Figure 9-1: System Settings>Gateway>Redundancy
5. Select
Redundant
in the Redundant Mode section.
6. Do this process for Gateway B as well.
The Gateway serial number will be used in diagnostic messages and host system
integration to help identify each Gateway. It is recommended that these numbers be
marked on each physical Gateway, in addition to the configuration settings.
Selecting left or right for Gateway A is for visualization purposes only. It has no effect on
performance or functionality.
After the redundancy system settings have been configured, the two Gateways must be
connected and undergo a pairing process.
To pair both Gateways and form a redundant system:
1. Connect a PC/laptop to the primary Ethernet port on Gateway A.
2. Log in using the admin user account.
3. Navigate to
System Settings>Gateway>Redundancy Status.
4. Connect the secondary Ethernet port on Gateway A to the secondary Ethernet port
on Gateway B (see
, Redundancy Setup Connections).
5. After a few minutes, a dialog will appear on the page; select Form redundant pair.
6. Wait for the Pairing to redundant peer status to turn green.
Appendix C
Reference Manual
February 2019
00809-0500-4410
56
Emerson.com/Rosemount
Содержание 1410H
Страница 6: ...Introduction Reference Manual February 2019 00809 0500 4410 6 Emerson com Rosemount ...
Страница 30: ...Installation Reference Manual February 2019 00809 0500 4410 30 Emerson com Rosemount ...
Страница 40: ...Operation and Maintenance Reference Manual February 2019 00809 0500 4410 40 Emerson com Rosemount ...
Страница 46: ...Troubleshooting Reference Manual February 2019 00809 0500 4410 46 Emerson com Rosemount ...
Страница 48: ...Appendix A Reference Manual February 2019 00809 0500 4410 48 Emerson com Rosemount ...
Страница 65: ...Reference Manual 00809 0500 4410 February 2019 Emerson com Rosemount 65 ...