INSTALLATION & ASSEMBLY INSTRUCTIONS
Introduction to Refrigerants R32

10

The maximum charge and the required minimum floor area 

3

3

3

m

 = (4 

m

) x 

LFL , m

 = (26 

m

)) x 

LFL,  m

 = (130 

m

 )x 

LFL

1

2

3

3

3

Where 

LFL 

is the lower flammable limit in kg/ 

m

, R32 LFL is 0.306 kg/ 

m .

For the appliances with a charge amount 

m

 < 

M m

:

1

2

(5/4)

1/2

The maximum charge in a room shall be in accordance with the following:

m

= 2. 5 x (

LFL

)

 

h

 x (

A

)

max

0

The required minimum floor area 

A

min to install an appliance with refrigerant charge 

(kg)

(5/4) 2

shall be in accordance with following: 

A

 = (

M

/ (2.5 x (

LFL

)

h

)) 

min

0

Where:

m

 is the allowable maximum charge in a room, in kg;

max

is the refrigerant charge amount in appliance, in kg;

A

min is the required minimum room area, in m2;

2

is the room area, in m ;

3

LFL 

is the lower flammable limit, in kg/m ;

h

 is the installation height of the appliance, in meters for calculating 

m

 or 

A

, 1.8 m for wall mounted;

0

max

min

Table GG.1  Maximum charge (kg)

Category

LFL

(kg/m )

h

0

(m)

2

Floor area

(m )

Category

LFL

(kg/m )

h

0

(m)

Charge amount (

M

( kg)

2

Minimum room area

(m )

2

Table GG.2  Minimum room area (m )

Before installing the appliance, you must read the manual carefully to get the safety 
information and notes.
When filling the combustible refrigerant, any of your rude operations may cause serious 
injury or injuries to human body or bodies and object or objects.
A leak test must be done after the installation is completed.
It is a must to do the safety inspection before maintaining or repairing an air conditioner 
using combustible refrigerant in order to ensure that the fire risk is reduced to minimum.
It is necessary to operate the machine under a controlled procedure in order to ensure 
that any risk arising from the combustible gas or vapor during the operation is reduced to 
minimum.
Requirements for the total weight of filled refrigerant and the area of a room to be equipped 
with an air conditioner (are shown as in the following Tables GG.1 and GG.2)

Содержание 10000 BTU

Страница 1: ...1 1 PANTONE Cool Gray 10 CVC PANTONE 653 CVC 10 BLACK 20 BLACK ...

Страница 2: ... Electronic Window Air Conditioner Thank you very much for purchasing our air conditioner Please read this owner s manual carefully before using your air conditioner 6 000 BTU 8 000 BTU 10 000 BTU 12 000 BTU ...

Страница 3: ......

Страница 4: ......

Страница 5: ...INSTRUCTIONS PACKING LIST INSTALLATION ASSEMBLY INSTRUCTIONS USING YOUR AIR CONDITIONER CARE AND CLEANING TROUBLESHOOTING INTRODUCTION TO REFRIGERANTS R32 ELECTRICAL REQUIREMENTS OPERATING YOUR AIR CONDITIONER 1 2 3 4 5 12 14 15 16 ...

Страница 6: ...itions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation Any Changes or modifications not expressly approved by the party responsible for compliance could void the user s authority to operate the equipment ...

Страница 7: ...tinuously operating sources for example open flames an operating ignition gas appliance or an operating electric heater Please contact the nearest after sale service center when maintenance is necessary At the time of maintenance the maintenance personnel must strictly comply with the Operation Manual provided by the corresponding manufacturer and any non professional is prohibited to maintain the...

Страница 8: ...3 6K 8K 0 8 amps 10K 12K 0 12 amps 6K 8K 10 amp 10K 12K 15 amp ...

Страница 9: ...4 ...

Страница 10: ...5 FIG 1 FIG 2 0 8 OFFSET STOOL SILL INTERIOR WALL EXTERIOR WALL OFFSET STOOL SILL INTERIOR WALL EXTERIOR WALL ...

Страница 11: ...6 Only used for 6K 8K Head 6K 8K 10K 12K ...

Страница 12: ...7 FIG 3 3 FIG 4 FIG 5 Head ...

Страница 13: ...8 Suggest to keep a downward to let accumulated rain water to drain out from back side of the unit bottom angle FIG 6 FIG 7 FIG 8 FIG 9 FIG 10 FIG 11 FIG 12 FIG 13 ...

Страница 14: ...9 FIG 14 ...

Страница 15: ...m or A 1 8 m for wall mounted 0 max min Table GG 1 Maximum charge kg Category LFL 3 kg m h0 m 2 Floor area m Category LFL 3 kg m h0 m Charge amount M kg 2 Minimum room area m 2 Table GG 2 Minimum room area m Before installing the appliance you must read the manual carefully to get the safety information and notes When filling the combustible refrigerant any of your rude operations may cause seriou...

Страница 16: ...ropriate anti static measures such as wear anti static clothing and or gloves 4 It is necessary to choose the site convenient for installation or maintenance wherein the air inlets and outlets of the indoor and outdoor units should be not surrounded by obstacles or close to any heat source or combustible and or explosive environment 5 If the indoor unit suffers refrigerant leak during the installa...

Страница 17: ...op time The display will show the time your machine will automatically turn on To cancel the set function press the TIMER button again 5 Timer Button Cool Mode The cooling function allows the air conditioner to cool the room and at the same time reduces humidity Press the MODE button to activate the cooling function To optimize this function adjust the temperature by pressing the up and down arrow...

Страница 18: ...ically adjust the temperature and fan speed to make the room more comfortable during the night The set temperature will automatically raise every 30 60 minutes and at most change sixtimes until the set temperature is 81 or 82 7 Sleep Button Press the FAN SPEED button to select the fan speed In COOL MODE you can choose the following settings HI MED LO or AUTO In FAN MODE you can choose from HI MED ...

Страница 19: ...e unit will turn off once the room is cooled to the user set temperature The unit will turn back on when the room temperature rises above the user set temperature Before the compressor stars the fan motor will keep running for a while and stop for a while and again to provide much more comfortable feeling and save the energy ECO Use these buttons on the control panel and remote to set the Timer Ti...

Страница 20: ...The Check Filter light will automatically turn on after the fan motor has been in operation for a total of 500 hours 15 FIG 15 15 ...

Страница 21: ...16 ...

Страница 22: ...17 For any questions or Technical Support Please Call Customer Service 1 844 801 8880 ...

Страница 23: ......

Страница 24: ......

Страница 25: ......

Отзывы: