CASH VALVES™

 TYPE LTC CRYOGENIC REVERSE ACTING TEMPERATURE REGULATOR

INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS

OPERATING INSTRUCTIONS

Temperature Adjustment

The temperature regulator can be set to 
cut-off the flow of gas at any temperature 
from 0 to -40°F (-17 to -40°C) temperature 
range. To adjust the cut-off temperature turn 
the temperature adjustment wheel (10) in a 
counter-clockwise direction to set the regula tor 
at a higher temperature. Turn the wheel in a 
clockwise direction to set the regulator at a 
lower temperature. The wheel is mounted on 
ball bearings to eliminate friction and ensure 
easy operation.

MAINTENANCE INSTRUCTION

CAUTION

Before attempting to replace any spare parts, 
be sure to shut off all pressure connections to 
the valve. With the valve closed however, system 
pressure could still be locked between the shut 
off valve and the inlet and/or outlet sides of the 
regulator. Before proceeding with any valve 
service, be certain to relieve the pressure from 
both sides of the regulator.

When properly applied and correctly installed 
the Type LTC Temperature Regulator should 
require very little attention or maintenance. 
However, the Type LTC, like every mechanical 
device, deserves some care to ensure 
continued dependability and to protect the 
long serv ice life for which it was designed. 
When atten tion is required use only genuine 
Cash Valve replacement parts. 
Refer to the Type LTC Regulator cut 
away view for parts identification during 
maintenance procedures.

Servicing The Valve Pull Rod Packing (16)

The valve yoke nut should be kept tight. Should 
it become necessary to replace the pull rod 
packing proceed as follows:
1.    Remove the yoke assembly (9) from 

the valve body (19) by removing the 
yoke nut (13).

2.   Remove the spacer (14), female adapter (15), 

the two worn packing seals (16), and the 
male adapter (17).

3.   Replace the packing seals and reassemble 

in reverse order. Tighten the yoke 
nut securely.

Servicing the Thermal System 

The thermal system used on the Type LTC 
Temperature Regulator is serviced only as 
a complete assembly except for the bulb 
bush ing (2) and the bulb gasket (3). The 
thermal system is set at the factory to operate 
only at the temperature range stamped on 
the nameplate which is affixed to the bellows 
housing. If it is necessary to install a new 
thermal system, the procedure listed below 
should be followed.
1.  Shut off the vaporizer system.
2.   Completely loosen the bushing nut (5), then 

take the bulb (1) out of the bulb bushing (2).

3.   Turn the temperature adjustment wheel (10) 

to its lowest position (counter-clockwise).

4.    Remove the screws (8) retaining the bellows 

housing (7) to the yoke (9), then lift the 
housing from the yoke.

Note:

 The bellows housing (7) may be under slight 

spring tension. Exercise care when removing 
the housing.

5.   Position the new bellows housing (7) on top 

of the spring, aligning the screw holes in the 
housing with those in the yoke.

6.   Using three 10-32 x 1" screws inserted 

in alternate holes in the bellows flange, 
tighten the screws evenly to draw the 
bellows housing (7) down until it contacts 
the yoke (9). Install the shorter standard 
screws (8) in the remaining holes, then 
replace the 10-32 x 1" slave screws with the 
standard screws. 

Note:

 An alternative method of install ing the new 

bellows housing to the yoke would be to cool the 
thermal bulb to ap proximately -40°F (-40°C) allowing 
the bellows to contract and thereby permit ting the 
standard screws to be installed.

7.   Install the new thermal system bulb (1) in 

its original position and lighten the bulb 
bushing nut (5).

8.   Turn the temperature adjustment wheel 

clockwise to its original position or 
approximately .675 inches above the 
lowest position.

INSTALLATION INSTRUCTIONS

Type LTC Regulator is to be installed between 
the vaporizer and the service line (or final line) 
regulator. The valve should be installed in a 
horizontal position with the bellows housing 
upright. For other installation requirements 
consult the factory. For ease of operation and 
maintenance, it is suggested that manual 
shut-off valves be installed upstream and 
downstream from the valve. Before installing 
the valve,  the piping should be thoroughly 
flushed out to remove any foreign material. 
Install the valve so that the arrow cast on the 
valve body points in the direction of flow. Use 
a compatible sealant on the male pipe threads 
and do not over tighten the valve connections. 
Exercise care when tightening the unions to 
ensure that the gaskets located in the union 
ends are properly positioned.

Bulb Installation

Install the thermostatic bulb at a point that is 
downstream from the vaporizer but upstream 
from the temperature regulator. When a 
thermometer is to be installed in the line, it 
should be placed directly after the bulb in the 
pipe line or at the same level as the bulb in a 
tank. The standard bulb is shown in the cut 
away view of the valve. A copper well is strongly 
recommended for each cryogenic tempera ture 
regulator installation, both for the protection 
of tho bulb and to allow for the removal of 
the capillary bulb without depressurizing 
the system. 
To install the bulb, remove the bulb bushing 
from the bulb. Insert the bulb and fasten 
by tightening the nut onto the bushing. The 
preferred bulb installation position is with the 
end of the bulb below horizontal. Although the 
horizontal position is permissible, care must 
be exercised to NEVER INSTALL THE BULB 
WITH THE END OF THE BULB ABOVE THE 
BULB FLANGE. 

Note:

 The flexible armored capillary tubing connecting 

the bulb and valve must not be cut, kinked, mashed 
or twisted. II may, however, be bent on a 4" radius 
or larger. During installation the tubing can be 
fastened permanently to a rigid location, how ever, 
never connect the capillary tubing to steam pipes, 
cold water lines or other loca tions where the tubing 
would be subject to extreme temperatures. It is 
recommended that a single coil ot tubing be made 
next to the regulator to absorb vibrations occurring in 
the pipe lines.

Содержание CASH VALVES

Страница 1: ...is available as an option and is recommended for each cryogenic application MAXIMUM OPERATING LIMITS Operating temperature range is 0 to 40 F 17 to 40 C standard setting is 20 F 28 C Maximum temperature limit is 300 F 208 C minimum temperature limit is 320 F 195 C Maximum body pressure on all sizes is 400 psi 27 5 bar however for proper operation maximum pressure differentials as shown on page 3 m...

Страница 2: ...with those in the yoke 6 Using three 10 32 x 1 screws inserted in alternate holes in the bellows flange tighten the screws evenly to draw the bellows housing 7 down until it contacts the yoke 9 Install the shorter standard screws 8 in the remaining holes then replace the 10 32 x 1 slave screws with the standard screws Note An alternative method of install ing the new bellows housing to the yoke wo...

Страница 3: ... fully close valve DIMENSIONS Size Dimension A B C D E in mm in mm in mm in mm in mm in mm Note Also available Separable well contact factory for more information Thermal system repair kit contact factory for more information C A E B D NPTF 5 82 6 ft approx Dia HOW TO ORDER To order repair parts refer to the cut away view of the Type LTC Regulator to identify the part required When ordering please...

Страница 4: ...rvices described herein or their use or applicability All sales are governed by our terms and conditions which are available upon request We reserve the right to modify or improve the designs or specifications of such products at any time without notice Emerson Electric Co does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and...

Отзывы: