Type ACE95jr Tank Blanketing Valve

Introduction

 

 WARNING

Failure to follow these instructions or 

to properly install and maintain this 

equipment could result in an explosion, 

fire and/or chemical contamination 

causing property damage and personal 

injury or death.
Fisher™ Tank blanketing valves must 

be installed, operated and maintained 

in accordance with federal, state and 

local codes, rules and regulations 

and Emerson Process Management 

Regulator Technologies, Inc. 

(Emerson) instructions.
If the valve vents gas or a leak develops 

in the system, service to the unit may be 

required. Failure to correct trouble could 

result in a hazardous condition.
Installation, operation and maintenance 

procedures performed by unqualified 

personnel may result in improper 

adjustment and unsafe operation. Either 

condition may result in equipment 

damage or personal injury. Use qualified 

personnel when installing, operating 

and maintaining the Type ACE95jr Tank 

Blanketing Valve.

Scope of the Manual

This Instruction Manual provides installation, startup 

and maintenance procedures for the Type ACE95jr 

tank blanketing valve. See Figure 1.

Figure 1.

 Type ACE95jr Tank Blanketing Valve

Product Description

The Type ACE95jr tank blanketing valve is an 

extension of the Type ACE95 tank blanketing valve 

and is intended to handle lesser flows on gas 

blanketing systems. The valve prevents a stored 

product from vaporizing into the atmosphere, reduces 

product combustibility and prevents oxidation or 

contamination of the product by reducing its exposure 

to air. The Type ACE95jr maintains a slightly positive 

pressure and thereby reduces the possibility of tank 

wall collapse during pump out operations.

Содержание ACE95jr

Страница 1: ...y unqualified personnel may result in improper adjustment and unsafe operation Either condition may result in equipment damage or personal injury Use qualified personnel when installing operating and maintaining the Type ACE95jr Tank Blanketing Valve Scope of the Manual This Instruction Manual provides installation startup and maintenance procedures for the Type ACE95jr tank blanketing valve See F...

Страница 2: ...Valve Sizing 110 of rated Cv Cv 0 2 use Cv 0 22 Cv 0 4 use Cv 0 44 IEC Sizing Coefficients Xt 0 655 Fd 0 86 Fl 0 89 Temperature Capabilities 1 Nitrile NBR 20 to 180 F 29 to 82 C Fluorocarbon FKM 0 to 212 F 18 to 100 C Ethylenepropylene EPDM FDA 20 to 212 F 29 to 100 C Perfluoroelastomer FFKM 20 to 212 F 29 to 100 C Approximate Weight with all accessories 30 lbs 14 kg 1 The pressure temperature lim...

Страница 3: ... on these components therefore the outlet control pressure of the unit is not affected by fluctuating inlet pressure Installation WARNING Personal injury equipment damage or leakage due to escaping accumulated gas or bursting of pressure containing parts may result if this gas blanketing system is over pressured or installed where service conditions could exceed the limits given in the Specificati...

Страница 4: ...f foreign material Apply pipe compound only to the male pipe threads with a screwed body or use suitable line gaskets and good bolting practices with a flanged body 2 Inspect the nameplate on the upper actuator case It displays the model number serial number a blanketing gas supply pressure range the maximum inlet pressure set pressure and CV value These must agree with the system that you are bla...

Страница 5: ...e contact Emerson for alternate methods of installation A single array manifold is available for such situations Gauges and Shutoff Valves Inlet gas shutoff valves are desirable for servicing If this Type ACE95jr tank blanketing valve was not ordered with an inlet pressure gauge it is advisable to install a gauge between the inlet shutoff valve and the blanketing valve Note Safety considerations m...

Страница 6: ...pe Adhesive Loctite 222 Be certain that nameplates are updated to accurately indicate any field changes in equipment materials service conditions or pressure settings Monthly Maintenance 1 Visually inspect the unit to ensure tight connections tight seals and safe operation 2 Observe the blanketing pressure 3 Inspect the inlet pressure for the proper pressure stamped on the valve nameplate Annual M...

Страница 7: ...essure range Valve information is on the nameplate attached to the upper actuator case When performing disassembly or re assembly operations refer to Figure 6 for key numbers unless otherwise directed Disassembly WARNING To avoid personal injury resulting from sudden release of pressure isolate the valve from all pressure and cautiously release trapped pressure from the valve before attempting dis...

Страница 8: ...ppet from the piston and remove the rolling diaphragm key 38 Assembly When assembling the Type ACE95jr tank blanketing valve clean all parts inspect for unusual wear lightly lubricate all O rings and the groove that locates the rolling diaphragm bead See Figure 6 Cage Sub Assembly 1 Install the internal O rings key 16 into the body key 18 2 Place the rolling diaphragm key 38 over the threaded port...

Страница 9: ...screws key 55 with lock washers key 54 Tighten all uniformly 4 Place an O ring key 14 into the groove of the diaphragm bolt key 15 5 Build the diaphragm sub assembly with the diaphragm key 11 and two diaphragm plates keys 10 and 48 Fasten the plates together with the diaphragm bolt key 15 and the diaphragm retaining nut key 13 Apply Loctite 222 to the diaphragm bolt Note In cases where the pressur...

Страница 10: ... ring 2 required Nitrile NBR 1F115306992 Ethylenepropylene EPDM FDA 1F1153X0062 Fluorocarbon FKM 1F1153X0022 Perfluoroelastomber FFKM 1F1153X0032 18 Body CV 0 2 1 2 NPT GC052930X02 NPS 1 2 DN 15 CL150 RF GC052930X02 1 NPT GC052930X02 NPS 1 DN 25 CL150 RF GC052930X02 NPS 1 2 x 1 DN 15 x 25 CL150 RF GC052930X02 NPS 1 DN 25 Sanitary Flange GC052930X02 1 2 x 1 NPT GC052930X02 Body CV 0 4 1 2 NPT GC052...

Страница 11: ...0 32 27 55 54 162 L1 L1 L1 T T L1 L1 L1 L1 T APPLY LUBRICANT OR SEALANT 1 T THREAD LOCKER L1 GENERAL PURPOSE POLYTETRAFLUOROETHYLENE PTFE OR LITHIUM GREASE MAIN VALVE DETAIL 1 Lubricants must be selected such that they meet the temperature requirements Figure 6 Type ACE95jr Tank Blanketing Valve Assembly ...

Страница 12: ...ark owned by Fisher Controls International LLC a business of Emerson Automation Solutions The contents of this publication are presented for informational purposes only and while every effort has been made to ensure their accuracy they are not to be construed as warranties or guarantees express or implied regarding the products or services described herein or their use or applicability All sales a...

Отзывы: