background image

IM-IND-553130-RevAA

Installation & Maintenance Instructions 

3–WAY REDUNDANT DUAL SOLENOID–OPERATED PILOT VALVES 

NORMALLY CLOSED AND NORMALLY OPEN OPERATION 

BRASS AND/OR STAINLESS STEEL CONSTRUCTION

1/4” NPT – INSTRUMENT AIR SERVICE

SERIES 

8323G0XX

8323G3XX

Page 1 of 4

E316582 - 08/2021 

All Rights Reserved.  

IM-IND-553130-RevAA

No.  57,  Kundrathur  Main  Rd.,  Gerugambakkam,  Chennai  -  6000128,  India   

  www.emerson.com                                      

NOTICE: See separate solenoid installation and 

maintenance instructions for information on: Wiring, 

Solenoid Temperature, Causes of Improper Operation or 

Solenoid Replacement.

DESCRIPTION

Series 8323G0XX, and 8323G3XX are 3-way redundant dual 

solenoid-operated pilot valves designed for instrument air 

service. Valves are normally closed or normally open depending 

upon requirements.

Series 8323G0XX valves are supplied with a general purpose or 

a explosionproof/watertight solenoid enclosures.

Series 8323G3XX valves are provided with low power general 

purpose solenoid enclosures.

Operation Identification Chart 

(Operation vs Catalog Number)

Operation

Catalog Number / Construction

Normally Closed 

(See Note)

8323G051 / Brass

8323G052 / Stainless Steel

8232G351 / Brass

8323G352 / Stainless Steel

Normally Open 

(See Note)

8323G053 / Stainless Steel
8323G353 / Stainless Steel

NOTE: Normally closed pilot valves are used on ASCO no-

voltage release manual reset valves; normally open pilot valves 

are used on trip shut-off manual-reset valves.

OPERATION

Normally Closed (Pressure at Port 3)

Both Solenoids De-energized

: Flow is from Port 1 to Pilot 

Exhaust.

Either or Both Solenoids Energized

: Flow is from Port 3 to 

Port 1.

Normally Open (Pressure at Solenoid Pilot)

Both Solenoids De-energized

: Flow is from Pilot Press to Port 

1.

Either or Both Solenoids Energized

: Flow is from Port 1 to 

Port 3.

INSTALLATION

Check nameplate for correct catalog number, pressure, voltage, 

frequency, and service. Never apply incompatible fluids or 

exceed pressure rating of the valve. Installation and valve 

maintenance to be performed by qualified personnel.

Future Service Considerations

Provision should be made for performing seat leakage, external 

leakage, and operational tests on the valve with a non-hazardous, 

non-combustible fluid after disassembly and reassembly.

Temperature Limitations

For valve fluid and ambient temperature ranges, refer to chart 

below. Check catalog number on nameplate.

Catalog Number Fluid & Ambient Temperature Range

8323G051

8323G052

8323G053

AC Service

32 °F (0 °C) to 125 °F (52 °C)

DC Service

32 °F (0 °C) to 104 °F (40 °C)

8323G351

8323G352

8323G353

-40 °F (-40 °C) to 140 °F (60 °C)

Positioning

Valve may be mounted in any position.

Mounting

Refer to Figure l, for valve body mounting dimensions.

Содержание 8323G0 Series

Страница 1: ...teel 8323G353 Stainless Steel NOTE Normally closed pilot valves are used on ASCO no voltage release manual reset valves normally open pilot valves are used on trip shut off manual reset valves OPERATION Normally Closed Pressure at Port 3 Both Solenoids De energized Flow is from Port 1 to Pilot Exhaust Either or Both Solenoids Energized Flow is from Port 3 to Port 1 Normally Open Pressure at Soleno...

Страница 2: ...s part of routine maintenance or surveillance activities and no additional exercise is necessary The actual frequency of exercise necessary will depend on specific operating conditions A successful operating history is the best indication of a proper interval between exercise cycles Depending on the medium and service conditions periodic inspection of internal valve parts for damage or excessive w...

Страница 3: ...mped on the valve nameplate If the number of the kit is not visible order by indicating the number of kits required and the Catalog Number and Serial Number of the valve s for which they are intended Part Name Torques Values In Lbs Torque Value Nm Cartridge Assembly or Solenoid Base Sub Assembly 175 25 19 8 2 8 Torque Chart Figure 2 Redundant Pilot Operator Assembly Series 8323G051 and 8323G052 Fi...

Страница 4: ...Page 4 of 4 All Rights Reserved IM IND 553130 RevAA No 57 Kundrathur Main Rd Gerugambakkam Chennai 6000128 India www emerson com Figure 5 Redundant Pilot Operator Assembly Series 8323G353 ...

Отзывы: