Emerson specs a wall-mounted relative humidity (RH) sensor
(P/N 203-5751) and combined RH and temperature sensor 
(P/N 203-5752) for use in building control and anti-sweat control 
applications using Emerson input boards.

Specifications

INPUT POWER

Voltage

Class 2; 12 to 24 Vdc or 24 Vac

AC Voltage Tolerance

±10%

AC Frequency

50/60 Hz

OUTPUT

Voltage Output

0 to 5 V or 0 to 10 V (jumper selectable)

Voltage Min. Load Resistance

5 kΩ

Voltage Min. Sinking Current

0.2 mA

HUMIDITY

RH Element

Digitally profiled thin-film capacitive, non-removable

Accuracy

3% (10 to 90% RH, 20 to 30 °C)

Temperature Effect (Outside 20° to 30°C)

0.1% RH per °C

Response Time (to 90% change at 20°C)

110 sec

Annual Drift

≤1%

Humidity (RH) and Temperature Sensor

Wall-mounted RH Sensor and 
RH/Temperature Sensor

Installation Guide

Содержание 203-5751

Страница 1: ...plications using Emerson input boards Specifications INPUT POWER Voltage Class 2 12 to 24 Vdc or 24 Vac AC Voltage Tolerance 10 AC Frequency 50 60 Hz OUTPUT Voltage Output 0 to 5 V or 0 to 10 V jumper selectable Voltage Min Load Resistance 5 kΩ Voltage Min Sinking Current 0 2 mA HUMIDITY RH Element Digitally profiled thin film capacitive non removable Accuracy 3 10 to 90 RH 20 to 30 C Temperature ...

Страница 2: ...ctor as shown in the image below Clip the SHIELD wire 3 Connect the SHIELD and BLACK wires to the 0V terminal of the input board Connect the WHITE wire to the SIG terminal of the input board 4 Connect the RED wire to the 12V power terminal on the input board Output Scaling 0 to 100 RH TEMPERATURE OPTION Sensor Type Thermistor 10k Ohm OPERATING ENVIRONMENT Operating Temperature 0 to 50 C 32 to 122 ...

Страница 3: ...t to the OFF position LEFT for MultiFlex DOWN for 16AI Refer to the input board s user manual for locations of the input dip switches Temperature models only Operations Emerson wall mounted humidity sensors measure the levels of RH and temperature if equipped in the air inside a room To maintain accurate functionality keep all pickup vents clear and free of dust debris etc LEGEND RTD RTD T RTD RTD...

Страница 4: ...ocument may be photocopied for personal use Visit our website at www climate emerson com for the latest technical documentation and updates Dimensions Installation 1 Remove the cover by pressing the tab on the bottom of the sensor while pulling outward on the bottom edge of the cover ...

Страница 5: ...use Visit our website at www climate emerson com for the latest technical documentation and updates 2 Position the sensor vertically on the wall 4 feet 1 5 m above the floor Place so that the Install This End Up statement on the board is in the upper right corner 3 Mount the backplate onto the wall using the screws provided ...

Страница 6: ...tional purposes only and they are not to be construed as warranties or guarantees express or implied regarding the products or services described herein or their use or applicability Emerson reserves the right to modify the designs or specifications of such products at any time without notice Responsibility for proper selection use and maintenance of any product remains solely with the purchaser a...

Отзывы: