November 2021
Installation, Operation and Maintenance Manual
VCIOM-15590-EN Rev. 0
Input and Output Data
12
Section 4: Input and Output Data
4.2.7
Status 3
Module number: 18
Hex
ID-byte: 50
Hex
(1 word AA / consistency 1 word)
Data format: 16-bit, error number
Table 10.
Error Code
Meaning
3
Motor temperature warning
4
Motor temperature cut-out
5
Phase sequence error or phase loss
9
Error in the power supply or the frequency converter
11
Error in the failsafe unit (provided there is one)
17
Fault, displacement potentiometer
22
Fault, torque potentiometer
Parameter P15.7 can be used to set alternative output functions for Status 3.
4.2.8
Status 4
Module number: 19
Hex
ID-byte: 50
Hex
(1 word AA / consistency 1 word)
Data format: 16-bit (bit field)
Reserved for future use.
Structure:
Table 11.
Bit no.
Function
Description
0 and 1
Channel Activity
Bit1
Bit0 Signal
0
0
Bus: Channel A active.
0
1
Bus: Channel B active.
1
0
Bus: Channel A and B active, main channel for inputs is channel A.
1
1
Bus: Channel A and B active, main channel for inputs is channel B.
2
Reserved
3
Reserved
4
Reserved
5
Reserved
6
Reserved
7
Reserved
8 and 9
PVST Status
Bit9
Bit8 Signal
0
0
PVST functionality not activated or no PVST realised yet.
0
1
PVST active: There is a PVST active currently.
1
0
PVST OK: The last PVST was successful.
1
1
PVST Error: The last PVST was not successful.
10
reserved
11
reserved
12
reserved
13
reserved
14
reserved
15
reserved
Parameter P15.6 can be used to set alternative output functions for Status 2.