Installation, Operation and Maintenance Manual 

VCIOM-17114-EN Rev. 1

August 2022

Bettis OM13 - SCE300

3-Wires Module

Содержание Bettis OM13-SCE300

Страница 1: ...Installation Operation and Maintenance Manual VCIOM 17114 EN Rev 1 August 2022 Bettis OM13 SCE300 3 Wires Module ...

Страница 2: ...Notes August 2022 Installation Operation and Maintenance Manual VCIOM 17114 EN Rev 1 This page intentionally left blank ...

Страница 3: ...odels 63 125 Nm Old Version US or Non US Market 4 2 2 Assembling Procedure for Models 250 500 1000 2000 Nm Old Version US or Non US Market 9 2 3 Assembling Procedure for Models 63 125 Nm New Version US or Non US Market 14 2 4 Assembling Procedure for Models 250 500 1000 2000 Nm New Version US or Non US Market 20 Section 3 OM13 Module Setting and Configuration OM13 Module Setting and Configuraton 2...

Страница 4: ...Notes August 2022 Installation Operation and Maintenance Manual VCIOM 17114 EN Rev 1 This page intentionally left blank ...

Страница 5: ...functionality 120 240 V AC 1 phase 50 60 Hz 3 wire control for open close operations without additional power supply NOTE For decommissioning instructions please refer to the relevant section in the SCE300 VCIOM 15516 EN NOTE The OM13 command has to be provided by two separate switches for open and for close with a delay of at least one second between the two commands when reversing the operation ...

Страница 6: ...onfiguration commissioning maintenance and repair works are carried out by qualified personnel and checked by responsible specialists WARNING Repair work other than operations outlined in this manual is strictly reserved to qualified Emerson personnel or to personnel authorized by the company itself 1 2 Manufacturer Manufacturer with respect to Machinery Directive 98 37 as specified on the SCE300 ...

Страница 7: ...with the OM13 are available as described in Section 4 Using Section 4 select only mechanical parts screws and spacers depending on actuator models Gather the right tools for the assembly and for setting the actuator controls With an Allen wrench of 5 mm unscrew the cover screws as shown in Figure 1 Remove the actuator cover as shown in Figure 2 Figure 2 Figure 1 Follow one of the following assembl...

Страница 8: ...erify that you received the correct OM13 3 wire module as shown in Figure 3 Remove the following as indicated in Figure 4 3 pins connector cable 4 pins connector cable 8 pins connector cable Figure 3 Figure 4 Remove the 3 wire power connector cable from the power card as indicated in Figure 5 Remove the 3 screws 3 pcs M3x10 from the logic board and screw the 3 metal spacers as shown in Figure 6 ...

Страница 9: ...v 1 August 2022 5 Installation Section 2 Installation Figure 5 Figure 6 Place the OM13 card onto the spacers and tighten the 4 screws as shown in Figure 7 Remove the 2 pins connector cable from J1 on the power card as shown in Figure 8 Figure 7 screws metal spacers ...

Страница 10: ...N Rev 1 6 Installation Section 2 Installation Figure 8 Connect the 2 wire power connector cable of the OM13 card to the power card as shown in Figure 9 Connect the 3 wire power connector cable of the terminal board to the OM13 card as shown in Figure 10 Figure 9 Figure 10 ...

Страница 11: ...ule to the logic card as shown in Figure 11 Reconnect the 8 pins connector cable and 4 pins connector cable as shown in Figure 12 Figure 11 Figure 12 Connect the 2 pins black connector from OM13 module to the 2 pins connector previously removed as shown in Figure 13 Connect the 2 pins connector black cable from the OM13 module to the power card as shown in Figure 14 ...

Страница 12: ...August 2022 Installation Operation and Maintenance Manual VCIOM 17114 EN Rev 1 8 Installation Section 2 Installation Figure 13 Figure 14 black cable ...

Страница 13: ...llation 2 2 Assembling Procedure for Models 250 500 1000 2000 Nm Old Version US or Non US Market Verify that you received the correct OM13 3 wire module as shown in Figure 15 Remove the following as indicated in Figure 16 3 pins connector cable 4 pins connector cable 8 pins connector cable Figure 15 Figure 16 ...

Страница 14: ...er card as shown in Figure 17 Remove the 2 pins connector cable from J1A on the logic card as shown in Figure 18 Figure 17 Figure 18 Connect the 3 wire power connector cable from the terminal board to the OM13 as shown in Figure 19 Place the OM13 card onto the heatsink spacers if necessary use 3 2 mm height plastic spacers and tighten the 4 screws as shown in Figure 20 ...

Страница 15: ...ust 2022 11 Installation Section 2 Installation Figure 19 Figure 20 Connect the 2 wire power connector cable of the OM13 card to the power card as shown in Figure 21 Reconnect the 8 pins connector cable and the 4 pins connector cable as shown in Figure 22 Figure 21 screw ...

Страница 16: ...Rev 1 12 Installation Section 2 Installation Figure 22 Connect the 3 pins connector cable of the OM13 module to the logic card as shown in Figure 23 Connect the 2 pins black connector from OM13 module to the 2 pins connector previously removed as shown in Figure 24 Figure 23 ...

Страница 17: ...nance Manual VCIOM 17114 EN Rev 1 August 2022 13 Installation Section 2 Installation Figure 24 Connect the 2 pins connector black cable from the OM13 module to connector J1A on the logic card as seen in Figure 25 Figure 25 black cable ...

Страница 18: ...Assembling Procedures for Models 63 125 Nm New Version US or Non US Market Verify that you received the correct OM13 3 wire module as shown in Figure 26 Remove the following as indicated in Figure 27 3 pins connector cable 4 pins connector white cable 4 pins connector black cable 8 pins connector cable Figure 26 Figure 27 ...

Страница 19: ...ion Figure 29 Remove the 3 wire power connector cable from the power card as indicated in Figure 28 Remove the 2 pins cable from connector on the power card as indicated in Figure 29 Remove the 3 screws from the logic board screw the 3 metal spacers and insert the plastic spacer as indicated in Figure 30 Figure 28 ...

Страница 20: ...lation Section 2 Installation Figure 30 Place the OM13 card onto the spacer and tighten the 3 screws as indicated in Figure 31 Connect the 2 wire power connector cable of the OM13 card to the power card as indicated in Figure 32 Figure 31 Figure 32 screws spacer plastic spacer metal spacer ...

Страница 21: ...nnector cable and 4 pins connector black cable as shown in Figure 33 Connect the 3 wire power connector cable of the terminal board to the OM13 card as shown in Figure 34 Figure 33 Figure 34 Reconnect the 4 pins connector cable as seen in Figure 35 Connect the 3 pins connector cable of the OM13 module to the logic card as shown in Figure 36 ...

Страница 22: ... 1 18 Installation Section 2 Installation Figure 35 Figure 36 Connect the 2 pins connector black cable from the OM13 module to the power card as seen in Figure 37 Connect the 2 pins black connector from OM13 module to the 2 pins connector previously removed as seen in Figure 38 ...

Страница 23: ...Installation Operation and Maintenance Manual VCIOM 17114 EN Rev 1 August 2022 19 Installation Section 2 Installation Figure 38 black cable Figure 37 ...

Страница 24: ...dure for Models 250 500 1000 2000 Nm New Version US or Non US Market Verify that you received the correct OM13 3 wire module as seen in Figure 39 Remove the following as indicated in Figure 40 2 pins connector cable 3 pins connector cable 4 pins connector white cable 4 pins connector black cable 8 pins connector cable Figure 39 Figure 40 ...

Страница 25: ... power card as seen in Figure 41 Screw the 3 spacers and unscrew the screw that fixes the motor cable as seen in Figure 42 Figure 41 Figure 42 Place the OM13 card onto the spacers and tighten the 4 screws as seen in Figure 43 Reconnect the 8 pins connector cable the 4 pins connector black cable and the 4 pins connector white cable as seen in Figure 44 spacers screw ...

Страница 26: ... EN Rev 1 22 Installation Section 2 Installation Figure 43 Figure 44 Connect the 3 wire power connector cable from the terminal board to the OM13 as seen in Figure 45 Connect the 2 wire power connector cable of the OM13 card to the power card as seen in Figure 46 screws ...

Страница 27: ...able of the OM13 module to the logic card as seen in Figure 47 Connect the 2 pins black connector from OM13 module to the 2 pins connector previously removed as seen in Figure 48 Connect the 2 pins connector black cable from the OM13 module to connector on the logic card as seen in Figure 48 The OM13 card is now connected Replace the actuator cover and fix it properly ...

Страница 28: ... 1 24 Installation Section 2 Installation Figure 47 Figure 48 NOTE Please note that all the connectors provided with the base actuator and all optional cards are different from each other in terms of design and number of pins In no way is it possible to make a wrong connection ...

Страница 29: ...n 3 OM13 Module Setting and Configuration For the SCE300 basic actuator settings please refer to the Installation Operation and Maintenance Manual The OM13 does not need any setting and configuration WARNING Do not electrically operate the SCE300 when the electrical enclosures are removed Operating the unit with the electrical enclosures removed could cause personal injury ...

Страница 30: ...t SCE300 models Depending on models only some spacers and screws has to be used Refer to Tables 1 and 2 and Figure 50 to choose the correct mechanical parts Figure 49 Table 1 SCE300 Cross Reference Table Non US Market Actuator model Old 63 125 Old 250 2K New 63 125 New 250 2K Product coding chart digit X7 X8 1 phase UV VU UV VU LV HV LV HV Product coding chart digit X7 X8 3 phase 31 32 33 31 32 33...

Страница 31: ...ence Table US Market Actuator model Old E006 E013 Old E025 E171 New E006 E013 New E025 E171 Product coding chart digit 6 1 phase 0 4 0 4 L H L H Product coding chart digit 6 3 phase 1 2 3 1 2 3 A B C A B C A 1 11 11 4 8 5 8 B 2 12 12 1 11 6 9 C 3 13 13 2 12 7 10 D 14 14 15 Figure 50 Points A B C and D to Fix the Board on Standard Group ...

Страница 32: ...uct Coding Chart Figures 51 54 allow to distinguish old version of SCE300 from the new version on the labels the digits of Product Number are boxed furthermore the logic boards with heatsink identifies old version models while logic boards without heatsink identifies new version models Figure 51 Label for Non Us Market Digits X7 X8 on product coding chart ...

Страница 33: ...Operation and Maintenance Manual VCIOM 17114 EN Rev 1 August 2022 29 OM13 Kit Section 4 OM13 Kit Figure 53 Example of SCE300 Old Version Heatsink Present Figure 54 Example of SCE300 New Version Heatsink Not Present ...

Страница 34: ...Note 1 Note 3 Ground NOTES 1 L1 L2 connection to open L2 L3 connection to close Supply from 110 to 240 V AC 1 ph L2 neutral 2 Contacts shown in intermediate position CLC1 CLC2 end of travel signaling in CLOSING Contacts shown in intermediate position OPC1 OPC2 end of travel signaling in OPENING 3 Internal heater max 10 watt is activated when a power supply from 110 to 240 V AC is connected to the ...

Страница 35: ...ng command line To avoid this unwanted effect realize a cabling system where unused line either L1 OPEN or L3 CLOSE is pulled to NEUTRAL line To do this a switch may be used For example with the BACO PN NC02GQ1 the following configuration may be used short circuit pins 1 and 3 short circuit pins 5 and 7 short circuit pins 2 and 8 short circuit pins 4 and 6 pin 3 PHASE pin 5 NEUTRAL L2 pin 2 OPEN L...

Страница 36: ...ness Estate East P O Box 6908 Greenstone 1616 Modderfontein Extension 5 South Africa T 27 11 451 3700 EUROPE Holland Fasor 6 Székesfehérvár 8000 Hungary T 36 22 53 09 50 Strada Biffi 165 29017 Fiorenzuola d Arda PC Italy T 39 0523 944 411 www emerson com bettis VCIOM 17114 EN CP 01495 2022 Emerson All rights reserved The Emerson logo is a trademark and service mark of Emerson Electric Co BettisTM ...

Отзывы: