October 2019
Installation, Operation and Maintenance Manual
MAN-02-04-97-0713-EN Rev. 1
22
Installation
Section 3: Installation
Figure 26
3.9
Instructions For Explosion-proof Enclosures
NOTICE
The Bettis XTE3000 electric actuator shall be installed and maintained according to the
applicable rules regarding electrical installations in hazardous area (other than mines) classified
as zone 1 (gas); for example: EN 60079-10 (hazardous area classification), EN 60079-14
(electrical installation), EN 60079-17 (maintenance), and/or other national standards.
During the dismantling and subsequent reassembling of the explosion-proof enclosures
(covers, cable glands, joints), be careful to restore these enclosures back to their original
condition to maintain their integrity. In particular, ensure that the joint surfaces of all
enclosures are spread with a film of recommended grease (see Section 4, Lubrication).
Table 7.
Model
Motor
cover
Terminal
enclosure cover
Local interface
cover
Material
010
M8x30
M10x30
M10x35
AISI 316/ASME B16.11 A182-F316
(yield strength ≥ 450 N/mm² (65,266 psi)
020
M8x30
M10x30
M10x35
AISI 316/ASME B16.11 A182-F316
(yield strength ≥ 450 N/mm² (65,266 psi)
030
M10x35
M10x30
M10x35
AISI 316/ASME B16.11 A182-F316
(yield strength ≥ 450 N/mm² (65,266 psi)
040
M10x35
M10x30
M10x35
AISI 316/ASME B16.11 A182-F316
(yield strength ≥ 450 N/mm² (65,266 psi)
050
M12x45
M10x30
M10x35
AISI 316/ASME B16.11 A182-F316
(yield strength ≥ 450 N/mm² (65,266 psi)