background image

Lux-Ray LED - Emergency lighting

Emergi-Lite

Tel: (888) 552-6467 

Fax: (800) 316-4515

www.emergi-lite.com

02/13 750.1712 Rev. A

2/2

6. Close the inside cover and tighten the screw.

7. Remove the unit housing from the package. Units with DC-

remote power: go to step 8 (see figure 3).

a.   Units with battery back-up: plug the battery connector in the 

slot. The connector is polarized, do not force-fit . Correct 
installation has the positive red wire at the left (see figure 3).

b.  Units with dual AC circuit: connect the orange wire labeled 

“VOLTAGE SELECTOR” to one of the two wires labeled AC 
VOLTAGE  (black: 120V; orange: 277V). Cap the unused 
wire with a wire connector.

8. Hook the security wire to the backplate and tighten the screw 

(see figure 3).

9. Align the unit housing over the back plate and press until it 

snaps in place (see figure 4).

10. Energize the circuits. Units with battery back-up will have the 

test button illuminated. 

     

Testing the emergency lights

Allow the unit to charge for 24 hours before testing. Press the test 
button. The unit will light in emergency mode for one minute. To 
abandon the test press the test button again.

Testing the normal lighting

Turn the AC power on: the unit will light.  
Units equipped with photo-switch: mask the small circular window 
with the finger: the unit will light. Uncover the window: when 
exposed to ambient light the unit will turn off.

Maintenance

None required.  

WARNING:

 Hold the housing in your hand and open the unit with a 

flat head screwdriver. When replacing the housing assembly 

ALWAYS hook and tighten the security wire.

 

Disconnect the battery if the emergency power supply is disabled 
for two months or more.

Self-diagnostics / self-test (battery units)

1. Once supplied with power the unit will automatically initiate self-

diagnostic routines and a self-test calendar as follows:

a.   Verifies battery connection, battery failure, charger board 

failure and lamps failure.

b. Executes one-minute monthly self-test.

c. Executes a 30-minute self-test every 6th month.

d. Executes a 90-minute self-test every 12th month.

 

2. The LED pilot light is bi-color and indicates the following status:

a.   Green color: AC-on / self-test  

b. Red color: Service alert (see figure 5)

3. Transfer time delay (TD option)
This function acts when the AC power was restored: it keeps the 
emergency lights "on" for a period of: 5, 10 or 15 minutes (factory-
set). If the battery depletes before the end of the time delay, the 
lamps turn off and the unit goes in stand-by mode.

Battery

Backplate

Housing

+

-

Hook and tighten the security wire

Figure 3

Connect 
battery

  Figure 4

Housing

Back plate

Steady on

Battery 

Two Blinks

Charger Failure

Three Blinks

Lamp Failure

Battery Failure

One Blink

red

red

red

red

green

Blinking

Testing Mode

Steady

AC On

green

Disconnect

Figure 5

      

Отзывы: