws in the motor
assembly and loosen the remaining two screws
(Figure 6).

10.

Connect the terminals of the lower housing
assembly to the terminals of the fan motor
assembly (Figure 6).

11.

Attach the lower housing assembly to the fan motor
using the two key slot holes. (Figure 7). Secure the
lower housing assembly by tightening the two
screws. Reinstall the two screws that were removed.

NOTE: Make sure wires and terminals are positioned
in raised center area of lower housing assembly,
and not pinched between fan and light kit.

5

Electrical Requirements

If your fan is to replace an existing ceiling light fixture,
turn electricity off at the main fuse box at this time and
remove the existing light fixture.

Your new ceiling fan will require a grounded electrical
supply line of 120 volts AC, 60 Hz, 15 amp circuit.
The outlet box must be securely anchored and
capable of withstanding a load of at least 50 pounds.

TERMINALS

LOWER 
HOUSING
ASSEMBLY

FAN MOTOR
ASSEMBLY

REMOVE 
2 SCREWS

LOOSEN 
2 SCREWS

FUSE AND 
FUSE HOLDER

Figure 6

LOWER
HOUSING
ASSEMBLY

RAISED CENTER
AREA OF LIGHT
KIT HOUSING

SCREWS (2)

KEY
SLOT
HOLE (2)

Figure 7

To reduce the risk of fire, electric shock, or personal
injury, mount fan to outlet box marked “Acceptable
for Fan Support”, and use screws supplied with
outlet box. Most outlet boxes commonly used for
support of light fixtures are not acceptable for fan
support and may need to be replaced. Consult a
qualified electrician if in doubt.

WARNING

!

Turning off wall switch is not sufficient. To avoid
possible electrical shock, be sure electricity is
turned off at the main fuse box before wiring. All
wiring must be in accordance with National and
Local codes and the ceiling fan must be properly
grounded as a precaution against possible electrical
shock.

WARNING

!

To avoid fire or shock, follow all wiring instructions
carefully.
Any electrical work not described in these
instructions should be done or approved by a
licensed electrician.

WARNING

!

How to Hang Your

Ceiling Fan

CEILING

FLOOR

AT LEAST

7'

Figure 8

The fan must be hung with at least 7' of clearance
from floor to blades (Figure 8).

WARNING

!

The outlet box and joist must be securely mounted
and capable of supporting at least 50 lbs. Use only a
U.L. outlet box listed as “Acceptable for Fan
Support”.

WARNING

!

8.

To ensure proper blade assembly, make sure the
label on the blades are facing the bottom of the
ceiling fan. Slide blade through center slot in fan
housing. Mount blade to fan housing using three 
3/16-24 x 1/2” slotted Phillips washer head blade
screws (Figure 5).

MOTOR
HUB

3/16-24 x 1/2" SLOTTED
PHILLIPS WASHER HEAD
BLADE SCREWS

FAN BLADE

BLADE SLOT
IN HOUSING

LABEL
(LOCATED ON
BOTTOM OF BLADE)

Figure 5

U.L. Model No.: CF955

Содержание CF955BS 00

Страница 1: ...ers shown on the product with your request To return the product to an authorized service center call 1 800 654 3545 for the address of the nearest authorized service center You will be responsible for all insurance freight or other transportation charges to our factory or authorized service center Your Emerson Air Comfort Ceiling Fan should be properly packed to avoid damage in transit since we w...

Страница 2: ...let box Most outlet boxes commonly used for support of light fixtures are not acceptable for fan support and may need to be replaced Consult a qualified electrician if in doubt 4 The downrod furnished with the fan proves the minimum recommended floor to fan blade clearance for an 8 foot ceiling 5 The fan must be mounted with the fan blades at least 7 feet from the floor to prevent accidental conta...

Страница 3: ...d of the following size 3 Unpacking Instructions For your convenience check off boxes are provided next to each step As each step is completed place a check mark in the box This will insure that all steps have been completed and will be helpful in finding your place should you be interrupted 2 Remove the fan assembly from the protective plastic bag Place the fan assembly into the upper foam pad wi...

Страница 4: ...oth the ceiling cover and the coupler cover are oriented correctly Figure 3 5 Reinstall the hanger ball Figure 4 on the downrod as follows Route the motor leads through the downrod Position the pin through the two holes in the downrod and align the ball so the pin is captured in the groove in the top of the hanger ball Pull the hanger ball up tight against the pin and securely tighten the setscrew...

Страница 5: ...t box marked Acceptable for Fan Support and use screws supplied with outlet box Most outlet boxes commonly used for support of light fixtures are not acceptable for fan support and may need to be replaced Consult a qualified electrician if in doubt WARNING Turning off wall switch is not sufficient To avoid possible electrical shock be sure electricity is turned off at the main fuse box before wiri...

Страница 6: ...d the green grounding lead from the hanger bracket to the grounding conductor of supply this may be a bare wire or wire with green colored insulation Securely connect wires with wire connectors supplied Figure 11 NOTE If you are using an Emerson Light Fixture with your fan see Light Fixture Owner s Manual for wiring 2 Securely connect the fan motor white wire to the supply white neutral wire using...

Страница 7: ...OFF up is ON 3 Install the supplied 12V battery into the transmitter with the and terminals are positioned according to the diagram in the battery compartment Replacement batteries for transmitter 12V batteries recommended are Duracell MN21 Eveready A23 and GP23A CEILING COVER THREADED STUD KNURLED KNOB LOCKWASHERS 2 Figure 12 CODE SWITCH BATTERY COVER REMOTE CONTROL TRANSMITTER BATTERY S E T 1 2 ...

Страница 8: ...ace the battery Replacement batteries for transmitter 12V batteries recommended are Duracell MN21 Eveready A23 and GP23A Operation of Your Remote Control FAN SPEED BUTTONS AIR FLOW DIRECTION BUTTON LIGHT LEVEL BUTTON OFF BUTTON 3 4 1 6 2 5 Figure 16 8 Programming the Ceiling Fan Receiver 1 Restore electrical power to the outlet box by turning the electricity on at the main fuse box 2 Flip the wall...

Страница 9: ...ger ball downrod assembly loose 3 Screws securing fan blade flanges to motor are 3 Check to be sure screws which attach the fan blade loose flanges to the motor are tight 4 Fan blade flanges not seated properly 4 Check to be sure the fan blade flanges seat firmly and uniformly to the surface of the motor If flanges are seated incorrectly loosen the flange screws and retighten according to the proc...

Страница 10: ...leaning your ceiling fan It could damage the motor or the blades and create the possibility of an electrical shock WARNING To reduce the risk of fire electric shock or personal injury mount fan to outlet box marked Acceptable for Fan Support and use screws supplied with outlet box Most outlet boxes commonly used for support of light fixtures are not acceptable for fan support and may need to be re...

Страница 11: ...11 9 4 15 11 6 1 2 3 7 5 14 8 17 16 12 19 10 13 18 3 4 1 6 2 5 Repair Parts U L Model No CF955 ...

Страница 12: ...63743 763743 17 GU 24 Fluorescent 13W Lamp 763747 763747 763747 18 Receiver Motor Control 763742 763742 763742 19 Fuse 1 0A 120W 763744 763744 763744 Owner s Manual BP7373 BP7373 BP7373 Contact your nearest authorized Emerson fan dealer for replacement Fan Light Control Before discarding packaging material be certain all parts have been removed HOW TO ORDER REPAIR PARTS WHEN ORDERING REPAIR PARTS ...

Отзывы: