Operating Instructions 

Control Modules FSE-0 

GB

Emerson Electric GmbH & Co. OHG 

Heerstr.111 –  D-71332 Waiblingen 

Tel.: 07151 509-0  -  Fax.: -200 

www.emersonclimate.eu

 

 

FSE Control Modules

 operate together with 

FSP 

Power Modules

 to control the speed of condenser 

fan motors according to pressure changes. Make 
sure that the motor is approved by the motor/unit 
manufacturer for variable speed by means of phase 
cutting (TRIAC). 

!

  Safety instructions: 

 

Read installation instructions thoroughly. 
Failure to comply may result in device failure, 
system damage or personal injury.  

 

It is intended for use by persons having the 
appropriate knowledge and skill. 

 

Before opening any system make sure pressure 
in system is brought to and remains at 
atmospheric pressure. 

 

FSE are factory set to a specific cut-off 
pressure. If adjustment is needed, refer to 
instructions for proper procedure. Improper 
adjustment may result in system damage or 
failure.  

 

Do not exceed safe working pressure. 

 

FSE are for use with FSP only. Do not connect 
to any other voltage supply. 

Mounting location:  

see Fig. 1: after condenser (1) before accumulator 
(2), preferred with pressure connection down. (3) = 
fan, (4) = evaporator, (5) = mains power supply  

Pressure connection:  

See Fig. 2 for thread connection. Use copper gasket 
(1).  
See Fig. 3 for solder connection. Use damp cloth (2) 
to keep housing temp. below 70°C while soldering. 

Electrical connection  

Use FSE-Nxx cable assembly (DIN 43650). Push 
plug slightly on the pins of control module. Only 
one direction possible see Fig. 4. No gasket required. 
Fasten screw with 0,05 Nm.  
Note: Plug can not be repaired. In case of failure 
replace connector. 

Leakage test: 

 

After completion of installation, a test pressure 
must be carried out as follows: 

- According to EN378 for systems which must 

comply with European pressure equipment 
directive 97/23/EC 

- To maximum working pressure of system for other 

applications 

Warning: 

1.

 

Failure to do so may result in loss of refrigerant 
and person injury.

 

2.

 

The pressure test must be conducted by skilled 
persons with due respect regarding the danger 
related to pressure. 

Setting 

FSE-0 Control Modules are factory preset for 2V 
output voltage if decreasing pressure / temperature 
falls below the value given in the table below.  
 

Factory Set Point 

Type 

Refrigerant 

Pressure bar  Temp. °C 

FSE-01_ 

R134a 

7.8 35 

FSE-02_ 

R22 

15.5 43 

FSE-02_ 

R407C 

15.5 37.5 

FSE-02_ 

R507 

15.5 36.5 

FSE-03_ 

R410A 

20.4 35 

For temperatures below these values FSP will stop 
fan motors (cut-off). 
For adjustment to other settings follow procedure 
below before mounting FSE (Numbers refer to Fig. 
5): 
Remove sealing cap (3). Insert enclosed  2mm allen 
key (2) into adjustment screw (1). Turn allen key 
clockwise (+) to increase, or counterclockwise (-) to 
decrease pressure setting. Do not turn adjustment 
screw 

more than 3 turns clockwise

 (+3).  

1 turn causes a pressure change of approximately 2.6 
bar. 

To readjust to factory setting, a pressure gauge, a 
constant voltage of 10 VDC and a DC volt meter is 
needed. Apply constant voltage between pin 2 (+) 
and pin 4 (-). Connect voltage meter between pin 1 
(+) and pin 4 (-). Apply pressure of  ~60% of 
maximum operating pressure PS, than decrease 
pressure slowly to the needed setpoint per table 
"Factory Set Point". Pressure should not be below 
setpoint at any time. Adjust voltage with adjustment 
screw (1) to 2 V. For confirmation decrease pressure 
to ~30% of  maximum pressure PS, than increase to 
~60% of PS, than decrease again slowly to setpoint. 
If necessary correct again with adjustment screw (1). 
After adjustment insert sealing cap (3) and make 
sure that it is properly fitted. IP65 protection 
requires firmly sealed plug.

  

 
Technical Data 

Supply voltage: 

10 VDC  

Output signal: 

0 … 10 V 

Max. medium temperature at 
pressure connection: 

70°C 

Ambient temperature range TS: 

-20°C … +65°C 

 Max. 

operating 

Pressure PS 

Test Pressure 

PT 

FSE-01_:  

27 bar 

30 bar 

FSE-02_:  

32 bar 

36 bar 

FSE-03_:  

43 bar 

48 bar 

Medium 
compatibility: 

HFC, HCFC 

Protection class: 

IP 65 according to EN 
60529/IEC 529 

Marking: 

 

 
 
 

Содержание ALCO CONTROLS FSE-0

Страница 1: ...sure of system for other applications Warning 1 Failure to do so may result in loss of refrigerant and person injury 2 The pressure test must be conducted by skilled persons with due respect regarding the danger related to pressure Setting FSE 0 Control Modules are factory preset for 2V output voltage if decreasing pressure temperature falls below the value given in the table below Factory Set Poi...

Страница 2: ... Systems für alle anderen Anwendungen Achtung 1 Bei Nichbeachten droht Kältemittelverlust und Verletzungsgefahr 2 Die Druckprüfung darf nur von geschultem und erfahrenem Fachpersonal durchgeführt werden Einstellung Die FSE 0 Steuerteile sind ab Werk folgendermaßen eingestellt Das Ausgangssignal von 2 V wird unterschritten wenn bei sinkendem Druck sinkender Temperatur die folgenden Werte unterschri...

Страница 3: ... 23 pour les autres applications respecter la pression maximum de test Avertissement 1 Le non respect de ces règles peut entraîner des pertes de fluides ou des blessures sur les personnes 2 Le test de pression doit être fait par des personnes qualifiées et informées du danger dû à la pression Réglages Le module FSE 0 est préréglé en usine pour une tension de sortie de 2V si la pression température...

Страница 4: ...jo del sistema para el resto de aplicaciones Atención 1 La omisión de este tipo de test podría repercutir en el futuro en pérdidas de refrigerante en el sistema o daños físicos a las personas 2 La prueba de presión deberá ser llevada a cabo únicamente por personal especializado Ajuste Los módulos de control FSE 0 se ajustan en fábrica para proporcionar una señal de salida de 2 V si la presión o la...

Страница 5: ...sione di lavoro del sistema per altre applicazioni Attenzione 1 La non osservanza potrebbe causare perdite di refrigerante e danni alle persone 2 La prova di tenuta deve essere effettuata da personale qualificato facendo attenzione ai rischi connessi alle alte pressioni Regolazione Il modulo FSE 0 è regolato in fabbrica per fornire un segnale in uscita pari a 2V se la pressione o la temperatura sc...

Страница 6: ...worden uitgevoerd Voor installaties welke dienen te voldoen aan het Europese Drukvaten Besluit 97 23 EC conform EN378 Voor overige installaties met de maximale bedrijfsoverdruk Waarschuwing 1 Het niet doorvoeren van een lektest kan leiden tot koudemiddelverlies 2 Lektest mag alleen worden doorgevoerd door gekwalificeerd en ervaren personeel Instellingen FSE 0 regel modules zijn febarieksmatig inge...

Страница 7: ...é jen v jedné poloze viz obr 1 a 2 Těsnění je součástí svorkovnice Utahovací moment šroubku je 0 05 Nm Poznámka Svorkovnice nelze opravovat musí se vyměnit celá sestava Zkouška těsnosti Po každé montáži je nutno prověřit těsnost systému Pro těsnostní zkoušky platí předpisy EN378 se vztahem na předpis pro tlakové nádoby 97 23 EC Jestliže systém neodpovídá zařazení dle uvedených norem provádí se zko...

Страница 8: ...nych zastosowań Ostrzeżenie 1 Niezastosowanie się do powyższych wymagań może spowodować ucieczkę czynnika chłodniczego i obrażenia ciała 2 Próba ciśnieniowa musi być przeprowadzona przez osoby wykwalifikowane przy odpowiednim uwzględnieniu niebezpieczeństwa związanego z ciśnieniem Ustawienia Moduły sterujące FSE 0 są nastawione fabrycznie na napięcie wyjściowe 2 V jeżeli ciśnienie temperatura spad...

Страница 9: ...sistemele care se incadreaza la Directiva European ptr echipamente sub presiune 97 23 EC La presiune maxima de lucru a sistemului ptr alte aplicatii Warning Atentie 1 Nerespectarea acestora poate duce la pierdere de refrigerant sau raniri de persoane 2 testul de presiune trebuie condus de persoane calificate constiente de pericolele legate da lucrul cu presiune Setare FSE 0 este presetat din fabri...

Страница 10: ... давлении для всех остальных случаев Внимание 1 Невыполнение данного требования может привести к утечкам хладагента и травмам персонала 2 Испытания давлением должны проводиться квалифицированным персоналом со всеми предосторожностями необходимыми при работе с оборудованием под давлением Настройка Управляющие модули FSE 0 имеют заводскую настройку на выходное напряжение 2В для падения давления темп...

Страница 11: ...0716136 FSE 0 Emerson Electric GmbH Co OHG Heerstr 111 D 71332 Waiblingen Tel 07151 509 0 Fax 200 www emersonclimate eu M 230VAC 50 60 Hz 5A 230VAC 50 60 Hz 5A Signal 0 10 V FSP xx0 FSE Nxx FSE 0xx 5 4 2 3 1 15 Nm 1 max 70 C 2 Fig 1 Fig 2 Fig 3 3 6 Fig 4 Fig 5 ...

Отзывы: